Installation Manual 3P581074-1D
DGE601A51/DGE602A51
35
English
3.7.2
Wiring specifications
•
Cable type: Ordinary tough rubber sheathed cord (60245 IEC 53) equivalent or higher
Ordinary polyvinyl chloride sheathed cord (60227 IEC 53) equivalent or
higher
• Core thickness: Power wire: 1.0 2.0 mm²
Earth lead: Size must comply with local codes and be the same
thickness as the power wire.
•
Earth lead terminal treatment: Be sure to use a round crimp-type terminal (2-M4).
•
Power supply voltage: Single phase 100 to 240 V AC (at 50/60 Hz)
• Electric power consumption: 23 W
• Earth leakage breaker: Rated current 10 A (Rated sensitivity current 30 mA operating
time 0.1 sec or less)
3 mm minimum contact gap and allpole disconnection
CAUTION
•
Be sure to install an earth leakage breaker capable of shutting down the power
supply to the entire system, as required.
•
Turning on/off the earth leakage breaker turns on/off the power supply to the
DGE601A51.
•
Select an earth leakage breaker that offers protection against overcurrent and
short-circuit. When the earth leakage breaker only serves as earth device,
make sure to also install a wiring interrupter.
•
The power supply requires earth leakage breaker installation and earth wire
connection. After installing an earth leakage breaker, be sure to connect only
the DGE601A51 to it.
•
To prevent accidents due to wire breakage or disconnection, secure the power
supply cables with clamps.
•
Be sure to connect the earth wire.
•
Do not connect the earth wire to gas or water pipes, lighting rods, or telephone
earth wires.
•
Replace the unit when the unit cannot be turned on due to the blowing of the
electrical fuse.
NOTE
A power supply cable is not provided with the unit.
Use a 3-core power supply cable with a core thickness of 1.0 - 2.0 mm
2
that complies
with local standards and is rated at 300 V AC or higher.
01_EN_3P581074-1D.indd 35
2021/06/22 13:00:20
Содержание DGE601A51
Страница 1: ...Model DGE601A51 DGE602A51 Installation Manual 3P581074 1D 01_EN_3P581074 1D indd 1 2021 06 22 13 00 16...
Страница 2: ...01_EN_3P581074 1D indd 2 2021 06 22 13 00 16...
Страница 67: ...01_EN_3P581074 1D indd 65 2021 06 22 13 00 28...
Страница 68: ...3P581074 1D EM18A018A 2107 HT 01_EN_3P581074 1D indd 66 2021 06 22 13 00 28...