
EHBH/X16
Daikin Altherma - Low Temperature Split
4P313776-1 – 2012.05
Installer reference guide
12
5 Application guidelines
Configuration
Benefits
Q
Comfort.
Q
The smart room thermostat functionality can decrease or
increase the desired leaving water temperature based on
the actual room temperature (modulation).
Q
The combination of the two heat emitter systems provides
the excellent heating comfort of the under floor heating, and
the excellent cooling comfort of the heat pump convectors.
Q
Efficiency.
Q
Depending on the demand, the indoor unit supplies
different leaving water temperature matching the design
temperature of the different heat emitters.
Q
Under floor heating has the best performance with
Altherma LT.
5.3
Setting up an auxiliary heat source for space
heating
Q
Space heating can be done by:
Q
The indoor unit
Q
An auxiliary boiler (field supply) connected to the system
Q
When the room thermostat requests heating, the indoor unit or
the auxiliary boiler starts operating depending on the outdoor
temperature (status of the changeover to external heat source).
When the permission is given to the auxiliary boiler, the space
heating by the indoor unit is turned OFF.
Q
Bivalent operation is only possible for space heating, NOT for
domestic hot water production. Domestic hot water is always
produced by the DHW tank connected to the indoor unit.
Setup
Q
Integrate the auxiliary boiler as follows:
Q
Make sure the return water to the heat pump does NOT exceed
55°C. To do so:
Q
Set the desired water temperature via the auxiliary boiler
controller to maximum 55°C.
Q
Install an aquastat valve in the return water flow of the
heat pump.
Q
Set the aquastat valve to close above 55°C and to open
below 55°C.
Q
Install non-return valves.
Q
Make sure to only have one expansion vessel in the water
circuit. An expansion vessel is already is already premounted in
the indoor unit.
Setting
Value
Unit temperature control:
Q
#: [A.2.1.7]
Q
Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Note:
Q
Main room = user interface
used as room thermostat
functionality
Q
Other rooms = external
room thermostat
functionality
Number of water temperature
zones:
Q
#: [A.2.1.8]
Q
Code: [7-02]
1 (2 LWT zones): Main +
additional
In case of heat pump convectors:
External room thermostat for the
additional
zone:
Q
#: [A.2.2.5]
Q
Code: [C-06]
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition. No separation
between heating or cooling
demand.
Shut-off valve output
Set to follow the thermo demand
of the main zone.
Shut-off valve
If the main zone must be shut off
during cooling mode to prevent
condensation on the floor, set it
accordingly.
At the mixing valve station
Set the desired main leaving
water temperature for heating
and/or cooling.
INFORMATION
Q
During heating operation of the heat pump, the
heat pump operates to achieve the desired
temperature set via the user interface. When weather-
dependent operation is active, the water temperature
is determined automatically depending on the outdoor
temperature.
Q
During heating operation of the auxiliary boiler, the
auxiliary boiler operates to achieve the desired water
temperature set via the auxiliary boiler controller.
a
Outdoor unit
b
Indoor unit
c
Heat exchanger
d
Backup heater
e
Pump
f
Shut-off valve
g
Motorised 3-way valve (delivered with DHW tank)(field
supply)
h
Non-return valve
i
Shut-off valve
j
Collector (field supply)
k
Auxiliary boiler (field supply)
l
Aquastat valve (field supply)
m
DHW tank (option)
n
Heat exchanger coil
FHL1...3
Under floor heating
NOTICE
Q
Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
Q
Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
a
b c
d e
f
g
h
j
FHL1
FHL2
FHL3
M
h
i
i
l
k
f
m
n
Содержание ERLQ011CA
Страница 83: ......
Страница 84: ...4P313776 1 2012 05 Copyright 2012 Daikin ...