background image

9

Drain Pan (Side View)

Drain Connection

Install condensate drain trap as shown. Use  3/4”  drain line 

and fittings or larger. Do not operate without trap. 

h

OrizOntal

 d

rain

 

Drainage of condensate directly onto the roof may be ac-

ceptable; refer to local code. It is recommended that a small 

drip pad of either stone, mortar, wood or metal be provided 

to prevent any possible damage to the roof. 

C

leaning

Due to the fact that drain pans in any air conditioning unit 

will have some moisture in them, algae and fungus will grow 

due to airborne bacteria and spores. Periodic cleaning is 

necessary to prevent this build-up from plugging the drain.

STARTUP, ADJUSTMENTS, AND CHECKS

P

re

-s

tartuP

 i

nstruCtiOns

STANDARD

SIDE DRAIN

DRAIN PLUG

(FACTORY-INSTALLED)

NOTE: 

Trap should be deep enough to offset maximum

unit static difference.  A minimum 4” trap is recommended.

Drain Plug

Roof Curb

See NOTE

Base Rail

Open Vent

2” Min

HIGH VOLTAGE! 

OND

 

THE

 

FRAME

 

OF

 

THIS

 

UNIT

 

TO

 

THE

 

BUILDING

 

ELECTRICAL

 

GROUND

 

BY

 

USE

 

OF

 

THE

 

GROUNDING

 

TERMINAL

 

PROVIDED

 

OR

 

OTHER

 

ACCEPTABLE

 

MEANS

. D

ISCONNECT

 

ALL

 

POWER

 

BEFORE

 

SERVICING

 

OR

 

INSTALLING

 

THIS

 

UNIT

T

O

 

AVOID

 

PERSONAL

 

INJURY

 

OR

 

DEATH

 

DUE

 

TO

 

ELECTRICAL

 

SHOCK

B

WARNING

T

O

 

PREVENT

 

PROPERTY

 

DAMAGE

 

OR

 

PERSONAL

 

INJURY

, D

O

 

NOT

 

START

 

THE

 

UNIT

 

UNTIL

 

ALL

 

NECESSARY

 

PRE

-

CHECKS

 

AND

 

TESTS

 

HAVE

 

BEEN

 

PERFORMED

.

CAUTION

Prior to the beginning of Startup, Adjustments, and Checks 

procedures, the following steps should be completed in the 

building.

h

eating

 s

tartuP

 

On new installations, or if a major component has been re-

placed, the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. 

If any sparking, odors, or unusual sounds are encountered, 

shut off electrical power and recheck for wiring errors, or ob-

structions in or near the blower motors. 

Duct covers must be 

removed before operating unit.

The Startup, Adjustments, and Checks procedure provides 

a step-by-step sequence which, if followed, will assure the 

proper startup of the equipment in the minimum amount of 

time. Air balancing of duct system is not considered part of 

this procedure. However, it is an important phase of any air 

conditioning system startup and should be performed upon 

completion of the Startup, Adjustments, and Checks proce-

dure. The Startup, Adjustments, and Checks procedure at 

outside ambients below 55°F should be limited to a readiness 

check of the refrigeration system with the required final check 

and calibration left to be completed when the outside ambient 

rises above 55°F.

t

emPOrary

 h

eating

 O

r

 C

OOling

If the unit is to be used for temporary heating or cooling, a 

“Startup, Adjustments, and Checks” must first be performed in 

accordance with this manual.  Damage or repairs due to fail-

ure to comply with these requirements are not covered under 

the warranty.  After the machines are used for temporary heat-

ing or cooling, inspect the coils, fans, and motors for unaccept-

able levels of construction dust and dirt and install new filters.

C

OntraCtOr

 r

esPOnsibility

The installing contractor must be certain that:

• All supply and return air ductwork is in place, properly 

sealed, and corresponds with installation instructions.

•  All thermostats are mounted and wired in accordance with 

installation instructions.

•  All electric power, all gas, hot water or steam line connec-

tions, and the condensate drain installation have been 

made to each unit on the job. These main supply lines must 

be functional and capable of operating all units simultane-

ously.

•  All filters are in place.

r

OOf

 C

urb

 i

nstallatiOn

 C

heCk

Inspect the roof curb for correct installation. The unit and curb 

assembly  should  be  level.  Inspect  the  flashing  of  the  roof 

mounting curb to the roof, especially at the corners, for good 

workmanship. Also check for leaks around gaskets. Note any 

deficiencies in a separate report and forward to the contractor.

MOVING MACHINERY HAZARD!

T

O

 

PREVENT

 

POSSIBLE

 

PERSONAL

 

INJURY

 

OR

 

DEATH

DISCONNECT

 

POWER

 

TO

 

THE

 

UNIT

 

AND

 

PADLOCK

 

IN

 

THE

 “OFF” 

POSITION

 

BEFORE

 

SERVICNG

 

FANS

.

WARNING

Содержание DCC Series

Страница 1: ... 3 Clearances 4 Roof Curb Post Installation Checks 5 Roof Top Duct Connections 5 Rigging Details 5 Electrical Wiring 6 Circulating Air and Filters 8 Condensate Drain Connection 8 Startup Adjustments and Checks 9 Air Flow Adjustments 10 INSTALLATION INSTRUCTIONS WARNING PROP 65 WARNING FOR CALIFORNIA CONSUMERS Cancer and Reproductive Harm www P65Warnings ca gov 0140M00517 A ONLY PERSONNEL THAT HAVE...

Страница 2: ...d performance is achieved after 72 hours of operation Rated performance is delivered at the specified airflow See product specification sheet for light commercial models Specification sheets can be found at www daikinac com for Daikin brand products Within the website please select the commercial products menu and then select the submenu for the type of product to be installed such as air conditio...

Страница 3: ...pt of any visible damage to shipment or container 2 Notify carrier promptly and request an inspection 3 In case of concealed damage carrier should be notified as soon as possible preferably within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Original invoice or ...

Страница 4: ...de on any surface as this may damage unit base The unit must be stored on a flat level surface Protect the condenser coil because it is easily damaged Roof Curb Installations Only Curb installations must comply with local codes and should be done in accordance with the established guidelines of the National Roofing Contractors Association Proper unit installation requires that the roof curb be fir...

Страница 5: ...ET UNIT ON CURB CAUTION Horizontal Discharge To convert to horizontal discharge remove the covers over the horizontal duct connections save washered screws Refer to IOD 7006 included in the literature pack for install ing horizontal duct covers to the downflow duct connections Flexible duct connectors between the unit and ducts are rec ommended Insulate and weatherproof all external ductwork and j...

Страница 6: ...an tilever curb is used care should be taken to center the unit Check for proper alignment and orientation of supply and return openings with duct Rigging Removal Remove spreader bars lifting cables and other rigging equipment ELECTRICAL WIRING For unit protection use a fuse or hacr circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protecti...

Страница 7: ...e absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 A ground lug is provided for this purpose Size grounding conductor in accordance with Table 250 95 of the National Electrical Code Do not use the ground lug for connecting a neutral conductor Remove plug in panel located at the condenser end of unit and route conduit to control box Remove plug in control ...

Страница 8: ...the thermostat 3 Use 18 AWG wire for 24V control wiring runs not ex ceeding 75 feet Use 16 AWG wire for 24V control wir ing runs not exceeding 125 feet Use 14 AWG wire for 24V control wiring runs not exceeding 200 feet Low volt age wiring may be National Electrical Code NEC Class 2 where permitted by local codes 4 Route thermostat wires from sub base terminals to the unit Control wiring should ent...

Страница 9: ...a step by step sequence which if followed will assure the proper startup of the equipment in the minimum amount of time Air balancing of duct system is not considered part of this procedure However it is an important phase of any air conditioning system startup and should be performed upon completion of the Startup Adjustments and Checks proce dure The Startup Adjustments and Checks procedure at o...

Страница 10: ... 4 3 Percent Voltage Unbalance 100 x 1 8 Percent voltage unbalance MUST NOT exceed 2 4 216 400 216 100 X AIR FLOW ADJUSTMENTS NOTE For 2 speed models airflow adjustments must be made on high speed i e 2nd stage cooling or in heat mode Refer to Motor Sheave Adjustments section When the final adjustments are complete the current draw of the motor should be checked and compared to the full load curre...

Страница 11: ...RCE lbs SHEAVE DIAMETER in TYPE New V belts will drop rapidly during the first few hours of use Check tension frequently during the first 24 hours of operation Tension should fall between the minimum and maximum force To determine the deflection distance from a normal position measure the distance from sheave to sheave using a straightedge or a cord This is your refer ence line On multiple belt dr...

Страница 12: ...G After the cooling mode is checked out turn the thermo stat system switch to OFF 10 Turn the thermostat system switch to HEAT and fan switch to AUTO 11 Slowly raise the heating temperature setting When the heating first stage makes contact stop raising the tem perature setting The compressor blower and fan should now be running with the reversing valve in the de ener gized heating position After ...

Страница 13: ...ature of the refrigerant in the outdoor coil must be below the tempera ture of the outdoor air in order to extract heat from the air Thus the greater the difference in the outdoor temperature and the outdoor coil temperature the greater the heating capacity of the heat pump This phenomenon is a char acteristic of a heat pump It is a good practice to provide supplementary heat for all heat pump ins...

Страница 14: ...ENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS NEVER OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM Cabinet Finish Maintenance Use a fine grade automotive wax on the cabinet finish to maintain the finish s original high luster This is especial ly important in installations with extended periods of direct sunlight Clean Outside Coil Qualified Service...

Страница 15: ... shift a Undercharged check for leaks b Valve Body Damaged Replace valve c Unit Properly Charged If it is on the heating cycle raise the discharge pressure by restricting airflow through the indoor coil If the valve does not shift tap it lightly on both ends with a screwdriver handle DO NOT TAP THE VALVE BODY If the unit is on the cooling cycle raise the discharge pressure by restricting airflow t...

Страница 16: ...representsdry coil without filter to compensate for filter add 0 08 to measured E S P SCFM correction for wet coil 4 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 6 2793 1 64 2603 1 39 2450 1 18 2270 0 97 0 8 2903 1 87 2696 1 57 2369 1 23 2236 1 05 1987 0 82 1 0 2776 1 86 2682 5 1 69 2445 1 38 2196 1 12 1968 0 90 1 2 2599 1 71 2539 1 57 2310 1 29 1932 0 96 1 4 2424 1 57 2305 1 40 2032 1 11 1 6...

Страница 17: ...ORIZONTAL INCLUDES 2 SPEED MOTOR ON HIGH SPEED CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 6 2746 1 38 2515 1 12 0 8 2721 1 47 2494 1 21 2261 0 97 1 0 2689 1 56 2500 1 32 2255 1 06 1994 0 83 1 2 2752 1 74 2473 1 40 2252 1 15 1996 0 91 1 4 2802 1 88 2487 1 53 2286 1 27 2037 1 02 1 6 2553 1 67 2308 1 40 1997 1 08 1 8 2355 1 51 2014 1 19 2 2055 1 29 NOTES Table representsdry coil without filter...

Страница 18: ... 30 4 35 EHK4 20 24 0 3 3 37 9 40 EHK4 25 30 1 3 3 45 5 50 14 3 20 EHK4 10 12 0 18 6 20 EHK4 15 18 0 26 1 30 EHK4 20 24 0 33 6 35 EHK4 25 30 1 41 3 45 3 3 17 6 25 EHK4 10 12 0 3 3 22 8 25 EHK4 15 18 0 3 3 30 3 35 EHK4 20 24 0 3 3 37 8 40 EHK4 25 30 1 3 3 45 4 50 12 3 15 EHK7 10 10 0 15 4 20 EHK7 15 15 1 21 8 25 EHK7 20 20 0 27 9 30 EHK7 25 25 1 34 3 35 2 6 14 9 20 EHK7 10 10 0 2 6 18 6 20 EHK7 15 ...

Страница 19: ... 41 8 45 EHK4 20 24 0 3 3 49 3 50 EHK4 25 30 1 3 3 57 0 60 14 3 20 EHK4 10 12 0 29 3 30 EHK4 15 18 0 36 8 40 EHK4 20 24 0 44 3 45 EHK4 25 30 1 52 0 60 3 3 17 6 25 EHK4 10 12 0 3 3 32 6 35 EHK4 15 18 0 3 3 40 1 45 EHK4 20 24 0 3 3 47 6 50 EHK4 25 30 1 3 3 55 3 60 12 3 15 EHK7 10 10 0 24 8 25 EHK7 15 15 1 31 1 35 EHK7 20 20 0 37 3 40 EHK7 25 25 1 43 6 45 2 6 14 9 20 EHK3 10 10 0 2 6 27 4 30 EHK3 15 ...

Страница 20: ...DEL NUMBER MINIMUM CFM EHK 10 2100 EHK 15 2100 EHK 20 2100 EHK 25 2100 MINIMUM AIR FLOW FOR ELECTRIC HEAT 6 TON ATTENTION INSTALLING PERSONNEL Use only the heater kit specified for each model as dictated by the table above ...

Страница 21: ...URN SUPPLY 12 17 7 3 8 11 25 6 1 4 4 7 8 DRAIN THRU CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES BOTTOM VIEW OF UNIT 8 3 16 5 7 8 19 7 16 27 3 8 47 1 2 4 1 2 7 1 2 SUPPLY RETURN NOTE Refer to IOD 7006 included in the literature pack for installing horizontal duct covers ...

Страница 22: ...n the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH APPENDIX D WIRING DIAGRAMS DCC072 208 230 460 575 3 60 1 SPEED ...

Страница 23: ...the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 23 WIRING DIAGRAMS DCH072 208 230 3 60 1 SPEED ...

Страница 24: ...ring diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 24 DCH072 460 575 3 60 1 SPEED ...

Страница 25: ...NAL USE COPPER CONDUCTORS ONLY 2 IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON SHRT PLM AND CONNECT ECON PLM TO ECON PLF 3 TB3 LOW VOLTAGE TERMINAL BLOCK 4 TERMINALS FOR 24VAC PWR RD BR WIRE AND 6 TERMINALS FOR 24VAC COM BL WIRE 4 CONNECTIONS SHOWN ARE FOR 1 STAGE HEAT OPERATION WHEN 2 STAGE OPERATION IS REQIRED REMOVE JUMPER WIRE CONNECTING W2 TO W1 ON TB1 5 IF OPTIONAL SMOKE DETECTOR S ARE INS...

Страница 26: ...T1 T2 T3 CC OR RD BK OR RD YL BK T1 T3 COMP T2 EM BR OR RD BK WH OR BL GY BL YL GY BL YL GR RD BK 2 3 4 24V CNTL VOLTAGE LINE VOLTAGE TR1 LOW VOLTAGE FIELD WIRING HIGH VOLTAGE Y2 2ND STAGE COOL CALL OUTPUT Y1 1ST STAGE COOL CALL OUTPUT W2 2ND STAGE HEAT CALL OUTPUT W1 1ST STAGE HEAT CALL OUTPUT G C R TB1 CONNECTION 24VAC PWR INPUT THERMOSTAT IN OUT 24VAC COM INPUT FAN CALL OUTPUT THERMOSTAT CO NNE...

Страница 27: ...P T2 EM OR RD BK WH OR BL GY BL YL GY BL YL GR RD BK 2 3 4 24V CNTL VOLTAGE LINE VOLTAGE TR1 LOW VOLTAGE FIELD WIRING HIGH VOLTAGE Y2 2ND STAGE COOL CALL OUTPUT Y1 1ST STAGE COOL CALL OUTPUT W2 2ND STAGE HEAT CALL OUTPUT W1 1ST STAGE HEAT CALL OUTPUT G C R TB1 CONNECTION 24VAC PWR INPUT THERMOSTAT IN OUT 24VAC COM INPUT FAN CALL OUTPUT THERMOSTAT CONNECTIONS YELLOW PINK STRIPE YELLOW YL PK BL PK B...

Страница 28: ... TO ECON PLF 3 TB3 LOW VOLTAGE TERMINAL BLOCK 4 TERMINALS FOR 24VAC PWR RD BR WIRE AND 6 TERMINALS FOR 24VAC COM BL WIRE 4 CONNECTIONS SHOWN ARE FOR 1 STAGE HEAT OPERATION WHEN 2 STAGE OPERATION IS REQIRED REMOVE JUMPER WIRE CONNECTING W2 TO W1 ON TB1 5 IF OPTIONAL SMOKE DETECTOR S ARE INSTALLED REMOVE JUMPER WIRE CONNECTING S1 TO S2 ON TB1 WIRE CONNECTIONS FROM ACCESSORY KIT CONNECT RD WIRE TO TB...

Страница 29: ...2 L3 T1 T2 T3 CC OR RD BK OR RD YL BK T1 T3 COMP T2 EM OR RD BK WH OR BL GY BL YL GY BL YL GR RD BK 2 3 4 24V CNTL VOLTAGE LINE VOLTAGE TR1 LOW VOLTAGE FIELD WIRING HIGH VOLTAGE Y2 2ND STAGE COOL CALL OUTPUT Y1 1ST STAGE COOL CALL OUTPUT W2 2ND STAGE HEAT CALL OUTPUT W1 1ST STAGE HEAT CALL OUTPUT G C R TB1 CONNECTION 24VAC PWR INPUT THERMOSTAT IN OUT 24VAC COM INPUT FAN CALL OUTPUT THERMOSTAT CONN...

Страница 30: ...30 WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLS FOR COMPLETE INFORMATION AND INSTALLATION INSTRUCTIONS FOR MODELS WITH DDC CONTROLS SEE MANUAL DK DDC TGD XXX ...

Страница 31: ...3 60 SEE NOTE 2 BI7 CFS PK BL PK RD YL GR 1 4 HEATER PLF BK BK PU PU RD OR RD BK RD BK BC CC DAT AI1 GND AGND 24VAC AI4 AI5 AI6 AI7 AI8 AI2 AI3 BK BR GR BL BL BL RD 24V RD RD BL BL SEE NOTE 4 YL RD PK RD OR BK RD YL BK RD GR WH RD BL BL BL GR YL BR WH WH WH BR 2 3 5 6 7 8 9 BK BK RD BL AG C PU T5 T4 T3 T2 T1 TB2 TB1 RD SEE NOTE 5 CS PS ES XS RD BK PU BL OAT HGRH EXF ALRM AGND T3 GR AO3 AO2 AO1 COM...

Страница 32: ... PROVING SWITCH CONTACTOR COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CONDENSOR FAN CONDENSOR FAN CONTACTOR CLOGGED FILTER SWITCH CRANKCASE HEATER CRANKCASE HEATER SWITCH CONDENSER MOTOR COMMON C ON TB2 COMPRESSOR COM1 AND SMOKE DETECTOR DEFROST THERMOSTAT ECONOMIZER EVAPORATOR MOTOR ECON COM3 8 BI1 AND SMOKE DETECTOR EXHAUST FAN EQUIPMENT GROUND HOT GAS REHEAT HIGH PRESSURE SWITCH LOAD SHEDDI...

Страница 33: ...TER PLF C L2 BR BK BK DFT RD RD BK BK GR F C PU BK PU RD BK RD OR RD BK RD BK RCCF BK BC CFC CC DAT AI1 GND AGND 24VAC AI4 AI5 AI6 AI7 AI8 AI2 AI3 BK BR GR BL CHS RVC BL BL RD 24V RD RD BL BL RD SEE NOTE 4 YL RD PK RD OR BK RD YL BK RD RD BK RD RD BK RD GR WH RD BL BL BL GR BK YL BR WH WH WH OR BR OR BK RD BK BK RD 2 3 5 6 7 8 9 T2 T1 L1 BK BK RD BL BL BL AG C PU T5 T4 T3 T2 T1 TB2 TB1 RD SEE NOTE...

Страница 34: ...RY INPUTS BLOWER LOW SPEED BLOWER PROVING SWITCH COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CLOGGED FILTER SWITCH CRANKCASE HEATER CRANKCASE HEATER SWITCH CONDENSER MOTOR COMMON C ON TB2 COMPRESSOR COM1 AND SMOKE DETECTOR DEFROST THERMOSTAT ECONOMIZER EVAPORATOR MOTOR ECON COM3 8 AND SMOKE DETECTOR EXHAUST FAN EQUIPMENT GROUND HOT GAS REHEAT HIGH PRESSURE SWITCH LOAD SHEDDING LOW PRESSURE SWI...

Страница 35: ...BL PK 6 4 9 8 7 3 2 1 BI4 BI5 BI6 BI7 GND GND COM3 8 RL8 AO4 COM2 AO3 AO2 AO1 COM3 8 RL7 RL6 RL5 RL4 RL3 RL2 RL1 COM1 BL HGRH EXF ALRM RD YL PU BK T3 T2 T1 L2 L1 OR RD BK BL BL BL OR RD RD BK BL BL RD BK BK RD RD WH PK BK BK L3 T3 T2 T1 L2 L1 BK RD C BK PU RD RD YL BK BK RD SEE NOTE 4 575 C 460 BL 24V RD BL 24V SEE NO TE 5 RD RD TB1 RD BK PU PU PK YL PK BK PK AI1 BK BR GR BL DAT OAT BI8 AI2 AI3 AI...

Страница 36: ...Y EQUIPPED WHEN REQUIRED OR ORANGE AGND AO AI ALRM BC BCC BHS BI BLS BPSW CC CCR CFS CH CHR CHS CM COM COMP CS DFT ECON EM ES EXF GND HGRH HPS LDS LPS OAT OARH PLF PS RCCF RL RSS RVC SAT DAT SMK EMG SPCTEMP SPCRH T1 T5 TB1 2 TR1 2 XS DC GROUND FOR ANALOG SENSORS AG ON TB2 4 ANALOG OUTPUTS 8 ANALOG INPUTS ALARM BLOWER CONTACTOR BLOWER CONTACTOR COIL BLOWER HIGH SPEED 8 BINARY INPUTS BLOWER LOW SPEE...

Страница 37: ... 24VAC AI4 AI5 AI6 AI7 AI8 AI2 AI3 BK BR GR BL BL RD 24V RD RD BL BL SEE NOTE 4 YL RD PK BK GR WH RD BL BL GR GR YL BR BR WH WH 2 3 5 6 7 8 9 BK AG C PU T5 T4 T3 T2 T1 TB2 TB1 RD SEE NOTE 5 CS PS ES XS RD BK PU BL OAT HGRH EXF ALRM AGND GR AO3 AO2 AO1 COM3 8 RL7 RL6 RL5 RL4 RL3 RL2 RL1 COM1 BK 240 575 208 460 BL BL BPSW GR BK YL PK BL PK BL PK HPS LPS YL YL PK YL RD WH WH WH BK GR CO2 VOUT DC GND ...

Страница 38: ...VING SWITCH COMPRESSOR CONTACTOR COMPRESSOR 2ND STAGE SOLENOID CONDENSOR FAN CONDENSOR FAN CONTACTOR COIL CLOGGED FILTER SWITCH CRANKCASE HEATER CRANKCASE HEATER SWITCH CONDENSER MOTOR COMMON C ON TB2 COMPRESSOR DEFROST THERMOSTAT ECONOMIZER EVAPORATOR MOTOR ECON COM3 8 BI1 AND SMOKE DETECTOR EXHAUST FAN EQUIPMENT GROUND HOT GAS REHEAT HIGH PRESSURE SWITCH LOAD SHEDDING LOW PRESSURE SWITCH OUTDOOR...

Страница 39: ...AI2 AI3 BK BR GR CHS RVC BL BL RD 24V RD RD BL BL RD SEE NOTE 4 YL RD PK RD RD RD WH RD BL BL GR BK YL BR WH WH WH OR BR OR BK RD BK BK RD 2 3 5 6 7 8 9 T2 T1 L1 BL AG C PU T5 T4 T3 T2 T1 TB2 TB1 SEE NOTE 5 CS PS ES XS RD BK BL OAT HGRH EXF ALRM AGND GR AO3 AO2 AO1 COM3 8 RL7 RL6 RL5 RL4 RL3 RL2 RL1 COM1 BK BL BL 208 240 3 60 0140L06609 A GND VOUT DC OARH SPCRH STPT OFFSET GND TEMP SPCTEMP VOUT DC...

Страница 40: ... 2 COM1 RL1 RL2 COM2 COM3 8 AI3 RL3 RL4 RL5 CC RL6 CFC RL7 RL8 RVC 24VAC GND ECON PLF SMK EMG AO1 AO2 AO3 AO4 DDC BI4 2 2 208 240 3 60 208 240 3 60 SWITCH PRESS OVERCURRENT PROT DEVICE TERMINAL PLUG CONNECTION FIELD GROUND IGNITER JUNCTION INTERNAL TO INTEGRATED CONTROL SCHEMATIC SYMBOL SEE NOTE 5 HGRH EXF ALRM 0140L06610 A OARH CO2 SPC TEMP COM SENSOR OFFSET SPCRH SEE NOTE 4 CS BC1 AGND AO AI ALR...

Страница 41: ...6 RL5 RL4 RL3 RL2 RL1 COM1 BL HGRH EXF ALRM RD YL PU BK T3 T2 T1 L2 L1 BC2 RD BK BL BL OR RD BK BL BL RD BK RD WH PK BK BK L3 T3 T2 T1 L2 L1 BK RD C BK PU RD RD YL BK BK RD SEE NOTE 7 575 C 460 BL 24V RD BL 24V SEE NOTE 8 RD RD TB1 RD BK PU PU PK YL PK BK PK AI1 BK BR GR BL DAT OAT BI8 AI2 AI3 AI4 AI5 AI6 AI7 AI8 GND AGND 24VAC AGND AG C GR RD BK BL BL BL BR WH OR BR WH OR BK RD BK BL BPSW YL PK B...

Страница 42: ... BI BPSW CC CFS CH CHR CHS CM COM COMP DFT ECON EM ES EXF GND HGRH HPS LDS LPS OAT OARH PLF PS RCCF RL RSS RVC SAT DAT SMK EMG SPCTEMP SPCRH T1 T5 TB1 2 TR1 2 XS SD CS CFC TB1 T3 PM DC GROUND FOR ANALOG SENSORS AG ON TB2 4 ANALOG OUTPUTS 8 ANALOG INPUTS ALARM HIGH SPEED CONTACTOR LOW SPEED CONTACTOR 8 BINARY INPUTS BLOWER PROVING SWITCH COMPRESSOR CONTACTOR CLOGGED FILTER SWITCH CRANKCASE HEATER C...

Страница 43: ...ty service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place Check gas piping for leaks Verify gas pressure to the unit is within the range specified on the serial plate Check to ensure that all fans pulleys and wheels are secure Check for proper belt tension and alignment per installatio...

Страница 44: ...Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heating Supply Air Temperature PRESSURES Gas Inlet Pressure Gas Manifold Pressure Suction Circuit 1 Suction Circuit 2 Discharge Circuit 2 Superheat Orifice System Superheat Orifice System Subcooling TXV System S...

Страница 45: ...45 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 46: ...46 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 47: ...47 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 48: ...K Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page ...

Отзывы: