8 Configuration
Timers
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
N/A
[7-00]
Overshoot temperature. Temperature
difference above the domestic hot water
set point temperature before the booster
heater is turned OFF. The domestic hot
water tank temperature will increase with
[7-00] above selected temperature
set point.
N/A
[7-01]
Hysteresis. Temperature difference
between booster heater ON and booster
heater OFF temperature. The minimum
hysteresis temperature is 2°C.
N/A
[6-00]
The temperature difference determining
the heat pump ON temperature.
N/A
[6-01]
The temperature difference determining
the heat pump OFF temperature.
#
Code
Description
N/A
[8-00]
Minimum running time for domestic hot
water operation. During this time, space
heating/cooling is NOT allowed, even
when the target domestic hot water
temperature has been reached.
N/A
[8-01]
Maximum running time for domestic hot
water operation. Domestic hot water
heating stops even when the target
domestic hot water temperature is NOT
reached. The actual maximum running
time also depends on setting [8-04].
Q
When system layout = Room
thermostat control: This preset value
is only taken into account if there is
a request for space heating or
cooling. If there is NO request for
space heating/cooling, the tank is
heated until heat pump OFF
temperature.
Q
When system layout
≠
Room
thermostat control: This preset value
is always taken into account.
N/A
[8-02]
Anti-recycling time.
Minimum time between two cycles for
domestic hot water. The actual anti-
recycling time also depends on setting
[8-04].
#
Code
Description
N/A
[8-03]
Booster heater delay timer.
Only for EKHW*
Start-up delay time for the booster heater
when domestic hot water mode is active.
Q
When domestic hot water mode is
NOT active, the delay time is
20 minutes.
Q
The delay time starts from booster
heater ON temperature.
Q
By adapting the booster heater
delay time versus the maximum
running time, you can find an
optimal balance between the energy
efficiency and the heat up time.
Q
If the booster heater delay time is
set too high, it might take a long time
before the domestic hot water
reaches its set temperature.
Q
The setting [8-03] is only meaningful
if setting [4-03]=1. Setting [4-
03]=0/2/3 limits the booster heater
automatically in relation to
heat pump operation time in
domestic water heating mode.
Q
Make sure that [8-03] is always in
relation with the maximum running
time [8-01].
N/A
[8-04]
Additional running time for the maximum
running time depending on the outdoor
temperature [4-02] or [F-01].
CAUTION
The disinfection function settings must be configured by the
installer according to the applicable legislation.
#
Code
Description
[A.4.4.2]
[2-00]
Operation day:
Q
Each day
Q
Monday
Q
Tuesday
Q
Wednesday
Q
Thursday
Q
Friday
Q
Saturday
Q
Sunday
[A.4.4.2]
[2-01]
Disinfection
Q
No
Q
Yes
[A.4.4.3]
[2-02]
Start time: 00~23:00, step: 1:00.
[A.4.4.4]
[2-03]
Temperature target:
Q
With booster heater: 55~80°C,
default: 70°C.
Q
Without booster heater: 60°C
(fixed).
[A.4.4.5]
[2-04] Duration:
Q
With booster heater: 5~60 minutes,
default: 10 minutes.
Q
Without booster heater: 40~60
minutes, default: 60 minutes.
#