4 Unit installation
Installation manual
5
ELSH/X(B)12P30+50E
Daikin Altherma 3 R MT ECH
₂
O
4P708484-1 – 2023.03
3.1
Indoor unit
3.1.1
To remove the accessories from the
indoor unit
a
Handle (only required for transport)
b
Thread cover
c
Spillover connector
d
Assembly wrench
e
Shut-off valve
f
Flat gasket
g
O‑ring
h
Securing clip
i
Venting hose
j
Drain pan hose
k
Drain pan hose clamp
l
Cable fixation for strain relief
m
Cable tie
n
O‑ring
o
Chimney socket
p
Securing clip
q
Switch box metal insert
r
Screw for switch box metal insert
s
WLAN cartridge
t
General safety precautions
u
Declaration of conformity
v
Indoor unit installation manual
w
Operation manual
x
Addendum software changelog
y
Addendum commercial warranty
3.1.2
To handle the indoor unit
Use the handles at the back and at the front to carry the unit.
NOTICE
The indoor unit is top-heavy as long as the storage tank is
empty. Secure the unit accordingly and only transport by
using the handles.
If optional Backup Heater (EKECBU*) is installed, see the
installation manual of the Backup Heater.
c
b
360°
a
1
2
a
Screw plug
b
Assembly wrench
c
Handle
1
Open the screw plugs on the front and back of the tank.
2
Attach the handles horizontally and turn by 360°.
3
Use the handles to carry the unit.
4
After carrying the unit remove the handles, add the screw plugs
again and insert the thread covers on the plugs.
4
Unit installation
WARNING
Installation shall be done by an installer, the choice of
materials and installation shall comply with the applicable
legislation. In Europe, EN378 is the applicable standard.
4.1
Preparing the installation site
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
WARNING
DO NOT reuse refrigerant piping that has been used with
any other refrigerant. Replace the refrigerant pipes or
clean thoroughly.
4.1.1
Installation site requirements of the
indoor unit
▪ The indoor unit is designed for indoor installation only and for the
following ambient temperatures:
▪ Space heating operation: 5~30°C
▪ Space cooling operation: 5~35°C
▪ Domestic hot water production: 5~35°C. If EKECBUAF6V is
installed, ambient temperature is limited to 5~32°C.
INFORMATION
Cooling is only applicable in case of reversible models.
▪ Mind the following measurements guidelines:
Maximum refrigerant piping length
(a)
between indoor
unit and outdoor unit
50 m
Minimum refrigerant piping length
(a)
between indoor
unit and outdoor unit
3 m
Maximum height difference between indoor unit and
outdoor unit
30 m
(a)
Refrigerant piping length is the one-way length of liquid piping.
▪ Mind the following spacing installation guidelines: