background image

4

INSTALLATION

Pre-Installation Checkpoints

Before attempting any installation, the following points 

should be considered: 

•  Structural strength of supporting members

•  Clearances and provision for servicing

•  Power supply and wiring

•  Air duct connections

•  Drain facilities and connections

•  Location may be on any four sides of a home,   

manufactured or modular, to minimize noise

Clearance

The unit is designed to be located outside the building 

with unobstructed condenser air inlet and discharge.  

Additionally, the unit must be situated to permit access 

for service and installation. Condenser air enters from 

three sides. Air discharges upward from the top of the 

unit. Refrigerant gauge connections are made on the right 

side of the unit as you face the compressor compartment.  

Electrical connections can be made either on the right 

or left sides of the unit. The best and most common 

application is for the unit to be located 10” from wall (4” 

minimum) with the connection side facing the wall. This 

“close to the wall” application minimizes exposed wiring.

Close to the wall application assures free, unobstructed 

air to the other two sides. In more confined application 

spaces, such as corners provide a minimum 10” clearance 

on all air inlet sides. Allow 18” minimum for service access 

to the compressor compartment and controls. The top of 

the unit should be completely unobstructed. If units are to 

be located under an overhang, there should be a minimum 

of 36” clearance and provisions made to deflect the warm 

discharge air out from the overhang.

Location

Consider the effect of outdoor fan noise on conditioned 

space and any adjacent occupied space. It is 

recommended that the unit be placed so that condenser air 

discharge does not blow toward windows less than 25 feet 

away.

The unit should be set on a solid, level foundation - 

preferably a concrete slab at least 4 inches thick. The 

slab should be above ground level and surrounded by 

a graveled area for good drainage. Any slab used as a 

unit’s foundation should not adjoin the building as it is 

possible that sound and vibration may be transmitted to 

the structure. For rooftop installation, steel or treated wood 

beams should be used as unit support for load distribution.

Heat pumps require special location consideration in areas 

of heavy snow accumulation and/or areas with prolonged 

continuous subfreezing temperatures. Heat pump unit 

bases have holes under the outdoor coil to permit drainage 

of defrost water accumulation. The unit must be situated 

to permit free unobstructed drainage of the defrost water 

and ice. A minimum 2” clearance under the outdoor coil is 

required in the milder climates.

Outside Slab Installation (Figure 1)

1.  The unit must be mounted on a solid, level 

foundation.

2.  Select a location that will minimize the length of the 

supply and return ducts.

3.  Select a location where external water drainage 

cannot collect around the unit.

4.  Consideration should also be given to shade, 

appearance and noise.

36"

36"

10"

UNIT

WALL

36"

Figure 1

Rooftop Installation (Figure 2)

1.  Before locating the unit on the roof, make sure that 

the strength of the roof and beams is adequate to 

support the weight involved. (See specification sheet 

for weight of units.) This is very important and the 

installer’s responsibility.

2.  Make proper consideration for the weather–

tight integrity of the roof and proper drainage of 

condensate.

3.  To ensure proper condensate drainage, unit must be 

installed in a level position.

4.  Consideration should also be given to shade, 

appearance and noise.  

Содержание DP5HH2441 Series

Страница 1: ...ourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the cus...

Страница 2: ...24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compressor Compressor damage may occur if this step is not followed Before using this manual check the seri...

Страница 3: ...ct work The units can also be easily converted to accommodate a plenum for normal or low static applications The DP C DP H series are self contained packaged units so the only connections needed for i...

Страница 4: ...the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away The unit should be set on a solid level foundation preferably a concrete slab at least 4 inches...

Страница 5: ...rter Your distributor has a factory designed square to round converter transition The model s of these kits are as follows Small Chassis 25 SQRPCH101 Medium Chassis 27 5 SQRPCH102 Large and Extra Larg...

Страница 6: ...ty of sufficient power to operate the unit The voltage frequency and phase at the power supply should be checked to make sure it corresponds to the unit s RATED VOLTAGE REQUIREMENT Install a branch ci...

Страница 7: ...gth of the run can be determined from Table 4 using the circuit ampacity found on the unit rating plate From the unit disconnect to unit the smallest wire size allowable in Table 4 may be used for the...

Страница 8: ...ndoor return air until the unit trips 13 If unit operates properly in the heating cycle raise the temperature setting until the heating second stage makes contact Supplemental resistance heat if insta...

Страница 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Страница 10: ...ostat calls for heat At the end of the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 5 F the defrost cycle is termi...

Страница 11: ...ll use the higher speed setting NOTE GPC15 and GPH16 units are rated for a maximum E S P of 0 8 except when using a 20kw electric heater The maximum static for 20 kW electric heat is 0 5 E S P When th...

Страница 12: ...d small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Two stage systems running on low stage with TXV application s...

Страница 13: ...clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cut out Outside Air Into Return Duct Do not introduce cold outside air into...

Страница 14: ...M 1645 1602 1560 1517 1475 1433 1390 1347 Watts 285 297 309 321 333 346 358 370 CFM 1239 1184 1146 1091 1049 1001 948 890 Watts 152 163 175 184 194 205 220 235 CFM 1837 1789 1748 1706 1665 1623 1577 1...

Страница 15: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Страница 16: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Страница 17: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Страница 18: ...18 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 19: ...19 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 20: ...he feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and e...

Отзывы: