4 Unit installation
Installation manual
7
ELSH/X(B)12P30+50E
Daikin Altherma 3 R MT ECH
₂
O
4P708484-1 – 2023.03
4.1.3
Installation patterns
Depending on the type of room in which you install the indoor unit, different installation patterns are allowed:
Room type
Allowed patterns
Living room, kitchen, garage, attic, basement, storage room
1, 2, 3
Technical room (i.e. room that is NEVER occupied by persons)
1, 2, 3, 4
PATTERN 1
PATTERN 2
PATTERN 3
PATTERN 4
a
b
H
release
H
release
1a
b
A
1b
H
release
H
release
2a
b
c2
c1
A
B
2b
A
b
3a
c2
c1
A
Ventilation openings
N/A
Between room A and B
N/A
Between room A and
outside
Minimum floor area
Room A
Room A + Room B
N/A
N/A
Chimney
Might be needed
Might be needed
Connected to outside
N/A
Release in case of
refrigerant leakage
Inside room A
Inside room A
Outside
Inside room A
Restrictions
See
"Tables for PATTERN 1, 2 and 3"
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
a
If no chimney is installed, this is the default point of release
in case of refrigerant leakage.
If needed, you can connect a chimney here:
▪ Unit's connection point for the chimney = 1" male thread.
Use a compatible counterpart for the chimney.
▪ Make sure the connection is airtight.
b
Chimney
c1
Bottom opening for natural ventilation
c2
Top opening for natural ventilation
H
release
Actual release height:
1a
2a
: Without chimney. From floor to top of the unit.
▪ For 300 l units => H
release
=1.89 m
▪ For 500 l units => H
release
=1.90 m
1b
2b
: With chimney. From floor to top of the chimney.
▪ For 300 l units => H
release
=1.89 m + Chimney height
▪ For 500 l units => H
release
=1.90 m + Chimney height
3a
Installation with chimney connected to the outside. The
release height is not relevant. There are no requirements to
the minimum floor area.
N/A
Not applicable
Minimum floor area / Release height:
▪ The minimum floor area requirements depend on the release
height of the refrigerant in case of a leakage. The higher the
release height, the lower the minimum floor area requirements.
▪ The default point of release (without chimney) is at the top of the
unit. To decrease the minimum floor area requirements, you can
increase the release height by installing a chimney. If the chimney
leads outside of the building, there are no requirements anymore
to the minimum floor area.
▪ You can also take advantage of the floor area of the adjacent
room (= room B) by providing ventilation openings between the
two rooms.
▪ For installations in technical rooms (i.e. room that is NEVER
occupied by persons), additionally to patterns 1, 2 and 3, you can
also use
PATTERN
4
. For this pattern there are no requirements
to the minimum floor area if you provide 2 openings (one at the
bottom, one at the top) between the room and the outside to
ensure natural ventilation. The room must be protected from frost.
When connecting a chimney
▪ Install the chimney socket (delivered as accessory) to the plate
heat exchanger box.
Содержание ELSH12P30E
Страница 50: ......
Страница 51: ......
Страница 52: ...4P708484 1 2023 03 Copyright 2023 Daikin 4P708484 1 0000000T Verantwortung für Energie und Umwelt ...