Installation Manual 3P581074-1D
DGE601A51/DGE602A51
15
English
Wiring to each terminal
When wiring to
[plus ADP IF
DGE601A51 only
]
,
[RS-485]
,
[DIII-1]
,
[DIII-2
DGE601A51 only
]
,
[Do]
,
[Di 1-4]
, and
[Di 5-8
DGE601A51 only
]
, perform operations on the terminal block and
carry out the wiring as shown below.
(1)
Push in the opening knob with a precision flat-head screwdriver and open the inser
tion port.
(2)
Insert the cable into the open insertion port.
(3)
Move the opening knob forward and down and insert the cable.
(4)
Make sure that the connected cable has not come out.
When using stranded cable, make sure that no strands are protruding.
<How to wire to the terminal block>
A
(1)
(1)
(2)
(3)
A
Precision flat-head screwdriver
Make the length of the peeled portion of the cable 9 mm.
Refer to the
[strip gauge]
on the unit.
When peeling, be careful not to scratch the finish of the exposed part of the cable.
<Cable peeling allowance>
9 mm
Good example
Bad example
Frayed
Too short
Bent
Too long
01_EN_3P581074-1D.indd 15
2021/06/22 13:00:17