background image

32

3

4

+5%*

OFF

OFF

-5%

ON

OFF

10%

OFF

ON

-10%

ON

ON

Switch Bank: S3

Adjust Taps

DIP Switch  No.

(*Indicates factory setting)

NOTE: To enable adjustments and select -5, 5, -10 or 10%
trim, you must set dip switch S5-2 to ON.  If S5-2 is in the
OFF position, you will receive 0% trim.

Profile D

 ramps up to 50% of the demand for 1/2 minute,

then ramps to 85% of the full cooling demand airflow
and operates there for approximately 7 1/2 minutes.  The
motor then steps up to the full demand airflow.  Profile D
has a 1/2 minute at 50% airflow OFF delay.

OFF

OFF

7. Select the heating speed for your model from the heating

speed chart in the Specification Sheet.  The adjust setting
(already established by the cooling speed selection)
determines which set of speeds are available.  The
selected speed must provide a temperature rise within
the rise range listed with the particular model.

Example:

If the DM80VC0604BX is set for 1210 CFM
on cooling, the “ADJUST” is set to “+” (plus).
The four heating speeds available are “A
Plus”, “B Plus”, “C Plus”, and “D Plus”.   “A
Plus” has a rise of 38

°

F for both stages

which is within the 20-50°F rise range for
the DM80VC0604BX.  This setting will keep
electrical consumption to a minimum.  Set
the “Heat” speed DIP switches to “A”.

3

4

A

OFF

OFF

 B*

ON

OFF

C

OFF

ON

D

ON

ON

Switch Bank: S4

Heating

Airflow

DIP Switch  No.

(*Indicates factory setting)

8. Select the desired “heating” speed tap by positioning

switches S4- 3, 4 appropriately.  Refer to figure above.
Verify CFM by noting the number displayed on the dual
7-segment LED display.

In general lower heating speeds will: reduce electrical consump-
tion, lower operating sound levels of the blower, and increase
the outlet air temperature delivered to the home.   The speeds
available allow the blower performance to be optimized for the
particular homeowner’s needs.

B

LOWER

 H

EAT

 O

FF

 D

ELAY

 T

IMINGS

The integrated control module provides a selectable heat off
delay function. The heat off delay period may be set to 90, 120,
150, 180 seconds using the DIP switches or jumper provided
on the control module. The delay is factory shipped at 150
seconds but may be changed to suit the installation require-
ments and/or homeowner preference. Refer to the following fig-
ures for switch positions and corresponding delay times.

1

2

90 s econds

OFF

OFF

120 s econds

ON

OFF

150 s ec onds *

OFF

ON

180 s econds

ON

ON

(*Indic ates   f ac tory  s etting)

Heat OFF Delay

DIP Sw itc h No.

Sw itch Bank : S1

Heat Off Delay Dipswitches

C

OMFORT

N

ET

™ S

YSTEM

O

VERVIEW

The ComfortNet system is a system that includes a ComfortNet
compatible furnace and air conditioner or heat pump with a
CTK0* thermostat.  A valid ComfortNet system could also be a
compatible furnace, CTK0* thermostat and non-compatible,
single stage air conditioner.  Any other system configurations
are considered invalid ComfortNet systems and must be con-
nected as a traditional (or legacy) system (

see Electrical Con-

nections

 for wiring connections).

A ComfortNet heating/air conditioning system differs from a non-
communicating/traditional system in the manner in which the
indoor unit, outdoor unit and thermostat interact with one an-
other.  In a traditional system, the thermostat sends commands
to the indoor and outdoor units via analog 24 VAC signals.  It is
a one-way communication path in that the indoor and outdoor
units typically do not return information to the thermostat.

In a ComfortNet system, the indoor unit, outdoor unit, and ther-
mostat comprising a ComfortNet system “communicate” digi-
tally with one another. creating a two-way communications path.
The thermostat still sends commands to the indoor and out-
door units.  However, the thermostat may also request and
receive information from both the indoor and outdoor units.  This
information may be displayed on the CTK0* thermostat.  The
indoor and outdoor units also interact with one another.  The

Содержание DM80VC

Страница 1: ...ollow them The precautions listed in this Installation Manual are intended as supplemental to existing practices However if there is a direct conflict between existing practices and the content of thi...

Страница 2: ...STALLATION 15 FIX 1 LINER TERMINATION 15 FIX 2 CHANGE VENTING ARRANGEMENTS 15 FIX 3 REBUILD THE CROWN 16 FIX 4 RELINING 16 ELECTRICAL CONNECTIONS 16 WIRING HARNESS 17 115 VOLT LINE CONNECTIONS 17 JUNC...

Страница 3: ...EQUENCE OF OPERATION 36 POWER UP 36 HEATING MODE 36 COOLING MODE 38 FAN ONLY MODE 38 OPERATIONAL CHECKS 38 SAFETY CIRCUIT DESCRIPTION 38 INTEGRATED CONTROL MODULE 39 PRIMARY LIMIT 39 AUXILIARY LIMIT 3...

Страница 4: ...in the LOCATION REQUIREMENTS AND CONSIDERATIONS section of this manual This furnace may be used as a construction site heater only if certain conditions are met These conditions are listed in the PRO...

Страница 5: ...ERATURES AND WILL BE VACANT ALL WATER BEARING PIPES SHOULD BE DRAINED THE BUILDING SHOULD BE PROPERLY WINTERIZED AND THE WATER SOURCE CLOSED IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING T...

Страница 6: ...RE EXPLOSION SMOKE SOOT CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAINTENANCE OF THIS PRODUCT WARNING TO PREVENT PERSONAL INJURY OR DEA...

Страница 7: ...ollowing final construction clean up by a qualified person ELECTROSTATIC DISCHARGE ESD PRECAUTIONS NOTE Discharge body s static electricity before touching unit An electrostatic discharge can adversel...

Страница 8: ...l J Load Cal culations published by the Air Conditioning Contractors of America In the USA this furnace MUST be installed in accordance with the latest edition of theANSI Z223 1 booklet entitled Natio...

Страница 9: ...oximately 1 1 2 larger than the base of the furnace Ensure upflow or horizontal furnaces are not installed directly on carpeting or any other combustible material The only combustible material allowed...

Страница 10: ...EATER SHOULD TAKE PRECEDENCE OVER MINIMUM FIRE PRO TECTION CLEARANCE Agas fired furnace for installation in a residential garage must be installed so that the ignition source and burners are located n...

Страница 11: ...a mise en marche alors que tous les autres appareils raccord s au syst me de ventilation ne sont pas en marche 1 Sceller toutes les ouvertures inutilis es du syst me de ventilation 2 Inspecter le syst...

Страница 12: ...e from the right side of the cabinet When rotating the inducer a chimney transition bottom kit part 0270F01119 is needed for proper alignment of the inducer out let and the vent exit hole in the side...

Страница 13: ...peratures have a direct impact on the suitability of this type of venting In most situations the existing masonry chimneys will require a properly sized metallic liner POSSIBILITY OF PROPERTY DAMAGE P...

Страница 14: ...he lowest existing vent connector and examine the inside of the elbow or tee at the base of the liner Asmall amount of soot may be considered acceptable provided the installer vacuums it away If ruste...

Страница 15: ...gh PVC pipe Next use a flashlight and small mirror to sight up the liner B vent must be supported so as to not come into direct contact with the chimney walls or tile liner If it is not it can probabl...

Страница 16: ...A B149 2 latest editions and amendments To install the liner read and follow the liner manufacturer s in structions and your local codes Excess liner length should be pulled out of the chimney and cut...

Страница 17: ...configured for a right side electrical connection To make electrical connections through the opposite side of the furnace the junction box must be relocated to the left side prior to making electrical...

Страница 18: ...olt wiring NOTE For single stage cooling applications a jumper may be located between Y1 and Y2 at the furnace control in order to achieve the desired single stage cooling airflow Use of ramp ing prof...

Страница 19: ...HUM TRIM ENABLE Move to the ON position to enable dehumidification ON OFF S5 FOSSIL FUEL APPLICATIONS This furnace can be used in conjunction with a heat pump in a fossil fuel application A fossil fue...

Страница 20: ...NEUTRAL HUM OUT HUM IN 24VOLT HUMIDIFIER A 24 volt humidifier can be powered by feeding one of the HUM terminals with a field installed wire from the R terminal or by connecting to the NO side of the...

Страница 21: ...This unit is configured for natural gas The appropriate manufacturer s propane gas conversion kit must be applied for propane gas installations If converting to LP gas it is recommended that an LPLP0...

Страница 22: ...ough the left side of the furnace the installer must supply the following fittings starting from the gas valve 90 degree elbow Straight pipe to reach the exterior of the furnace A ground joint union d...

Страница 23: ...430 830 1 300 2 100 830 1 900 175 170 400 780 1 200 1 900 770 1 700 200 160 380 730 1 100 1 800 720 1 500 Sizing Between First and Second Stage Regulator Maxim um Propane Capacities listed are based o...

Страница 24: ...much external static pressure will result in insufficient air that can cause excessive temperature rise This can cause limit switch tripping and heat exchanger failure To determine total external duct...

Страница 25: ...used filters may also be centrally located 1 use 2 16X 25filters and two side returns or 20X 25filter on bottomreturn if furnace is connected to a cooling unit over 4tons nominal capacity Consider ins...

Страница 26: ...the setting Set the heat anticipator setting to 0 7 amps Follow the thermostat manufacturer s instructions on how to adjust the heat anticipa tor setting FURNACEOPERATION Purge gas lines of air prior...

Страница 27: ...apacity 4 The display will continue to flash Ft until high capacity 100 is achieved Once achieved the display will show Ft without flashing A 5 minute timer will be started to al low sufficient opport...

Страница 28: ...ecessary ad justments to pressure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer Reinstall plug befo...

Страница 29: ...PT hose barb fitting from the outlet pressure tap Replace the outlet pressure tap plug and seal with a high quality thread sealer b White Rodgers valve Turn outlet pressure test screw in to seal press...

Страница 30: ...of seconds per cubic foot sec ft3 of gas being delivered to the furnace If the dial is a two cubic foot dial divide the number of seconds recorded in step 2 by two 4 Calculate the furnace input in BT...

Страница 31: ...or other devices may require specific air flows consult installa tion instructions of those devices for requirements 3 Knowing the furnace model locate the high stage cooling air flow charts in the S...

Страница 32: ...F DELAY TIMINGS The integrated control module provides a selectable heat off delay function The heat off delay period may be set to 90 120 150 180 seconds using the DIP switches or jumper provided on...

Страница 33: ...anual for the airflow delivered during cooling or heat pump heating In continuous fan mode the CTK0 thermostat provides the airflow demand The thermostat may be configured for a low medium or high con...

Страница 34: ...le Single Stage AC ComfortNet G W1 W2 Y1 Y2 O 1 2 R C 4 Position Connectors from CTK0 Thermostat Kit System Wiring between Furnace and Non Communicating CompatibleSingleStageAirConditioner NOTE When u...

Страница 35: ...heat demand Humidity Fan Speed 1 2 3 4 Select Humidity Fan Speed this option is enabled when Humidity Setting of IND is selected 1 25 2 50 3 75 4 100 of maximum airflow SET UP Submenu Item Indication...

Страница 36: ...in 2 increments default is 0 Selects the airflow trim amount for the non communicating compatible single stage AC unit Cool Airflow Profile CL PRFL A B C or D default is A Selects the airflow profile...

Страница 37: ...nications Failure 2 Flashes Out of box reset Green Receive LED Off Nopower Communications error 1 Steady Flash No network found Rapid Flashing Normal network traffc On Solid Data 1 Data 2 miss wire Po...

Страница 38: ...thermostat contacts open completing the call for cool Outdoor fan and compressor are de energized Circulator blower continues running during a cool off delay period The OFF delay time and airflow leve...

Страница 39: ...cable to both installed and uninstalled ungrounded furnaces 1 Disconnect all power to the furnace Do not touch the integrated control module or any wire connected to the control prior to discharging y...

Страница 40: ...r flame and flame signal Drainage system Check for blockage and or leakage Check hose connections at and internal to furnace Wiring Check electrical connections for tightness and or corrosion Check wi...

Страница 41: ...hanger flue passageways should be inspected at the beginning of each heating season BEFORE LEAVING AN INSTALLATION Cycle the furnace with the thermostat at least three times Verify cooling and fan onl...

Страница 42: ...for Service icon illuminated ComfortNet thermostat scrolls Check Furnace message E0 Furnace lockout due to an excessive number of ignition retries 3 total LOCKOUT E0 Failure to establish flame Cause m...

Страница 43: ...and ductwork for blockage Clean or remove filters obstruction Check circulator blower speed and performance Correct speed or replace blower motor if necessary Check burners for proper alignment Check...

Страница 44: ...d improperly Blocked fue and or inlet air pipe blocked drain system or weak induced draft blower Incorrect pressure switch set point or malfunctioning switch contacts Loose or improperly connected wir...

Страница 45: ...ntrol module has lost communications with circulator blower motor MOTOR COMM b1 Loose wiring connection at circulator motor control leads Failed circulator blower motor Failed integrated control modul...

Страница 46: ...t scrolls Check Furnace message b7 MOTOR PARAMS b7 Furnace operates at reduced performance or Integrated control module LED display provides b9 error code b9 LOW ID AIRFLOW B9 Blocked filters Restrict...

Страница 47: ...D 115 VAC POLARITY DATANOT YET ON NETWORK INVALID MEMORYCARD DATA BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS MATCH BLOWER MOTOR OPERATING IN POWER TEMPERATURE OR SPEED LIMIT BLO...

Страница 48: ...ff Delay Short Run 30s ec 50 DC80VC0805C DM 80VC0803B DM 80VC0804C DM 80VC0805C Speed Selection Dip Switches C o o l Selec tio n Switc hes A djus t Selec tio n Switches P ro file Selec tio n Switc hes...

Страница 49: ...dd 5 Off Off Minus 5 On Off Add 10 Off On Minus 10 On On A Off Off B On Off C Off On D On On A Off Off B On Off C Off On D On On Disabled Off Enabled On Disabled Off Enabled On 25 Off Off 50 On Off 75...

Страница 50: ...1800 C D 60 sec 100 7 5 min 82 60 sec 100 To Set Airflow 1 Select model and desired High Stage CoolingAirflow Determine the corresponding tap A B C or D Set dip switches S3 1 and S3 2 to the appropria...

Страница 51: ...51 THIS PAGE LEFT INTENTIONALLY BLANK...