manualshive.com logo in svg
background image

Operation manual

5

0 EKCBX/H008BAV3

Unit for air to water heat pump system

4PW64603-1A – 08.2010

25.

SPACE HEATING/COOLING BUTTON 

=

This button allows manual switching between heating or cooling
mode (provided the unit is not a heating only unit).

When the unit is connected with an external room thermostat,
this button is not operable and the icon 

e

 is shown.

26.

DOMESTIC WATER HEATING BUTTON 

v

This button enables or disables heating of the domestic water.

This button is not used when the domestic hot water tank is not
installed.

27.

WEATHER DEPENDENT SET POINT BUTTON 

ba

This button enables or disables the weather dependent set point
function which is available in space heating operation only.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 11

), the weather dependent set point button

will not be operable.

28.

INSPECTION/TEST OPERATION BUTTON 

z

This button is used for installation purposes and changing 

fi

eld

settings. Refer to 

"Field settings" on page 11

.

29.

PROGRAMMING BUTTON 

<

This multi-purpose button is used to program the controller. The
function of the button depends on the actual status of the
controller or on previous actions carried out by the operator.

30.

SCHEDULE TIMER BUTTON 

r

/

p

The main function of this multi-purpose button is to
enable/disable the schedule timer.

The button is also used to program the controller. The function of
the button depends on the actual status of the controller or on
previous actions carried out by the operator.

If the controller is set in permission level 3 (refer to 

"Field

settings" on page 11

), the schedule timer button will not be

operable.

31.

TIME ADJUST BUTTON 

pi

 and 

pj

These multi-purpose buttons are used to adjust the clock, to
toggle between temperatures (water outlet temperature of the
indoor unit, outdoor ambient temperature and domestic hot
water temperature) and in schedule timer programming mode.

32.

TEMPERATURE ADJUST BUTTONS 

bi

 and 

bj

These multi-purpose buttons are used to adjust the current set
point in normal operation mode or in schedule timer
programming mode. In weather dependent set point mode the
buttons are used to adjust the shift value. Finally, the buttons are
also used to select the weekday while setting the clock.

33.

DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS

wbi

 and 

wbj

These buttons are used to adjust the current set point of the
domestic hot water temperature.

The buttons are not used when the domestic hot water tank is
not installed.

34.

QUIET MODE BUTTON 

s

This button enables or disables quiet mode.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 11

), the quiet mode button will not be

operable.

Setting up the controller

After initial installation, the user can set the clock and day of the
week.

The controller is equipped with a schedule timer that enables the user
to schedule operations. Setting the clock and day of the week is
required to be able to use the schedule timer.

Setting the clock

1

Hold down the 

pr

 button for 5 seconds.

The clock read-out and the day of week indicator start 

fl

ashing.

2

Use the 

pi

 and 

pj

 buttons to adjust the clock.

Each time the 

pi

 or 

pj

 button is pressed, the time will

increase/decrease by 1 minute. Keeping the 

pi

 or 

pj

button pressed will increase/decrease the time by 10 minutes.

3

Use the 

bi

 or 

bj

 button to adjust the day of the week.

Each time the 

bi

 or 

bj

 button is pressed the next or

previous day is displayed.

4

Press the 

<

 button to con

fi

rm the current set time and day of the

week.

To leave this procedure without saving, press the 

pr

 button.

If no button is pressed for 5 minutes the clock and day of the
week will return to their previous setting.

Setting the schedule timer

To set the schedule timer, refer to chapter 

"Programming and

consulting the schedule timer" on page 8

.

Description of the operation modes

Space heating operation (

h

)

In this mode, heating will be activated as required by the water
temperature set point. The set point can be set manually (refer to

"Manual operation" on page 6

) or weather dependent (refer to

"Selecting weather dependent set point operation (only in heating
mode)" on page 7

).

Startup (

d

)

At the start of a heating operation, the pump is not started until a
certain refrigerant heat exchanger temperature is reached. This
guarantees correct startup of the heat pump. During startup, icon

d

 is displayed.

