EHBH/X16
Daikin Altherma - Low Temperature Split
4P313776-1 – 2012.05
Installer reference guide
50
8 Configuration
Power consumption control
Only applicable for EHBH/X04+08 + EHVH/X04+08. See
"5 Application guidelines" on page 6 for detailed information about
this functionality.
Pwr consumpt. control
Note: power consumption control only based on heater priority is
possible for EHBH/X04+08 and EHVH/X04+08 models, but also for
EHBH/X16CA and EHVH/X16 models. Hereto you can limit the
operation of both electrical heaters (backup heater and booster
heater) by the following setting.
#
Code
Description
N/A
[E-08]
Power saving function for outdoor unit:
Q
0 (default): Disabled
Q
1: Enabled
#
Code
Description
[A.6.3.1]
[4-08]
Mode:
Q
0 (No limitation)(default): Disabled.
Q
1 (Continuous): Enabled: You can
set one power limitation value (in A
or kW) to which the system power
consumption will be limited for all
the time.
Q
2 (Digital inputs): Enabled: You
can set up to four different power
limitation values (in A or kW) to
which the system power
consumption will be limited when
the corresponding digital input
asks.
[A.6.3.2]
[4-09]
Type:
Q
0 (Current): The limitation values
are set in A.
Q
1 (Power)(default): The limitation
values are set in kW.
[A.6.3.3]
N/A
Value: Only applicable in case of full
time power limitation mode.
0~50 A, step 1 A (default: 50 A)
[A.6.3.4]
N/A
Value: Only applicable in case of full
time power limitation mode.
0~20 kW, step 0.5 kW (default: 20 kW)
Amp. limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on current values.
[A.6.3.5.1]
[5-05]
Limit DI1
0~50 A, step 1 A (default: 50 A)
[A.6.3.5.2]
[5-06]
Limit DI2
0~50 A, step 1 A (default: 50 A)
[A.6.3.5.3]
[5-07]
Limit DI3
0~50 A, step 1 A (default: 50 A)
3x
1 2 3
[A.6.3.5.4]
[5-08]
Limit DI4
0~50 A, step 1 A (default: 50 A)
kW limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on power values.
[A.6.3.6.1]
[5-09]
Limit DI1
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.2]
[5-0A]
Limit DI2
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.3]
[5-0B]
Limit DI3
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.4]
[5-0C]
Limit DI4
0~20 kW, step 0.5 kW (default: 20 kW)
Priority: Only applicable in case of an optional EKHW*.
[A.6.3.7]
[4-01]
Q
0 (None)(default): No heater is
prioritized. If the power
consumption control is enabled,
the booster heater will be limited
first.
Q
1 (BSH): The booster heater is
prioritized. If the power
consumption control is enabled,
the backup heater (step 1 and/or
step 2) will be limited first, before
the booster heater is limited.
Q
2 (BUH): The backup heater is
prioritized. If the power
consumption control is enabled,
the booster heater will be limited
first, before the backup heater is
limited.
#
Code
Description
[A.6.3.7]
[4-01]
Q
0 (None)(default): No heater is
prioritized. If the power
consumption control is enabled,
the booster heater will be limited
first.
Q
1 (BSH): The booster heater is
prioritized. If the power
consumption control is enabled,
the backup heater (step 1 and/or
step 2) will be limited first, before
the booster heater is limited.
Q
2 (BUH): The backup heater is
prioritized. If the power
consumption control is enabled,
the booster heater will be limited
first, before the backup heater is
limited.
#