About the units and options
Installer and user reference guide
55
EKVDX32~100A2VEB
VRV system air conditioner
4P664010-1 – 2021.08
14.4.1 Possible options for the indoor unit
CAUTION
▪
Each VAM unit is connected to only ONE EKVDX unit (via duct and electrical
connection).
▪
When connected to an EKVDX unit, there is NO connection of the VAM to any
other indoor unit, linkage or multiple EKVDX units.
▪
Each EKVDX unit MUST have ONLY ONE user interface. Only a safety system
compatible remote controller can be used as the user interface. See technical
data sheet for remote controller compatibility (e.g. H-type user interface like
BRC1H52/82*).
▪
Supervising and/or slave user interfaces are NOT allowed for EKVDX units.
▪
R32 refrigerant: the user interface MUST be installed in one of the rooms the
EKVDX unit is discharging into.
▪
R410A refrigerant: the user interface can also be installed in e.g. the hallway.
INFORMATION
All possible options are mentioned in the option list of the indoor unit. For more
information about an option, refer to the installation and operation manual of the
option.
14.4.2 Compatibility with outdoor unit
Refrigerant
Unit
EKVDX
R410A
All VRV – III
NO
All VRV-IV
YES
ERQ
NO
R32
All VRV-V
YES
14.4.3 Compatibility with VAM models
EKVDX32
EKVDX50
EKVDX80
EKVDX100
VAM500J8
●
—
—
—
VAM650J8
—
●
—
—
VAM800J8
—
●
—
—
VAM1000J8
—
—
●
—
VAM1500J8
—
—
—
●
VAM2000J8
—
—
—
●
—
Not compatible
●
Compatible in pair
The EKVDX option is not available for VAM350J8.