Installation Manual 3P581074-1D
DGE601A51/DGE602A51
53
English
Setting “Remote controller group MAIN” DIII-NET addresses
This section describes how to set
“Remote controller group MAIN”
DIIINET addresses.
1. Press and hold the Cancel button for 4 seconds or more.
The
[Service Settings]
menu is displayed.
<Step 1>
Cool
Set to
30
C
2.
Using the Up/Down buttons, select
[Group Address]
and press the Menu/OK button.
The
[Group Address]
menu is displayed.
<Step 2>
Test Operation
Maintenance Contact
Indoor Unit Air net Address
Return
Setting
Ser vice Settings
Field Settings
Min Setpoints Differential
1/3
Group Address
NOTE
The
[Group Address]
menu is not displayed when the DGE601A51 is not powered on.
Power on the DGE601A51 and wait for a while before trying to operate the remote
controller. The
[Group Address]
menu is also not displayed when the DGE601A51 is
not communicating with the indoor units normally. Check that the cables are connected
correctly.
3.
Using the Up/Down buttons, select
[Group Address (Group)]
and press the Menu/OK
button. The current address setting is displayed.
<Step 3>
Group Address (Unit)
Return
Setting
Group Address
Group Address (Group)
4. If an address is already
[Set]
, press the Menu/OK button to release the current address
setting. The mode indication changes from
[Set]
to
[Release]
, and you are now ready
to change the address.
<Step 4>
Gr Addr.
Set
1-00
Return
Release
Group Address (Group)
01_EN_3P581074-1D.indd 53
2021/06/22 13:00:27