In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
▪
Where the voltage fluctuates a lot
▪
In vehicles or vessels
▪
Where acidic or alkaline vapour is present
▪
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
▪
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
▪
Air flow.
Make sure nothing blocks the air flow.
▪
Drainage.
Make sure condensation water can be evacuated properly.
▪
Ceiling insulation
. When conditions in the ceiling exceed 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, then additional
insulation is required (minimum 10 mm thickness, polyethylene foam).
▪
Spacing
. Mind the following requirements:
≥600
A
b
c
a
A
2.7 m minimum distance to the floor (to avoid accidental touching)
a
Ceiling
b
Floor surface
c
Service space
▪
Discharge grille.
Minimum requirement installation height of discharge grille
≥1.8 m.
Service space and ceiling opening size
Make sure ceiling opening is big enough to ensure a sufficient clearance for
maintenance and service.