Operation manual

7

0 EKCBX/H008BAV3

Unit for air to water heat pump system

4PW64603-1A – 08.2010

Selection and setting of domestic water heating (

w

)

1

Use the 

v

 button to activate domestic water heating (

w

).

Icon 

w

 appears on the display.

2

Use the 

wi

 or 

wj

 button to display the actual

temperature set point and subsequently, to set the correct
temperature.

The actual temperature set point only appears on the display
after pressing one of the buttons 

wi

 or 

wj

. If no button is

pressed for 5 seconds, the temperature set point will
automatically disappear from the display again.
Temperature range for domestic water heating: 30°C to 78°C

3

Press the 

v

 button to deactivate domestic water heating (

w

).

Icon 

w

 disappears from the display.

Selecting powerful domestic water heating operation

1

Press 

v

 for 5 seconds to activate powerful domestic water

heating operation.

Icons 

w

 and 

m

 start 

fl

ashing.

Powerful domestic water heating is deactivated automatically
when the set point for the domestic hot water is reached.

Selecting quiet mode operation (

s

)

1

Use the 

s

 button to activate quiet mode operation (

s

).

Icon 

s

 appears on the display.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 11

), the 

s

 button will not be operable.

Selecting weather dependent set point operation (only in
heating mode)

1

Press the 

ba

 button to select weather dependent set point

operation.

Icon 

a

 appears on the display as well as the shift value. The

shift value is not shown in case it is 0.

2

Use the 

bi

 and 

bj

 buttons to set the shift value.

Range for the shift value: –5°C to +5°C

Displaying actual temperatures

1

Push the 

ba

 button for 5 seconds.

The 

b

 icon and the outgoing water temperature are displayed.

The icons 

l

 and 

=

 are 

fl

ashing.

2

Use the 

pi

 and 

pj

 buttons to display:

The outdoor temperature (

u

 icon is 

fl

ashing).

The domestic hot water tank temperature (

w

 icon is

fl

ashing).

The outgoing water temperature (

=

 are 

fl

ashing).

If no button is pressed for 5 seconds, the controller leaves the
display mode.

Schedule timer operation

In schedule timer operation, the installation is controlled by the
schedule timer. The actions programmed in the schedule timer will be
executed automatically.

The schedule timer always follows the last command until a new
command is given. This means that the user can temporarily overrule
the last executed programmed command by manual operation (Refer
to 

"Manual operation" on page 6

). The schedule timer will regain

control over the installation as soon as the next programmed
command of the schedule timer occurs.

The schedule timer is enabled (

p

 icon displayed) or disabled (

p

 icon

not displayed), by pressing the 

pr

 button.

To set up the SCHEDULE TIMER refer to chapter 

"Programming and

consulting the schedule timer" on page 8

.

NOTICE

Remark that pushing the 

y

 button has no in

fl

uence on

the domestic water heating. Domestic water heating is only
switched on or off by means of the 

v

 button.

NOTICE

Only use the 

pr

 button to enable or disable the

schedule timer. The schedule timer overrules the 

y

button. The 

y

 button only overrules the schedule

timer until the next programmed action.

If the auto restart function is disabled, the schedule
timer will not be activated when power returns to the
unit after a power supply failure. Press the 

pr

 button

to enable the schedule timer again.

When power returns after a power supply failure, the
auto restart function reapplies the user interface
settings at the time of the power supply failure.

It is therefore recommended to leave the auto restart
function enabled.

The programmed schedule is time driven. Therefore, it
is essential to set the clock and the day of the week
correctly. Refer to 

"Setting the clock" on page 5

.

Manually adjust the clock for summertime and
wintertime. Refer to 

"Setting the clock" on page 5

.

A power failure exceeding 2 hours will reset the clock
and the day of the week. The schedule timer will
continue operation, but with a disordered clock. Refer
to 

"Setting the clock" on page 5

 to adjust the clock and

the day of the week.

The actions programmed in the schedule timer will not
be lost after a power failure so that reprogramming the
schedule timer is not required.

Содержание EBHQ006BAV3

Страница 1: ...OPERATION MANUAL EBHQ006BAV3 EBHQ008BAV3 EKCBX008BAV3 EKCBH008BAV3 Unit for air to water heat pump system ...

Страница 2: ...ain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Dealer Sales distributor for products as per the subject of this manual Installer Techn...

Страница 3: ...the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB to the unit Bottom plate heater EKBPHT refer to the installation manual option Remote thermostat kit option An optional room thermostat EKRTW EKRTWA or EKRTR can be connected to the indoor unit Refer to the installation manual of the room thermostat for more information To obtain more...

Страница 4: ... that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open flame or any electrical appliance operating nearby If hydrogen is discharged through the tap it will probably make a sound as of air escaping 4 2 Operating the digital controller Operating the unit comes down to opera...

Страница 5: ... schedule timer 9 OFF ICON x This icon indicates that the OFF action is selected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes ...

Страница 6: ...button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enables the user to schedule operations Setting the clock and day of the week is required to be able to use the schedule timer Setting the clock 1 Hold down the pr button for 5 seconds The clock read out and the day of...

Страница 7: ...ture set point 2 Use the bi and bj buttons to set the desired water temperature Temperature range for heating 25 C to 55 C The temperature for heating can be set as low as 15 C see Field settings on page 11 However the temperature for heating should only be set lower than 25 C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid ov...

Страница 8: ...ntroller leaves the display mode Schedule timer operation In schedule timer operation the installation is controlled by the schedule timer The actions programmed in the schedule timer will be executed automatically The schedule timer always follows the last command until a new command is given This means that the user can temporarily overrule the last executed programmed command by manual operatio...

Страница 9: ...ated on a daily basis Take your time to enter all data accurately Try to program the actions in a chronological way start with action 1 for the first action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest ...

Страница 10: ... button to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows t...

Страница 11: ...ating you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the ...

Страница 12: ...to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day is blinking 5 Press the and ba button simultaneously for 5 seconds to delete the selected day 4 3 Field settings The i...

Страница 13: ...ater temperature by a maximum of 5 C 1 00 Low ambient temperature Lo_A low outdoor temperature 1 01 High ambient temperature Hi_A high outdoor temperature 1 02 Set point at low ambient temperature Lo_Ti the target outgoing water temperature when the outdoor temperature equals or drops below the low ambient temperature Lo_A Note that the Lo_Ti value should be higher than Hi_Ti as for colder outdoor...

Страница 14: ...per limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set point upper limit maximum leaving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation CAUTION The disinfection function field settings must be conf...

Страница 15: ...t determines the shift value of the weather dependent set point around outdoor temperature of 0 C E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature Tt Target water temperature T...

Страница 16: ...Auto restart 00 Status 0 ON 0 1 4 Space heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting 04 Installation related setting 5 Installation related settings 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Installation related setting 04...

Страница 17: ...ation related setting d Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Local shift value weather dependent 0 0 1 2 3 4 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperat...

Страница 18: ... a qualified installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or local authority for more information DANGER Do no...

Страница 19: ......

Страница 20: ...Copyright 2010 Daikin 4PW64603 1A 08 2010 ...

Отзывы: