4 Unit installation
Installation manual
10
ELSH/X(B)12P30+50E
Daikin Altherma 3 R MT ECH
₂
O
4P708484-1 – 2023.03
Calculate the total floor area.
(
A
total
=A
roomA
+A
roomB
)
See table 4:
Look up the minimum bottom opening area for natural
ventilation with the adjacent room (
A
nv-min
) for the given refrigerant charge,
the given floor area of room A (
A
roomA
)
[! NOT room A + room B !]
and the
given release height (
H1
).
Calculate
ΔH1:
difference between the minimum release height
required (
H1
) and the release height without chimney.
See table 2:
Look up the minimum release height (
H1
) for the
given floor area (
A
total
)
and the given refrigerant charge.
Is it practically feasible to
create ventilation openings that comply
with
A
nv-min
and with the
"Conditions ventilation
openings"
on previous page)?
See table 3:
For ΔH1
: Can the maximum
chimney length be respected, and is the
chimney practically feasible?
See table 2:
Do you
need a chimney or not?
(i.e. does table 2 result in a value or "
(*)
"?)
Yes
No
No
Yes
Needed
(i.e. table 2 results in a value)
Not needed
(i.e. table 2 results in "
(*)
")
Go to PATTERN 3
H1, ΔH1
A
nv
, A
nv-min
A
B
A
B
ΔH1
You can install the unit in room A if you create ventilation
openings. You do not need a chimney.
Ventilation openings must comply with
A
nv-min
and with
"Conditions ventilation openings"
on previous page).
2a
You can install the unit in room A if you install a chimney, and
create ventilation openings.
Chimney height =
ΔH1
.
Ventilation openings must comply with
A
nv-min
and with
"Conditions ventilation openings"
on previous page).
2b
A
nv
(≥A
nv-min
)
Min. 50%
of A
nv-min
A
nv
(≥A
nv-min
)
Min. 50%
of A
nv-min
Start PATTERN 2