background image

11

In general 400 CFM per ton of cooling capacity is a rule 

of thumb. Some applications depending on the sensible 

and latent capacity requirements may need only 350 

CFM or up to 425 CFM per ton. Check condition space 

load requirements (from load calculations) and equipment 

expanded ratings data to match CFM and capacity.

After unit is set and ducted, verify ESP with a 1” inclined 

manometer with pitot tubes or a Magnahelic gauge 

and confirm CFM to blower curves in the specification 

sheets. All units have multiple speed blower motors. If 

factory selected speed is not utilized, the speed tap can 

be changed. Never run CFM below 350 CFM per ton, 

evaporator freezing or poor unit performance is possible.

ADJUSTING SPEED TAP FOR INDOOR 

BLOWER MOTOR

EEM Motor

The blower motor speed for the EEM motor is controlled by 

three 24V low voltage leads: green, yellow, and white. The 

green lead sets the speed for fan-only mode. The yellow 

lead sets the speed for cooling and heat pump heating 

mode (if applicable). The white lead sets the speed for 

electric heat mode (emergency heat and second stage 

heat, if applicable).

The leads are factory connected as follows: Green to T1, 

Yellow to T2, and White to T3. T1 is the low speed setting 

and is dedicated to fan-only mode. T2 is medium speed 

cooling and T3 is medium speed heating. T4 is high speed 

cooling and T5 is high speed heating. To adjust the blower 

speed, move the yellow and/or white wires to T4 and T5.

NOTE: If more than one lead is energized at the 

same time, the motor will use the higher speed 

setting.

NOTE: GPC15 and GPH16 units are rated for a 

maximum E.S.P. of 0.8 except when using a 20kw 

electric heater. (The maximum static for 20 kW 

electric heat is 0.5 E.S.P.) When these units are 

installed in the 0.5 - 0.8 E.S.P. range, the white lead 

(electric heat) must be moved to T5 for proper 

operation of the electric heaters.

See CFM vs ESP tables in this manual.

Refrigerant Charge Check 

(Units with Fixed Orifice Devices)

After completing airflow measurements and adjustments 

the unit’s refrigerant charge must be checked. All package 

units with fixed orifice devices are charged using the 

super heat method at the compressor suction line. After 

superheat is adjusted it is recommended to check unit 

sub-cooling at the condenser coil liquid line out. For charge 

adjustments, see superheat and subcooling charts shown 

for each model.

SUPERHEAT CAN BE DETERMINED AS FOLLOWS:

1.  Read suction pressure. Determine Saturated 

Suction Temperature from tables or pressure gauge 

saturated temperature scale (R-410A).

2.  Read suction line temperature.

3.  Use the following formula:

SUPERHEAT = SUCTION LINE TEMP - SAT. 

SUCTION TEMP.

SUCTION

PRESSURE

SATURATED

SUCTION 

TEMPERATURE

ºF

LIQUID

PRESSURE

SATURATED

LIQUID 

TEMPERATURE

ºF

PSIG  

R-410A  

PSIG  

R-410A  

50

1

200

70

52

3

210

73

54

4

220

76

56

6

225

78

58

7

235

80

60

8

245

83

62

10

255

85

64

11

265

88

66

13

275

90

68

14

285

92

70

15

295

95

72

16

305

97

74

17

325

101

76

19

355

108

78

20

375

112

80

21

405

118

85

24

415

119

90

26

425

121

95

29

435

123

100

31

445

125

110

36

475

130

120

41

500

134

130

45

525

138

140

49

550

142

150

53

575

145

160

56

600

149

170

60

625

152

SATURATED

SUCTION PRESSURE

 TEMPERATURE CHART

SATURATED

LIQUID PRESSURE

 TEMPERATURE CHART

Содержание DP5HH2441 Series

Страница 1: ...ourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the cus...

Страница 2: ...24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compressor Compressor damage may occur if this step is not followed Before using this manual check the seri...

Страница 3: ...ct work The units can also be easily converted to accommodate a plenum for normal or low static applications The DP C DP H series are self contained packaged units so the only connections needed for i...

Страница 4: ...the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away The unit should be set on a solid level foundation preferably a concrete slab at least 4 inches...

Страница 5: ...rter Your distributor has a factory designed square to round converter transition The model s of these kits are as follows Small Chassis 25 SQRPCH101 Medium Chassis 27 5 SQRPCH102 Large and Extra Larg...

Страница 6: ...ty of sufficient power to operate the unit The voltage frequency and phase at the power supply should be checked to make sure it corresponds to the unit s RATED VOLTAGE REQUIREMENT Install a branch ci...

Страница 7: ...gth of the run can be determined from Table 4 using the circuit ampacity found on the unit rating plate From the unit disconnect to unit the smallest wire size allowable in Table 4 may be used for the...

Страница 8: ...ndoor return air until the unit trips 13 If unit operates properly in the heating cycle raise the temperature setting until the heating second stage makes contact Supplemental resistance heat if insta...

Страница 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Страница 10: ...ostat calls for heat At the end of the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 5 F the defrost cycle is termi...

Страница 11: ...ll use the higher speed setting NOTE GPC15 and GPH16 units are rated for a maximum E S P of 0 8 except when using a 20kw electric heater The maximum static for 20 kW electric heat is 0 5 E S P When th...

Страница 12: ...d small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Two stage systems running on low stage with TXV application s...

Страница 13: ...clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cut out Outside Air Into Return Duct Do not introduce cold outside air into...

Страница 14: ...M 1645 1602 1560 1517 1475 1433 1390 1347 Watts 285 297 309 321 333 346 358 370 CFM 1239 1184 1146 1091 1049 1001 948 890 Watts 152 163 175 184 194 205 220 235 CFM 1837 1789 1748 1706 1665 1623 1577 1...

Страница 15: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Страница 16: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Страница 17: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Страница 18: ...18 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 19: ...19 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 20: ...he feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and e...

Отзывы: