15 Technical data
Installer reference guide
98
ERLQ004~008CA + 08S18CA3VF
Daikin Altherma low temperature split
4P3662261 – 2014.01
15.7
ESP curve
15.7.1
ESP curve: indoor unit
Only for EHVH04S18CA3VF
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
A (kPa)
0 2 4 6 8 10 12 14 16 18 20 22 24 26
B (l/min)
Only for EHVH08S18CA3VF
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
A (kPa)
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34
B (l/min)
A
External static pressure available at space heating/cooling circuit
B
Water flow rate: water flow through space heating/cooling circuit
Note
1:
Selecting a flow outside the area of operation can cause
damage or malfunction of the unit. See also minimum and maximum
allow water flow range in the technical specifications.
Note
2:
Water quality MUST be according to EN directive
EC98/83EC.
Содержание ERLQ004CAV3
Страница 99: ...1 8 Field settings table Applicable indoor units EHVH04S18CA3VF EHVH08S18CA3VF Notes 4P366223 1 2014 02 ...
Страница 100: ...2 8 ...
Страница 107: ......
Страница 108: ...4P366226 1 2014 01 Copyright 2014 Daikin ...