4 Unit installation
Installation manual
11
ELSH/X(B)12P30+50E
Daikin Altherma 3 R MT ECH
₂
O
4P708484-1 – 2023.03
PATTERN 3
No
Yes
START PATTERN 3
A
You can install the unit in room A if you lead the chimney outside
the building.
3a
You CANNOT install the unit in the room. Place the unit in a larger
room.
3b
See table 3:
Is it possible to lead a chimney
outside the building respecting the maximum
chimney length?
Tables for PATTERN 1, 2 and 3
Table 1: Minimum floor area
For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is 3.5 kg, use the row of 3.65 kg.
Minimum floor area (m²)
Charge (kg)
Release height without chimney (m)
1.89 m (Unit=300 l)
1.90 m (Unit=500 l)
3.25 kg
9.05 m²
8.91 m²
3.45 kg
10.20 m²
10.04 m²
3.65 kg
11.42 m²
11.24 m²
3.85 kg
12.70 m²
12.50 m²
4.05 kg
14.05 m²
13.83 m²
Table 2: Minimum release height
Take the following into account:
• For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 7.25 m², use the column of 6.00 m².
• For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is 3.5 kg, use the row of 3.65 kg.
• (*): The release height of the unit without chimney (for 300 l units: 1.89 m; for 500 l units: 1.90 m) is already higher than the minimum
required release height. => OK (no chimney needed).
Minimum release height (m)
Charge (kg)
Floor area (m²)
4.00 m²
6.00 m²
8.00 m²
10.00 m²
12.00 m²
14.00 m²
16.00 m²
3.25 kg
3.53 m
2.35 m
2.01 m
(*)
(*)
(*)
(*)
3.45 kg
3.75 m
2.50 m
2.14 m
1.91 m
(*)
(*)
(*)
3.65 kg
3.96 m
2.64 m
2.26 m
2.02 m
(*)
(*)
(*)
3.85 kg
4.18 m
2.79 m
2.38 m
2.13 m
1.95 m
(*)
(*)
4.05 kg
4.40 m
2.93 m
2.51 m
2.24 m
2.05 m
1.89 m
(*)