Defrost (

d

)

In space heating operation or heat pump domestic water heating
operation, freezing of the outdoor heat exchanger may occur due to
low outdoor temperature. If this risk occurs, the system goes into
defrost operation. It reverses the cycle and takes heat from the indoor
system to prevent freezing of the outdoor system. After a maximum
of 8 minutes of defrost operation, the system returns to space heating
operation.

Space cooling operation (

c

)

In this mode, cooling will be activated as required by the water
temperature set point.

NOTICE

Remark that pushing the 

y

 button has no in

fl

uence

on the domestic water heating. Domestic water
heating is only switched on or off by means of the

v

 button.

The clock needs to be set manually. Adjust the setting
when switching from summertime to wintertime and vice
versa.

The space cooling temperature set point can only be
set manually (refer to 

"Manual operation" on page 6

).

Switching between space heating and space cooling
operation can only be done by pressing the 

=

button or by the external room thermostat.

Space cooling operation is not possible if the
installation is a "heating only" installation.

Содержание EBHQ006BAV3

Страница 1: ...OPERATION MANUAL EBHQ006BAV3 EBHQ008BAV3 EKCBX008BAV3 EKCBH008BAV3 Unit for air to water heat pump system ...

Страница 2: ...ain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Dealer Sales distributor for products as per the subject of this manual Installer Techn...

Страница 3: ...the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB to the unit Bottom plate heater EKBPHT refer to the installation manual option Remote thermostat kit option An optional room thermostat EKRTW EKRTWA or EKRTR can be connected to the indoor unit Refer to the installation manual of the room thermostat for more information To obtain more...

Страница 4: ... that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open flame or any electrical appliance operating nearby If hydrogen is discharged through the tap it will probably make a sound as of air escaping 4 2 Operating the digital controller Operating the unit comes down to opera...

Страница 5: ... schedule timer 9 OFF ICON x This icon indicates that the OFF action is selected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes ...

Страница 6: ...button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enables the user to schedule operations Setting the clock and day of the week is required to be able to use the schedule timer Setting the clock 1 Hold down the pr button for 5 seconds The clock read out and the day of...

Страница 7: ...ture set point 2 Use the bi and bj buttons to set the desired water temperature Temperature range for heating 25 C to 55 C The temperature for heating can be set as low as 15 C see Field settings on page 11 However the temperature for heating should only be set lower than 25 C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid ov...

Страница 8: ...ntroller leaves the display mode Schedule timer operation In schedule timer operation the installation is controlled by the schedule timer The actions programmed in the schedule timer will be executed automatically The schedule timer always follows the last command until a new command is given This means that the user can temporarily overrule the last executed programmed command by manual operatio...

Страница 9: ...ated on a daily basis Take your time to enter all data accurately Try to program the actions in a chronological way start with action 1 for the first action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest ...

Страница 10: ... button to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows t...

Страница 11: ...ating you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the ...

Страница 12: ...to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day is blinking 5 Press the and ba button simultaneously for 5 seconds to delete the selected day 4 3 Field settings The i...

Страница 13: ...ater temperature by a maximum of 5 C 1 00 Low ambient temperature Lo_A low outdoor temperature 1 01 High ambient temperature Hi_A high outdoor temperature 1 02 Set point at low ambient temperature Lo_Ti the target outgoing water temperature when the outdoor temperature equals or drops below the low ambient temperature Lo_A Note that the Lo_Ti value should be higher than Hi_Ti as for colder outdoor...

Страница 14: ...per limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set point upper limit maximum leaving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation CAUTION The disinfection function field settings must be conf...

Страница 15: ...t determines the shift value of the weather dependent set point around outdoor temperature of 0 C E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature Tt Target water temperature T...

Страница 16: ...Auto restart 00 Status 0 ON 0 1 4 Space heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting 04 Installation related setting 5 Installation related settings 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Installation related setting 04...

Страница 17: ...ation related setting d Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Local shift value weather dependent 0 0 1 2 3 4 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperat...

Страница 18: ... a qualified installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or local authority for more information DANGER Do no...

Страница 19: ......

Страница 20: ...Copyright 2010 Daikin 4PW64603 1A 08 2010 ...

Отзывы: