8
Configuration
Installer reference guide
51
ERLQ004~008CA + 08S18CA3VF
Daikin Altherma low temperature split
4P3662261 – 2014.01
NOTICE
The preset leaving water temperatures are ONLY
applicable for the main zone, as the schedule for the
additional zone consists of On/OFF actions.
NOTICE
Select preset leaving water temperatures in accordance
with the design and selected heat emitters to ensure the
balance between desired room and leaving water
temperatures.
#
Code
Description
Preset leaving water temperature for the main leaving water
temperature zone in case of NOT weather dependent
[7.4.2.1]
[809]
Comfort (heating)
[901]~[900] (default: 35°C)
[7.4.2.2]
[80A]
Eco (heating)
[901]~[900] (default: 33°C)
Preset leaving water temperature (shift value) for the main leaving
water temperature zone in case of weather dependent
[7.4.2.5]
N/A
Comfort (heating)
−10~+10°C (default: 0°C)
[7.4.2.6]
N/A
Eco (heating)
−10~+10°C (default: −3°C)
Temperature ranges (leaving water temperatures)
The purpose of this setting is to prevent selecting a wrong (i.e. too
hot) leaving water temperature. Thereto the available desired
heating temperature range can be configured.
NOTICE
In case of a floor heating application it is important to limit
the maximum leaving water temperature at heating
operation according to the specifications of the floor
heating installation.
NOTICE
▪ When adjusting the leaving water temperature ranges,
all desired leaving water temperatures are also
adjusted to guarantee they are between the limits.
▪ Always balance between the desired leaving water
temperature with the desired room temperature and/or
the capacity (according to the design and selection of
the heat emitters). The desired leaving water
temperature is the result of several settings (preset
values, shift values, weather dependent curves,
modulation). As a result, too high or too low leaving
water temperatures could occur which lead to
overtemperatures or capacity shortage. By limiting the
leaving water temperature range to adequate values
(depending on the heat emitter), such situations can be
avoided.
Example:
Set the minimum leaving water temperature to 28°C to
avoid NOT to be able to heat up the room: leaving water
temperatures must be sufficiently higher than the room temperatures
(in heating).
#
Code
Description
Leaving water temperature range for the main leaving water
temperature zone (= the leaving water temperature zone with the
lowest leaving water temperature in heating operation)
[A.3.1.1.2.2] [900]
Maximum temp (heating)
37~depending on outdoor unit (default:
55°C)
[A.3.1.1.2.1] [901]
Minimum temp (heating)
15~37°C (default: 25°C)
Leaving water temperature range for the additional leaving water
temperature zone (= the leaving water temperature zone with the
highest leaving water temperature in heating operation)
[A.3.1.2.2.2] [906]
Maximum temp (heating)
37~depending on outdoor unit (default:
55°C)
[A.3.1.2.2.1] [905]
Minimum temp (heating)
15~37°C (default: 25°C)
Leaving water temperature overshoot temperature
This function defines how much the water temperature may rise
above the desired leaving water temperature before the compressor
stops. The compressor will startup again when the leaving water
temperature drops below the desired leaving water temperature.
This function is ONLY applicable in heating mode.
#
Code
Description
N/A
[904]
1~4°C (default: 1°C)
Leaving water temperature compensation around 0°C
In heating operation, the desired leaving water temperature is locally
increased around an outdoor temperature of 0°C. This
compensation can be selected when using an absolute or a weather
dependent desired temperature (see illustration below). Use this
setting to compensate for possible heat losses of the building due to
the evaporation of melted ice or snow (e.g. in cold region countries).
T
t
T
A
R
L
0°C
T
t
T
A
R
L
0°C
a
b
a
Absolute desired LWT
b
Weather dependent desired LWT
#
Code
Description
N/A
[D03]
▪ 0 (disabled) (default)
▪ 1 (enabled) L=2°C,
R=4°C (−2°C<T
A
<2°C)
▪ 2 (enabled) L=4°C,
R=4°C (−2°C<T
A
<2°C)
▪ 3 (enabled) L=2°C,
R=8°C (−4°C<T
A
<4°C)
▪ 4 (enabled) L=4°C,
R=8°C (−4°C<T
A
<4°C)