background image

12

To  confirm  charge  levels  or,  if  a  leak  occurs  and  charge 

needs to be added to the system, it is recommended to 

evacuate the system and recharge refrigerant to the unit’s 

nameplate specifications.  This unit has been rated in the 

cooling mode at the AHRI rated conditions of:  indoor (80°F 

db/67°F wb) and outdoor (95°F db).  While operating at this 

condition,  units with a piston type metering device should 

operate with a superheat range from 9° F to 11° F for each 

refrigeration circuit measured at the suction service port  lo-

cated near the compressor.  For units with a TXV metering 

device, the unit should operate within a subcooling range 

of 14° to 16° for each refrigeration circuit measured at the 

liquid line service port.

s

tart

-u

P

 P

rOCedure

 

and

 C

heCklist

Begin with power turned off at all disconnects.

a

ir

 C

OnditiOning

  s

tart

-u

P

 P

rOCedure

1.  Turn thermostat system switch to “Cool,” and fan switch 

to “Auto” and turn temperature setting as high as it will 

go.

2.  Inspect all registers and set them to the normal open 

position.

3.  Turn on the electrical supply at the disconnect.
4.  Turn the fan switch to the “ON” position. The blower 

should operate after a 7 second delay.

5.  Turn the fan switch to “Auto” position. The blower should 

stop after a 65 second delay.

6.  Slowly lower the cooling temperature until the unit starts. 

The compressor, blower and fan should now be operat-

ing. Allow the unit to run 10 minutes, make sure cool air 

is being supplied by the unit. On 2 stage models, (mod-

els with a “V” in the 11th position) the unit is  now operat-

ing on low speed. After the 10 minute run, continue low-

ering cooling temperature until blower speed increases 

indicating 2nd stage cooling. Make sure cool air is still 

being supplied by unit and proceed to step 7.

7.  Turn the temperature setting to the highest position, 

stopping the unit. The indoor blower will continue to run 

for 65 seconds.

8.    Turn the thermostat system switch to “OFF” and discon-

nect all power when servicing the unit.

h

eat

 P

umP

 s

tart

-u

P

 P

rOCedure

9.  Check the cooling mode for the heat pump in the 

same manner as above. The reversing valve is ener-

gized when the thermostat is placed in the cooling po-

sition. A clicking sound should be noticeable from the 

reversing valve.  By lowering the temperature setting 

to call for cooling, the contractor is energized.  The 

compressor, blower and fan should then be running.

HIGH VOLTAGE! 

D

ISCONNECT

 

ALL

 

POWER

 

BEFORE

 

SERVICING

 

OR

 

INSTALLING

 

THIS

 

UNIT

. M

ULTIPLE

 

POWER

 

SOURCES

 

MAY

 

BE

 

PRESENT

. F

AILURE

 

TO

 

DO

 

SO

 

MAY

 

CAUSE

 

PROPERTY

 

DAMAGE

PERSONAL

 

INJURY

 

OR

 

DEATH

.

WARNING

 

After the cooling mode is checked out, turn the thermo-

stat system switch to “OFF”.

10. Turn the thermostat system switch to “HEAT” and fan 

switch to “AUTO”.

11.  Slowly raise the heating temperature setting. When the 

heating first stage makes contact, stop raising the tem

-

perature setting.. The compressor, blower and fan should 

now be running with the reversing valve in the de-ener-

gized (heating) position. After giving the unit time to settle 

out, make sure the unit is supplying heated air.

12.  If the outdoor ambient is above 80°F, the unit may trip on 

its high pressure cut out when on heating. The compres-

sor should stop.  The heating cycle must be thoroughly 

checked, so postpone the test to another day when con-

ditions are more suitable but-DO NOT FAIL TO TEST.

 

If the outdoor ambient is low and the unit operates prop-

erly on the heating cycle, you may check the pressure 

cutout operation by blocking off the indoor return air until 

the unit trips.

13. If unit operates properly in the heating cycle, raise the 

temperature setting until the heating second stage makes 

contact. Supplemental resistance heat, if installed should 

now come on. Make sure it operates properly.

 

NOTE:

 If outdoor thermostats are installed the outdoor 

ambient must be below the set point of these thermostats 

for the heaters to operate. It may be necessary to jumper 

these thermostats to check heater operation if outdoor 

ambient is mild.

14. For thermostats with emergency heat switch, return to 

step 11. The emergency heat switch is located at the 

bottom of the thermostat. Move the switch to emergency 

heat. The heat pump will stop, the blower will continue to 

run, all heaters will come on and the thermostat emer-

gency heat light will come on.

15.  If checking the unit in the wintertime, when the outdoor 

coil is cold enough to actuate the defrost control, observe 

at least one defrost cycle to make sure the unit defrosts 

completely.

f

inal

 s

ystem

 C

heCks

16.  Check to see if all supply and return air grilles are adjust-

ed and the air distribution system is balanced for the best 

compromise between heating and cooling.

17.  Check for air leaks in the ductwork.  See Sections on 

Air 

Flow Adjustments.

18.  Make sure the unit is free of “rattles”, and the tubing in 

the unit is free from excessive vibration. Also make sure 

tubes or lines are not rubbing against each other or sheet 

metal surfaces or edges. If so, correct the trouble.

19.  Set the thermostat at the appropriate setting for cooling 

and heating or automatic changeover for normal use.

20. Be sure the Owner is instructed on the unit operation, 

filter, servicing, correct thermostat operation, etc.

r

efrigeratiOn

 P

erfOrmanCe

 C

heCk

Check that compressor RLA corresponds to values shown 

in Appendix B.  RLA draw can be much lower than values 

Содержание DCC Series

Страница 1: ... 3 Clearances 4 Roof Curb Post Installation Checks 5 Roof Top Duct Connections 5 Rigging Details 5 Electrical Wiring 6 Circulating Air and Filters 8 Condensate Drain Connection 8 Startup Adjustments and Checks 9 Air Flow Adjustments 10 INSTALLATION INSTRUCTIONS WARNING PROP 65 WARNING FOR CALIFORNIA CONSUMERS Cancer and Reproductive Harm www P65Warnings ca gov 0140M00517 A ONLY PERSONNEL THAT HAVE...

Страница 2: ...d performance is achieved after 72 hours of operation Rated performance is delivered at the specified airflow See product specification sheet for light commercial models Specification sheets can be found at www daikinac com for Daikin brand products Within the website please select the commercial products menu and then select the submenu for the type of product to be installed such as air conditio...

Страница 3: ...pt of any visible damage to shipment or container 2 Notify carrier promptly and request an inspection 3 In case of concealed damage carrier should be notified as soon as possible preferably within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond b Original paid freight bill or indemnity in lieu thereof c Original invoice or ...

Страница 4: ...de on any surface as this may damage unit base The unit must be stored on a flat level surface Protect the condenser coil because it is easily damaged Roof Curb Installations Only Curb installations must comply with local codes and should be done in accordance with the established guidelines of the National Roofing Contractors Association Proper unit installation requires that the roof curb be fir...

Страница 5: ...ET UNIT ON CURB CAUTION Horizontal Discharge To convert to horizontal discharge remove the covers over the horizontal duct connections save washered screws Refer to IOD 7006 included in the literature pack for install ing horizontal duct covers to the downflow duct connections Flexible duct connectors between the unit and ducts are rec ommended Insulate and weatherproof all external ductwork and j...

Страница 6: ...an tilever curb is used care should be taken to center the unit Check for proper alignment and orientation of supply and return openings with duct Rigging Removal Remove spreader bars lifting cables and other rigging equipment ELECTRICAL WIRING For unit protection use a fuse or hacr circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protecti...

Страница 7: ...e absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 A ground lug is provided for this purpose Size grounding conductor in accordance with Table 250 95 of the National Electrical Code Do not use the ground lug for connecting a neutral conductor Remove plug in panel located at the condenser end of unit and route conduit to control box Remove plug in control ...

Страница 8: ...the thermostat 3 Use 18 AWG wire for 24V control wiring runs not ex ceeding 75 feet Use 16 AWG wire for 24V control wir ing runs not exceeding 125 feet Use 14 AWG wire for 24V control wiring runs not exceeding 200 feet Low volt age wiring may be National Electrical Code NEC Class 2 where permitted by local codes 4 Route thermostat wires from sub base terminals to the unit Control wiring should ent...

Страница 9: ...a step by step sequence which if followed will assure the proper startup of the equipment in the minimum amount of time Air balancing of duct system is not considered part of this procedure However it is an important phase of any air conditioning system startup and should be performed upon completion of the Startup Adjustments and Checks proce dure The Startup Adjustments and Checks procedure at o...

Страница 10: ... 4 3 Percent Voltage Unbalance 100 x 1 8 Percent voltage unbalance MUST NOT exceed 2 4 216 400 216 100 X AIR FLOW ADJUSTMENTS NOTE For 2 speed models airflow adjustments must be made on high speed i e 2nd stage cooling or in heat mode Refer to Motor Sheave Adjustments section When the final adjustments are complete the current draw of the motor should be checked and compared to the full load curre...

Страница 11: ...RCE lbs SHEAVE DIAMETER in TYPE New V belts will drop rapidly during the first few hours of use Check tension frequently during the first 24 hours of operation Tension should fall between the minimum and maximum force To determine the deflection distance from a normal position measure the distance from sheave to sheave using a straightedge or a cord This is your refer ence line On multiple belt dr...

Страница 12: ...G After the cooling mode is checked out turn the thermo stat system switch to OFF 10 Turn the thermostat system switch to HEAT and fan switch to AUTO 11 Slowly raise the heating temperature setting When the heating first stage makes contact stop raising the tem perature setting The compressor blower and fan should now be running with the reversing valve in the de ener gized heating position After ...

Страница 13: ...ature of the refrigerant in the outdoor coil must be below the tempera ture of the outdoor air in order to extract heat from the air Thus the greater the difference in the outdoor temperature and the outdoor coil temperature the greater the heating capacity of the heat pump This phenomenon is a char acteristic of a heat pump It is a good practice to provide supplementary heat for all heat pump ins...

Страница 14: ...ENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS NEVER OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM Cabinet Finish Maintenance Use a fine grade automotive wax on the cabinet finish to maintain the finish s original high luster This is especial ly important in installations with extended periods of direct sunlight Clean Outside Coil Qualified Service...

Страница 15: ... shift a Undercharged check for leaks b Valve Body Damaged Replace valve c Unit Properly Charged If it is on the heating cycle raise the discharge pressure by restricting airflow through the indoor coil If the valve does not shift tap it lightly on both ends with a screwdriver handle DO NOT TAP THE VALVE BODY If the unit is on the cooling cycle raise the discharge pressure by restricting airflow t...

Страница 16: ...representsdry coil without filter to compensate for filter add 0 08 to measured E S P SCFM correction for wet coil 4 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 6 2793 1 64 2603 1 39 2450 1 18 2270 0 97 0 8 2903 1 87 2696 1 57 2369 1 23 2236 1 05 1987 0 82 1 0 2776 1 86 2682 5 1 69 2445 1 38 2196 1 12 1968 0 90 1 2 2599 1 71 2539 1 57 2310 1 29 1932 0 96 1 4 2424 1 57 2305 1 40 2032 1 11 1 6...

Страница 17: ...ORIZONTAL INCLUDES 2 SPEED MOTOR ON HIGH SPEED CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 6 2746 1 38 2515 1 12 0 8 2721 1 47 2494 1 21 2261 0 97 1 0 2689 1 56 2500 1 32 2255 1 06 1994 0 83 1 2 2752 1 74 2473 1 40 2252 1 15 1996 0 91 1 4 2802 1 88 2487 1 53 2286 1 27 2037 1 02 1 6 2553 1 67 2308 1 40 1997 1 08 1 8 2355 1 51 2014 1 19 2 2055 1 29 NOTES Table representsdry coil without filter...

Страница 18: ... 30 4 35 EHK4 20 24 0 3 3 37 9 40 EHK4 25 30 1 3 3 45 5 50 14 3 20 EHK4 10 12 0 18 6 20 EHK4 15 18 0 26 1 30 EHK4 20 24 0 33 6 35 EHK4 25 30 1 41 3 45 3 3 17 6 25 EHK4 10 12 0 3 3 22 8 25 EHK4 15 18 0 3 3 30 3 35 EHK4 20 24 0 3 3 37 8 40 EHK4 25 30 1 3 3 45 4 50 12 3 15 EHK7 10 10 0 15 4 20 EHK7 15 15 1 21 8 25 EHK7 20 20 0 27 9 30 EHK7 25 25 1 34 3 35 2 6 14 9 20 EHK7 10 10 0 2 6 18 6 20 EHK7 15 ...

Страница 19: ... 41 8 45 EHK4 20 24 0 3 3 49 3 50 EHK4 25 30 1 3 3 57 0 60 14 3 20 EHK4 10 12 0 29 3 30 EHK4 15 18 0 36 8 40 EHK4 20 24 0 44 3 45 EHK4 25 30 1 52 0 60 3 3 17 6 25 EHK4 10 12 0 3 3 32 6 35 EHK4 15 18 0 3 3 40 1 45 EHK4 20 24 0 3 3 47 6 50 EHK4 25 30 1 3 3 55 3 60 12 3 15 EHK7 10 10 0 24 8 25 EHK7 15 15 1 31 1 35 EHK7 20 20 0 37 3 40 EHK7 25 25 1 43 6 45 2 6 14 9 20 EHK3 10 10 0 2 6 27 4 30 EHK3 15 ...

Страница 20: ...DEL NUMBER MINIMUM CFM EHK 10 2100 EHK 15 2100 EHK 20 2100 EHK 25 2100 MINIMUM AIR FLOW FOR ELECTRIC HEAT 6 TON ATTENTION INSTALLING PERSONNEL Use only the heater kit specified for each model as dictated by the table above ...

Страница 21: ...URN SUPPLY 12 17 7 3 8 11 25 6 1 4 4 7 8 DRAIN THRU CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES BOTTOM VIEW OF UNIT 8 3 16 5 7 8 19 7 16 27 3 8 47 1 2 4 1 2 7 1 2 SUPPLY RETURN NOTE Refer to IOD 7006 included in the literature pack for installing horizontal duct covers ...

Страница 22: ...n the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH APPENDIX D WIRING DIAGRAMS DCC072 208 230 460 575 3 60 1 SPEED ...

Страница 23: ...the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 23 WIRING DIAGRAMS DCH072 208 230 3 60 1 SPEED ...

Страница 24: ...ring diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 24 DCH072 460 575 3 60 1 SPEED ...

Страница 25: ...NAL USE COPPER CONDUCTORS ONLY 2 IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON SHRT PLM AND CONNECT ECON PLM TO ECON PLF 3 TB3 LOW VOLTAGE TERMINAL BLOCK 4 TERMINALS FOR 24VAC PWR RD BR WIRE AND 6 TERMINALS FOR 24VAC COM BL WIRE 4 CONNECTIONS SHOWN ARE FOR 1 STAGE HEAT OPERATION WHEN 2 STAGE OPERATION IS REQIRED REMOVE JUMPER WIRE CONNECTING W2 TO W1 ON TB1 5 IF OPTIONAL SMOKE DETECTOR S ARE INS...

Страница 26: ...T1 T2 T3 CC OR RD BK OR RD YL BK T1 T3 COMP T2 EM BR OR RD BK WH OR BL GY BL YL GY BL YL GR RD BK 2 3 4 24V CNTL VOLTAGE LINE VOLTAGE TR1 LOW VOLTAGE FIELD WIRING HIGH VOLTAGE Y2 2ND STAGE COOL CALL OUTPUT Y1 1ST STAGE COOL CALL OUTPUT W2 2ND STAGE HEAT CALL OUTPUT W1 1ST STAGE HEAT CALL OUTPUT G C R TB1 CONNECTION 24VAC PWR INPUT THERMOSTAT IN OUT 24VAC COM INPUT FAN CALL OUTPUT THERMOSTAT CO NNE...

Страница 27: ...P T2 EM OR RD BK WH OR BL GY BL YL GY BL YL GR RD BK 2 3 4 24V CNTL VOLTAGE LINE VOLTAGE TR1 LOW VOLTAGE FIELD WIRING HIGH VOLTAGE Y2 2ND STAGE COOL CALL OUTPUT Y1 1ST STAGE COOL CALL OUTPUT W2 2ND STAGE HEAT CALL OUTPUT W1 1ST STAGE HEAT CALL OUTPUT G C R TB1 CONNECTION 24VAC PWR INPUT THERMOSTAT IN OUT 24VAC COM INPUT FAN CALL OUTPUT THERMOSTAT CONNECTIONS YELLOW PINK STRIPE YELLOW YL PK BL PK B...

Страница 28: ... TO ECON PLF 3 TB3 LOW VOLTAGE TERMINAL BLOCK 4 TERMINALS FOR 24VAC PWR RD BR WIRE AND 6 TERMINALS FOR 24VAC COM BL WIRE 4 CONNECTIONS SHOWN ARE FOR 1 STAGE HEAT OPERATION WHEN 2 STAGE OPERATION IS REQIRED REMOVE JUMPER WIRE CONNECTING W2 TO W1 ON TB1 5 IF OPTIONAL SMOKE DETECTOR S ARE INSTALLED REMOVE JUMPER WIRE CONNECTING S1 TO S2 ON TB1 WIRE CONNECTIONS FROM ACCESSORY KIT CONNECT RD WIRE TO TB...

Страница 29: ...2 L3 T1 T2 T3 CC OR RD BK OR RD YL BK T1 T3 COMP T2 EM OR RD BK WH OR BL GY BL YL GY BL YL GR RD BK 2 3 4 24V CNTL VOLTAGE LINE VOLTAGE TR1 LOW VOLTAGE FIELD WIRING HIGH VOLTAGE Y2 2ND STAGE COOL CALL OUTPUT Y1 1ST STAGE COOL CALL OUTPUT W2 2ND STAGE HEAT CALL OUTPUT W1 1ST STAGE HEAT CALL OUTPUT G C R TB1 CONNECTION 24VAC PWR INPUT THERMOSTAT IN OUT 24VAC COM INPUT FAN CALL OUTPUT THERMOSTAT CONN...

Страница 30: ...30 WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLS FOR COMPLETE INFORMATION AND INSTALLATION INSTRUCTIONS FOR MODELS WITH DDC CONTROLS SEE MANUAL DK DDC TGD XXX ...

Страница 31: ...3 60 SEE NOTE 2 BI7 CFS PK BL PK RD YL GR 1 4 HEATER PLF BK BK PU PU RD OR RD BK RD BK BC CC DAT AI1 GND AGND 24VAC AI4 AI5 AI6 AI7 AI8 AI2 AI3 BK BR GR BL BL BL RD 24V RD RD BL BL SEE NOTE 4 YL RD PK RD OR BK RD YL BK RD GR WH RD BL BL BL GR YL BR WH WH WH BR 2 3 5 6 7 8 9 BK BK RD BL AG C PU T5 T4 T3 T2 T1 TB2 TB1 RD SEE NOTE 5 CS PS ES XS RD BK PU BL OAT HGRH EXF ALRM AGND T3 GR AO3 AO2 AO1 COM...

Страница 32: ... PROVING SWITCH CONTACTOR COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CONDENSOR FAN CONDENSOR FAN CONTACTOR CLOGGED FILTER SWITCH CRANKCASE HEATER CRANKCASE HEATER SWITCH CONDENSER MOTOR COMMON C ON TB2 COMPRESSOR COM1 AND SMOKE DETECTOR DEFROST THERMOSTAT ECONOMIZER EVAPORATOR MOTOR ECON COM3 8 BI1 AND SMOKE DETECTOR EXHAUST FAN EQUIPMENT GROUND HOT GAS REHEAT HIGH PRESSURE SWITCH LOAD SHEDDI...

Страница 33: ...TER PLF C L2 BR BK BK DFT RD RD BK BK GR F C PU BK PU RD BK RD OR RD BK RD BK RCCF BK BC CFC CC DAT AI1 GND AGND 24VAC AI4 AI5 AI6 AI7 AI8 AI2 AI3 BK BR GR BL CHS RVC BL BL RD 24V RD RD BL BL RD SEE NOTE 4 YL RD PK RD OR BK RD YL BK RD RD BK RD RD BK RD GR WH RD BL BL BL GR BK YL BR WH WH WH OR BR OR BK RD BK BK RD 2 3 5 6 7 8 9 T2 T1 L1 BK BK RD BL BL BL AG C PU T5 T4 T3 T2 T1 TB2 TB1 RD SEE NOTE...

Страница 34: ...RY INPUTS BLOWER LOW SPEED BLOWER PROVING SWITCH COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR RELAY CLOGGED FILTER SWITCH CRANKCASE HEATER CRANKCASE HEATER SWITCH CONDENSER MOTOR COMMON C ON TB2 COMPRESSOR COM1 AND SMOKE DETECTOR DEFROST THERMOSTAT ECONOMIZER EVAPORATOR MOTOR ECON COM3 8 AND SMOKE DETECTOR EXHAUST FAN EQUIPMENT GROUND HOT GAS REHEAT HIGH PRESSURE SWITCH LOAD SHEDDING LOW PRESSURE SWI...

Страница 35: ...BL PK 6 4 9 8 7 3 2 1 BI4 BI5 BI6 BI7 GND GND COM3 8 RL8 AO4 COM2 AO3 AO2 AO1 COM3 8 RL7 RL6 RL5 RL4 RL3 RL2 RL1 COM1 BL HGRH EXF ALRM RD YL PU BK T3 T2 T1 L2 L1 OR RD BK BL BL BL OR RD RD BK BL BL RD BK BK RD RD WH PK BK BK L3 T3 T2 T1 L2 L1 BK RD C BK PU RD RD YL BK BK RD SEE NOTE 4 575 C 460 BL 24V RD BL 24V SEE NO TE 5 RD RD TB1 RD BK PU PU PK YL PK BK PK AI1 BK BR GR BL DAT OAT BI8 AI2 AI3 AI...

Страница 36: ...Y EQUIPPED WHEN REQUIRED OR ORANGE AGND AO AI ALRM BC BCC BHS BI BLS BPSW CC CCR CFS CH CHR CHS CM COM COMP CS DFT ECON EM ES EXF GND HGRH HPS LDS LPS OAT OARH PLF PS RCCF RL RSS RVC SAT DAT SMK EMG SPCTEMP SPCRH T1 T5 TB1 2 TR1 2 XS DC GROUND FOR ANALOG SENSORS AG ON TB2 4 ANALOG OUTPUTS 8 ANALOG INPUTS ALARM BLOWER CONTACTOR BLOWER CONTACTOR COIL BLOWER HIGH SPEED 8 BINARY INPUTS BLOWER LOW SPEE...

Страница 37: ... 24VAC AI4 AI5 AI6 AI7 AI8 AI2 AI3 BK BR GR BL BL RD 24V RD RD BL BL SEE NOTE 4 YL RD PK BK GR WH RD BL BL GR GR YL BR BR WH WH 2 3 5 6 7 8 9 BK AG C PU T5 T4 T3 T2 T1 TB2 TB1 RD SEE NOTE 5 CS PS ES XS RD BK PU BL OAT HGRH EXF ALRM AGND GR AO3 AO2 AO1 COM3 8 RL7 RL6 RL5 RL4 RL3 RL2 RL1 COM1 BK 240 575 208 460 BL BL BPSW GR BK YL PK BL PK BL PK HPS LPS YL YL PK YL RD WH WH WH BK GR CO2 VOUT DC GND ...

Страница 38: ...VING SWITCH COMPRESSOR CONTACTOR COMPRESSOR 2ND STAGE SOLENOID CONDENSOR FAN CONDENSOR FAN CONTACTOR COIL CLOGGED FILTER SWITCH CRANKCASE HEATER CRANKCASE HEATER SWITCH CONDENSER MOTOR COMMON C ON TB2 COMPRESSOR DEFROST THERMOSTAT ECONOMIZER EVAPORATOR MOTOR ECON COM3 8 BI1 AND SMOKE DETECTOR EXHAUST FAN EQUIPMENT GROUND HOT GAS REHEAT HIGH PRESSURE SWITCH LOAD SHEDDING LOW PRESSURE SWITCH OUTDOOR...

Страница 39: ...AI2 AI3 BK BR GR CHS RVC BL BL RD 24V RD RD BL BL RD SEE NOTE 4 YL RD PK RD RD RD WH RD BL BL GR BK YL BR WH WH WH OR BR OR BK RD BK BK RD 2 3 5 6 7 8 9 T2 T1 L1 BL AG C PU T5 T4 T3 T2 T1 TB2 TB1 SEE NOTE 5 CS PS ES XS RD BK BL OAT HGRH EXF ALRM AGND GR AO3 AO2 AO1 COM3 8 RL7 RL6 RL5 RL4 RL3 RL2 RL1 COM1 BK BL BL 208 240 3 60 0140L06609 A GND VOUT DC OARH SPCRH STPT OFFSET GND TEMP SPCTEMP VOUT DC...

Страница 40: ... 2 COM1 RL1 RL2 COM2 COM3 8 AI3 RL3 RL4 RL5 CC RL6 CFC RL7 RL8 RVC 24VAC GND ECON PLF SMK EMG AO1 AO2 AO3 AO4 DDC BI4 2 2 208 240 3 60 208 240 3 60 SWITCH PRESS OVERCURRENT PROT DEVICE TERMINAL PLUG CONNECTION FIELD GROUND IGNITER JUNCTION INTERNAL TO INTEGRATED CONTROL SCHEMATIC SYMBOL SEE NOTE 5 HGRH EXF ALRM 0140L06610 A OARH CO2 SPC TEMP COM SENSOR OFFSET SPCRH SEE NOTE 4 CS BC1 AGND AO AI ALR...

Страница 41: ...6 RL5 RL4 RL3 RL2 RL1 COM1 BL HGRH EXF ALRM RD YL PU BK T3 T2 T1 L2 L1 BC2 RD BK BL BL OR RD BK BL BL RD BK RD WH PK BK BK L3 T3 T2 T1 L2 L1 BK RD C BK PU RD RD YL BK BK RD SEE NOTE 7 575 C 460 BL 24V RD BL 24V SEE NOTE 8 RD RD TB1 RD BK PU PU PK YL PK BK PK AI1 BK BR GR BL DAT OAT BI8 AI2 AI3 AI4 AI5 AI6 AI7 AI8 GND AGND 24VAC AGND AG C GR RD BK BL BL BL BR WH OR BR WH OR BK RD BK BL BPSW YL PK B...

Страница 42: ... BI BPSW CC CFS CH CHR CHS CM COM COMP DFT ECON EM ES EXF GND HGRH HPS LDS LPS OAT OARH PLF PS RCCF RL RSS RVC SAT DAT SMK EMG SPCTEMP SPCRH T1 T5 TB1 2 TR1 2 XS SD CS CFC TB1 T3 PM DC GROUND FOR ANALOG SENSORS AG ON TB2 4 ANALOG OUTPUTS 8 ANALOG INPUTS ALARM HIGH SPEED CONTACTOR LOW SPEED CONTACTOR 8 BINARY INPUTS BLOWER PROVING SWITCH COMPRESSOR CONTACTOR CLOGGED FILTER SWITCH CRANKCASE HEATER C...

Страница 43: ...ty service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place Check gas piping for leaks Verify gas pressure to the unit is within the range specified on the serial plate Check to ensure that all fans pulleys and wheels are secure Check for proper belt tension and alignment per installatio...

Страница 44: ...Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heating Supply Air Temperature PRESSURES Gas Inlet Pressure Gas Manifold Pressure Suction Circuit 1 Suction Circuit 2 Discharge Circuit 2 Superheat Orifice System Superheat Orifice System Subcooling TXV System S...

Страница 45: ...45 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 46: ...46 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 47: ...47 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 48: ...K Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page ...

Отзывы: