Installation Manual 3P581074-1D
DGE601A51/DGE602A51
29
English
3.5
Connecting to equipment which inputs output contact
points
By way of the output contact points on the DGE601A51, you can control other equipment,
by connecting to the contact input points on the other equipment.
WARNING
•
Be sure to perform the operation during power-off conditions. Not doing so
may cause an electric shock.
•
Do not clamp high-current cables together with low-current cables.
3.5.1
Terminals location and schematic connection diagram
<Schematic drawing of Do connection>
D
O
Di 1-4
A
DGE601A51
1a
1b
2a
2b
3a
3b
Do
Z1
Z2
Z3
Z1
Z2
Z3
L1
L2
L3
Lighting
Field supply
Fan
Buzzer
Operation lamp
Load L1 to L3 example
A
Do
Connect the contact output lines to the
[1a]
[1b]
[2a]
[2b]
[3a
DGE601A51 only
] [3b
DGE601A51 only
]
terminals of Do located on the upper part of the front face.
Connect
[1a]
to
[1b]
,
[2a]
to
[2b]
, and
[3a]
to
[3b]
.
Be sure to insert a diode on both ends of the relay coil. (A diode builtin type is recom
mended)
Contact point specifications
• Nonvoltage contact point
• Voltage: 24 V DC Maximum load current: 50 mA
3.5.2
Wiring specifications
•
Cable type: CPEV cable, FCPEV cable, CVV(S) cable
• Core thickness: CPEV cable, FCPEV cable:
φ
0.65 0.9 mm
CVV(S) cable: 0.75 - 1.25 mm²
• Cable length: 200 m or less
01_EN_3P581074-1D.indd 29
2021/06/22 13:00:19