Installer reference guide
32
8 Configuration
3
Set the system layout settings: Standard, Options, Capacities.
For more details, see Basic configuration.
4
Confirm by pressing
.
5
The user interface re-initialises and you can proceed the
installation by setting the other applicable settings and
commissioning of the system.
When the installer settings are changed, the system will request to
confirm. When confirmation is complete, the screen will shortly turn
OFF and "busy" will be displayed for several seconds.
8.2
Basic configuration
8.2.1 Quick wizard: Language / time and date
8.2.2 Quick wizard: Standard
Backup heater configuration (only for *9W model)
The backup heater in a *9W model is adapted to be connected to
most common European electricity grids. Besides hardware
configuration, the backup heater type must be set on the user
interface.
Space heating/cooling settings
The system can heat up or cool down a space. Depending on the
type of application, the space heating/cooling settings must be made
accordingly.
#
Code
Description
[A.1]
N/A
Language
[1]
N/A
Time and date
#
Code
Description
[A.2.1.5]
[5-0D]
BUH type:
Q
1 (1P,(1/1+2)): 3 kW 1~ 230 V (*9W)
Q
3 (3P,(1/1+2)): 6 kW 3~ 230 V (*9W)
Q
4 (3PN,(1/2)): 6 kW 3N~ 400 V
(*9W)
Q
5 (3PN,(1/1+2)): 9 kW 3N~ 400 V
(*9W)
#
Code
Description
[A.2.1.7]
[C-07]
Unit control method:
Q
0 (LWT control): Unit operation is
decided based on the leaving water
temperature regardless the actual
room temperature and/or heating or
cooling demand of the room.
Q
1 (Ext RT control): Unit operation is
decided by the external thermostat
or equivalent (e.g. heat pump
convector).
Q
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
[A.2.1.B]
N/A
Only if there are 2 user interfaces (1
installed in the room, 1 installed at the
indoor unit):
User interface location:
Q
At unit: the other user interface is
automatically set to In room and if
RT control is selected act as room
thermostat.
Q
In room(default): the other user
interface is automatically set to At
unit and if RT control is selected to
act as room thermostat.
#
Code
Description