background image

6

Plenum Application

A suitable plenum or square duct must be constructed. The 

duct cross-sectional area should be determined by industry 

duct sizing manuals or air duct calculators.

On ductwork exposed to outside air conditions of 

temperature and humidity, use an insulation with a good 

K factor, and a vapor barrier. Industry practices should be 

followed. Balancing dampers are recommended for each 

branch duct in the supply system. Ductwork should be 

properly supported from the unit.

NOTE: Proper sealing of all duct work and air 

handling compartments is extremely important to 

overall unit efficiency.

Filters

Filters are not provided with unit, and must be supplied 

and installed in the return duct system by the installer.  A 

field installed filter grille is recommended for easy and 

convenient access to the filters for periodic inspection and 

cleaning. Filters must have adequate face area for the 

rated quantity of the unit. See air delivery tables (Figure 4) 

for recommended filter size.

PIPING

Condensate Drain

The condensate drain connection of the evaporator is a 

half coupling of ¾” N.P.T. A trap must be provided to have 

Proper condensate drainage.

2" Minimum

3" Minimum

A Positive Liquid Seal

Is Required

Flexible

Tubing-Hose

Or Pipe

Drain

Connection

Unit

Figure 5

Install condensate drain trap as shown. Use ¾” drain 

connection size or larger. Do not operate without trap. Unit 

must be level or slightly inclined toward drain.

WIRING

CAUTION

To avoid property damage or personal injury due to fire, 

use only copper conductors.

All wiring should be made in accordance with the National 

Electrical Code. The local Power Company should 

be consulted to determine the availability of sufficient 

power to operate the unit. The voltage, frequency, and 

phase at the power supply should be checked to make 

sure it corresponds to the unit’s RATED VOLTAGE 

REQUIREMENT.

Install a branch circuit fused disconnect near the unit, in 

accordance with the N.E.C. or local codes. Wire sizes and 

overcurrent protection should be determined from the unit 

nameplate ampacity and in accordance with Table 4 (page 

7) or the N.E.C. Under no circumstances should wiring be 

sized smaller than is recommended by either of these two 

sources. 

Fuses smaller than that recommended on the wiring 

diagrams could result in unnecessary fuse failure or 

service calls. The use of protective devices of larger size 

than indicated could result in extensive damage to the 

equipment. The manufacturer bears no responsibility for 

damage caused to equipment as result of the use of larger 

than is recommended size protective devices. 

All units have undergone a run test prior to packaging for 

shipment. This equipment has been started at minimum 

rated voltage and checked for satisfactory operation. Do 

not attempt to operate this unit if the voltage is not within 

the minimum and maximum voltages shown on nameplate.

All exterior wiring must be within approved weatherproof 

conduit. The unit must be 

permanently grounded

 in 

accordance with local codes, or in absence of local codes, 

with N.E.C ANSI/ NFPA NO. 70-1984 or latest edition by 

using ground lug in the control box.

Fuses or HACR type circuit breakers may be used 

where codes permit.

CONTACTOR

R

W

G

G R W

FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT

24 VOLT CONTROL WIRING

Figure 6

NOTE: Some single phase units are equipped with a 

single pole contactor. Caution must be exercised 

when servicing as only one leg of the power 

supply is broken with the contactor.

To wire the unit, make the following high and low voltage 

connections.

Содержание DP5HH2441 Series

Страница 1: ...ourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the cus...

Страница 2: ...24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compressor Compressor damage may occur if this step is not followed Before using this manual check the seri...

Страница 3: ...ct work The units can also be easily converted to accommodate a plenum for normal or low static applications The DP C DP H series are self contained packaged units so the only connections needed for i...

Страница 4: ...the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away The unit should be set on a solid level foundation preferably a concrete slab at least 4 inches...

Страница 5: ...rter Your distributor has a factory designed square to round converter transition The model s of these kits are as follows Small Chassis 25 SQRPCH101 Medium Chassis 27 5 SQRPCH102 Large and Extra Larg...

Страница 6: ...ty of sufficient power to operate the unit The voltage frequency and phase at the power supply should be checked to make sure it corresponds to the unit s RATED VOLTAGE REQUIREMENT Install a branch ci...

Страница 7: ...gth of the run can be determined from Table 4 using the circuit ampacity found on the unit rating plate From the unit disconnect to unit the smallest wire size allowable in Table 4 may be used for the...

Страница 8: ...ndoor return air until the unit trips 13 If unit operates properly in the heating cycle raise the temperature setting until the heating second stage makes contact Supplemental resistance heat if insta...

Страница 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Страница 10: ...ostat calls for heat At the end of the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 5 F the defrost cycle is termi...

Страница 11: ...ll use the higher speed setting NOTE GPC15 and GPH16 units are rated for a maximum E S P of 0 8 except when using a 20kw electric heater The maximum static for 20 kW electric heat is 0 5 E S P When th...

Страница 12: ...d small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Two stage systems running on low stage with TXV application s...

Страница 13: ...clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cut out Outside Air Into Return Duct Do not introduce cold outside air into...

Страница 14: ...M 1645 1602 1560 1517 1475 1433 1390 1347 Watts 285 297 309 321 333 346 358 370 CFM 1239 1184 1146 1091 1049 1001 948 890 Watts 152 163 175 184 194 205 220 235 CFM 1837 1789 1748 1706 1665 1623 1577 1...

Страница 15: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Страница 16: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Страница 17: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Страница 18: ...18 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 19: ...19 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 20: ...he feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and e...

Отзывы: