16
|
Piping installation
Installer and user reference guide
67
EKVDX32~100A2VEB
VRV system air conditioner
4P664010-1 – 2021.08
a
b
a
Cut exactly at right angles.
b
Remove burrs.
3
Remove the flare nut from the stop valve and put the flare nut on the pipe.
4
Flare the pipe. Set exactly at the position as shown in the following figure.
A
Flare tool for R32
(clutch type)
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
A
0~0.5 mm
1.0~1.5 mm
1.5~2.0 mm
5
Check that the flaring is properly made.
a
b
c
a
Flare’s inner surface MUST be flawless.
b
The pipe end MUST be evenly flared in a perfect circle.
c
Make sure the flare nut is fitted.
16.2.6 To connect the refrigerant piping to the indoor unit
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to
be exposed to any substance which may corrode components containing refrigerant,
unless the components are constructed of materials that are inherently resistant to
corrosion or are suitably protected against corrosion.
▪
Pipe length
. Keep refrigerant piping as short as possible.
▪
Flare connections
. Connect refrigerant piping to the unit using flare connections.
▪
Insulation
. Insulate the refrigerant piping on the indoor unit as follows:
B
A
a
d
c
e f
b
b
a
d
c
e f
b
b
2
4
3
g
1
2
3
4
g
1
A B
A
Liquid piping
B
Gas piping
a
Insulation material (field supply)
b
Tie wrap (field supply)
c
Insulation tubes: large (gas pipe), small (liquid pipe) (accessories)
d
Flare nut (attached to the unit)
e
Refrigerant pipe connection (attached to the unit)