EHBH/X16
Daikin Altherma - Low Temperature Split
4P313776-1 – 2012.05
Installer reference guide
32
8 Configuration
5
Select the required action:
6
The user interface requests confirmation if you are sure to
proceed.
7
Confirm the selection on the screen by pushing
and all data
(languages, schedules etc.) will be synchronised from the
selected source user interface to the other one.
8
Your system is now set to be operated by the two user
interfaces.
8.1.4 To copy the language set from the first to the
second user interface
See "8.1.3 To copy the system settings from the first to the second
user interface" on page 31.
8.1.5 Quick wizard: Set the system layout after
first power ON
After first power ON of the system, you are guided on the user
interface to do initial settings:
Q
language,
Q
date,
Q
time,
Q
system layout.
By confirming the system layout, you can proceed with the
installation and commissioning of the system.
1
At power ON, the quick wizard starts as long as the system
layout was NOT confirmed yet, by setting the language.
2
Set the current date and time.
3
Set the system layout settings: Standard, Options, Capacities.
For more details, see Basic configuration.
4
Confirm by pressing
.
5
The user interface re-initialises and you can proceed the
installation by setting the other applicable settings and
commissioning of the system.
When the installer settings are changed, the system will request to
confirm. When confirmation is complete, the screen will shortly turn
OFF and "busy" will be displayed for several seconds.
8.2
Basic configuration
8.2.1 Quick wizard: Language / time and date
8.2.2 Quick wizard: Standard
Backup heater configuration (only for *9W model)
The backup heater in a *9W model is adapted to be connected to
most common European electricity grids. Besides hardware
configuration, the backup heater type must be set on the user
interface.
Q
Send data: the user interface you are operating contains
the correct data and the data on the other user interface will
be overwritten.
Q
Receive data: the user interface you are operating doesn’t
contain the correct data and the data on the other user
interface will be used to overwrite.
INFORMATION
Q
During the copying, both controllers display Busy and
will not be possible to operate. Please do not power off
or disconnect the user interface.
Q
The copy operation can take uptil 90 minutes.
#
Code
Description
[A.1]
N/A
Language
[1]
N/A
Time and date
#
Code
Description
[A.2.1.5]
[5-0D]
BUH type:
Q
1 (1P,(1/1+2)): 3 kW 1~ 230 V (*9W)
Q
3 (3P,(1/1+2)): 6 kW 3~ 230 V (*9W)
Q
4 (3PN,(1/2)): 6 kW 3N~ 400 V
(*9W)
Q
5 (3PN,(1/1+2)): 9 kW 3N~ 400 V
(*9W)