background image

21

Installer selects right or left side drain

and installs this hose accordingly.

Hose #1

Hose #2

45 degree

barb-pipe

adapter

45 degree

barb-pipe

adapter

Figure 22

Upflow Model Installed Horizontally with Right 

Side Down  

Minimum  5  ½”  clearance  is  required  for  the  drain  trap 

beneath the furnace.

1. 

Remove the clamps from both ends of the drain 

hoses.

2.  Remove the two screws holding the drain trap to the 

blower deck.

3.  Remove the trap and two hoses from the blower deck 

4.  Remove the two plugs from the right side of the 

cabinet and install them in the blower deck.

5.  (Draining the Vent Elbow ) Locate hose #2 (factory 

installed) and cut 1” away from the 45 degree bend, 

discard the 45 degree section. Insert hose #2 from 

outside the cabinet through the cabinet drain hole 

nearest the top, secure it to the barbed fitting in the 

elbow with a red clamp.

6.  For model DM92SS0403AN; locate the hose #2 

(factory installed) and cut 1.5” length from the end 

of the hose.  Insert hose #2 from outside the cabinet 

through the cabinet’s drain hole nearest to the top.  

Secure it to the barbed fitting in the elbow with a red 

clamp.

7.  (Draining the Collector Box) Install the non-grommet 

end of hose #11 from outside the cabinet in the 

bottom drain hole. Install on collector box and secure 

with a silver clamp.

8.  Use two silver clamps and secure the hoses to drain 

trap. The trap outlet faces the front of the furnace. 

Secure the trap to the cabinet using two screws 

removed in step 2 by inserting the two screws through 

the large set of holes in the top mounting tabs of the trap 

into the two predrilled holes in the side of the cabinet. 

9.  Refer to Field Supplied Drain section for instructions 

on field supplied / installed drain on outlet of furnace 

trap.

Hose #11

Hose #2

Figure 23

Upflow Model Installed Horizontally with Left 

Side Down

Minimum  5  ½”  clearance    is  required  for  the  drain  trap 

beneath the furnace.

*Also see Front Cover Pressure Switch Tube Location on 

page 10.

1.  Remove the clamps from the two drain tubes on the 

trap.  

2.  Remove the two screws holding the drain trap to the 

blower deck.

3.  Remove the trap and hoses from the blower deck .

4.  Remove the two plugs from the left side of the cabinet 

and install them in the blower deck.

5.  (Draining the Vent Elbow) Locate hose #6. Measuring 

from the non-grommet end; cut off and discard 1 ½”  

for a “D” width cabinet, 5” for a “C” width cabinet, 8 ½”  

for a “B” width cabinet.

6.  Remove the rubber plug from vent – drain elbow side 

port. Place hose #6 on the vent – drain elbow side 

port and secure with a silver clamp .

7.  Unused vent-drain elbow drip leg port must be 

sealed to prevent flue gases from escaping. Insert 

the rubber plug removed in step 6 into the unused 

elbow drain port. Inserting a blunt tool such as a 

3/16” Allen wrench into the center of the rubber 

plug will stretch the plug and allow complete 

insertion.

8.  Locate hose #5 and cut 3” from the non-grommet end. 

Discard the section without the grommet. 

9.  Insert the cut end of tube #5 through the lower cabinet 

drain hole.

10. Connect hose #6 & hose #5 using 100º elbow and 

secure with two red clamps 

11.  (Draining the Collector Box) Remove cap from left 

side collector box drain port (bottom in horizontal left 

position) and install it on right side (top) collector box 

drain port.

Содержание DM92SS

Страница 1: ...THIS SYMBOL AS A SAFETY PRECAUTION TABLE OF CONTENTS Safety Considerations 3 Shipping Inspection 4 Electrostatic Discharge ESD Precautions 5 To The Installer 5 Product Application 5 Location Requirem...

Страница 2: ...26 High Altitude Derate 26 Propane Gas Conversion 26 Gas Piping Connections 26 Gas Piping Checks 29 Propane Gas Tanks and Piping 29 Circulating Air Filters 29 Duct work Air Flow 29 Checking Duct Stati...

Страница 3: ...gas fired furnace for installation in a residential garage must be installed as specified in the LOCATION REQUIREMENTS AND CONSIDERATIONS section of this manual This furnace may be used as a construc...

Страница 4: ...electrical shock the furnace must be located to protect the electrical components from water Drain trap must be primed at time of installation Trap is internally partitioned add water to both inlet po...

Страница 5: ...ith static electricity i e do not move or shuffle your feet do not touch ungrounded objects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discha...

Страница 6: ...and the service area around the unit must have flooring To ensure proper furnace operation install operate and maintain the furnace in accordance with these installation and operation instructions al...

Страница 7: ...above substances This protects the non direct vent furnace from airborne contaminants To ensure that the enclosed non direct vent furnace has an adequate supply of combustion air vent from a nearby u...

Страница 8: ...nting system may be too large to properly vent the remaining attached appliances POSITION SIDES REAR FRONT BOTTOM FLUE TOP Upflow 0 0 3 C 0 1 Horizontal 6 0 3 C 0 6 C If placed on combustible floor fl...

Страница 9: ...ant l un des essais d crits ci dessus des correctifs doivent tre apport s au syst me de ventilation conform ment au National Fuel Gas Code ANSI Z223 1 NFPA 54 et ou au Code d installation du gaz natur...

Страница 10: ...tal counterflow furnaces return ductwork must be attached to the basepan top end of the blower compartment NOTE Ductwork must never be attached to the back of the furnace Contact your distributor for...

Страница 11: ...gy content difference between natural and propane gas High Stage Low Stage Natural None 45 3 5 w c 1 9 w c None Propane LPM 07 1 1 25mm 10 0 w c 6 0 w c None Gas Altitude Kit Orifice Manifold Pressure...

Страница 12: ...aterials and Joining Methods Two three inch nominal diameter PVC Schedule 40 pipe meeting ASTM D1785 PVC primer meeting ASTM F656 and PVC solvent cement meeting ASTM D2564 specifications must be used...

Страница 13: ...es above ground level or the anticipated snow level Vent terminations non direct and direct vent must terminate at least 3 feet above any forced air inlet located within 10 feet NOTE This provision do...

Страница 14: ...pipe Secure vent flue pipe directly into the furnace fitting with the appropriate glue Alternately a small section of 2 pipe may be glued in the furnace socket and a rubber coupling installed to allow...

Страница 15: ...er outlet 5 Install cut end of the flanged section and connect to inducer with rubber coupling supplied with furnace Install screws removed in step 1 securing flange to cabinet MODEL PIPE SIZE 1 2 3 4...

Страница 16: ...per material manufacturers specifications to prevent separation and flue gas leaks Figure 11 Insert flange Cut 2 long R 000142 F Figure 9 CUT HERE Figure 10 Vent Flue Pipe Cuts Upflow Horizontal model...

Страница 17: ...secured to the combustion air intake to prevent inadvertent blockage The tee used in the vent flue termination must be included when determining the number of elbows in the piping system Vent Flue Pi...

Страница 18: ...r specific details on termination construction For details concerning connection of pipes to the furnace refer to the Vent Flue Pipe and Combustion Pipe Standard Furnace Connections or Alternate Furna...

Страница 19: ...ecifications Condensate Drain Lines Drain Trap Acondensing gas furnace achieves its high level of efficiency by extracting heat from the products of combustion to the point where condensation takes pl...

Страница 20: ...ay be added in the area shown in Figure 21 Any unused cabinet opening must be sealed Do not allow drain hose to sag or trap water Figure 21 Drain Exiting Right Side 1 Locate and Install the 45 pipe ho...

Страница 21: ...the top mounting tabs of the trap into the two predrilled holes in the side of the cabinet 9 Refer to Field Supplied Drain section for instructions on field supplied installed drain on outlet of furn...

Страница 22: ...he non grommet end Discard the section without the grommet 5 Insert the cut end of tube 5 through the lower cabinet drain hole 6 Insert 100 degree elbow in the cut end of hose 5 7 Locate hose 6 Using...

Страница 23: ...ses needed for installation and install per the following directions 1 Remove the drain trap and factory installed drain tube assemblies 2 Remove two 1 plugs from right side of cabinet 3 Draining the...

Страница 24: ...n hole 12 Insert 100 elbow in hose 5 and secure with a red clamp 13 Locate hose 4 and cut a cut off a 4 straight section and discard the radius end 14 Connect the 4 straight section of hose 4 to the 1...

Страница 25: ...low NOTE Wire routing must not to interfere with circulator blower operation filter removal or routine maintenance Junction Box Relocation WARNING HIGH VOLTAGE To avoid personal injury or death due to...

Страница 26: ...t not be exceeded to prevent unit overfiring High Altitude Derate When this furnace is installed at high altitude the appropriate High Altitude orifice kit must be applied This is required due to the...

Страница 27: ...1 8 NPT pipe plug fitting accessible for test gauge connection immediately upstream of the gas supply connection to the furnace Always use a back up wrench when making the connection to the gas valve...

Страница 28: ...ation Gas Valve Burners Manual Shut Off Valve upstream from ground joint pipe union Drip Leg Grommet in Standard Gas Line Hole Ground Joint Pipe Union Ground Joint Pipe Union NOTE Union may be inside...

Страница 29: ...de NSCNGPIC CAN CSA B149 1 15 For satisfactory operation propane gas pressure must be 10 WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on thre...

Страница 30: ...an air conditioner coil or Electronic Air Cleaner is used in conjunction with the furnace the readings must also include theses components as shown in the following drawing 4 Consult proper tables for...

Страница 31: ...e furnace The installation of a centrally installed air cleaner cabinet or a return duct filter installation may offer more practicality Clean Comfort brand MERV 11 air cleaners have 5 media filters a...

Страница 32: ...t angle 2000 CFM 20 in X 25 in x 5 AM11 2025 5RA AM11 5RA Bottom return platform 2000 CFM 20 in X 25 in x 5 AM11 2832 5PP Bottom return platform 2000 CFM 20 in X 25 in x 5 AM11 2843 5PP AM11 5 2 X 160...

Страница 33: ...ances on the same gas supply line 4 Measure furnace gas supply pressure with burners firing Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table If supply pressure...

Страница 34: ...pplier if additional input rate adjustment is required 4 Turn ON gas to and relight all other appliances turned off in step 1 Be certain that all appliances are functioning properly and that all pilot...

Страница 35: ...als 4 Connect all unused blower motor leads to the PARK terminals on the integrated control module Any leads not connected to the PARK terminals must be taped 5 Turn ON power to furnace 6 Verify prope...

Страница 36: ...heat exchanger compartment temperatures It is a normally closed electrically automatic reset temperature activated sensor The limit guards against overheating as a result of insufficient conditioned...

Страница 37: ...following a one hour lockout period 2 Manual power interruption Interrupt 115 volt power to the furnace 3 Manual thermostat cycle Lower the thermostat so that there is no longer a call for heat for 1...

Страница 38: ...condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as necessary Flame Sensor Qualified Servicer Only Under some conditions the fuel or air supply c...

Страница 39: ...Loose or improperly connected wiring Pressure switch circuit not closed Induced draft blower isoperating Induced draft blower runs continuously with no further furnace operation Integrated control mo...

Страница 40: ...peration Rollout limit open Integrated control module fuse is blown Check burners for proper alignment Check flue and air inlet piping for blockage proper length elbows and termination Correct as nece...

Страница 41: ...N A 1203 N A 1158 N A 1111 1058 932 HIGH 5 0 2235 38 2166 39 2110 40 2021 42 1956 44 1855 1740 1618 MED 4 0 1955 44 1921 44 1860 46 1808 47 1746 49 1645 1572 1461 MED LO 3 5 1658 51 1634 52 1590 54 15...

Страница 42: ...OX 1 TO115 VAC 1 60HZ OR ID BLOWER PRESSURE SWITCH HEAT H GND WH RD WH GND BURNER COMPARTMENT BLOWER COMPARTMENT N O COOL H BK HI BR BR CAPACITOR YL WH CONTROL PRIMARY LIMIT AUTO RESET BL PU MANUAL RE...

Страница 43: ...nimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less...

Страница 44: ...se DB F Delta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG...

Страница 45: ...45 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 46: ...46 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 47: ...47 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 48: ...e protec on of the standard warranty registering your product is a rela vely short process and en tles you to addi onal warranty protec on except that failure by California and Quebec residents to reg...

Отзывы: