UPFLOW

SPEED 

TAP

ESP

(In H2

O)

SCFM

RPM

BHP

T1

0.1

2124

558

0.06

0.2

1635

566

0.06

0.3

1445

611

0.07

0.4

1270

662

0.08

0.5

1079

715

0.08

0.6

855

765

0.09

0.7
0.8

T2

0.1

3069

727

0.21

0.2

2953

761

0.22

0.3

2843

794

0.23

0.4

2731

829

0.24

0.5

2594

869

0.25

0.6

2453

909

0.26

0.7

2310

947

0.27

0.8

2189

981

0.28

T3

0.1

3069

727

0.21

0.2

2953

761

0.22

0.3

2843

794

0.23

0.4

2731

829

0.24

0.5

2594

869

0.25

0.6

2453

909

0.26

0.7

2310

947

0.27

0.8

2189

981

0.28

T4

0.1

3456

794

0.29

0.2

3343

825

0.30

0.3

3242

856

0.31

0.4

3137

886

0.32

0.5

3024

919

0.33

0.6

2907

953

0.34

0.7

2780

988

0.36

0.8

2659

1023

0.37

T5

0.1

3785

850

0.47

0.2

3688

875

0.48

0.3

3590

904

0.50

0.4

3500

931

0.51

0.5

3407

958

0.53

0.6

3310

987

0.54

0.7

3176

1021

0.56

0.8

3050

1058

0.58

HORIZONTAL

SPEED 

TAP

ESP

(In H2

O)

SCFM

RPM

BHP

T1

0.1

2125

552

0.06

0.2

1583

553

0.06

0.3

1132

591

0.07

0.4

911

653

0.07

0.5
0.6
0.7
0.8

T2

0.1

3125

708

0.20

0.2

3006

746

0.21

0.3

2910

778

0.22

0.4

2805

810

0.23

0.5

2690

844

0.24

0.6

2553

882

0.25

0.7

2414

919

0.26

0.8

2295

953

0.27

T3

0.1

3125

708

0.20

0.2

3006

746

0.21

0.3

2910

778

0.22

0.4

2805

810

0.23

0.5

2690

844

0.24

0.6

2553

882

0.25

0.7

2414

919

0.26

0.8

2295

953

0.27

T4

0.1

3509

776

0.28

0.2

3395

809

0.29

0.3

3300

839

0.30

0.4

3203

869

0.31

0.5

3102

899

0.33

0.6

2990

931

0.34

0.7

2876

963

0.35

0.8

2765

995

0.36

T5

0.1

3869

838

0.46

0.2

3757

867

0.48

0.3

3662

896

0.49

0.4

3559

924

0.51

0.5

3470

951

0.53

0.6

3377

979

0.54

0.7

3282

1007

0.56

0.8

3163

1040

0.57

BLOWER PERFORMANCE TABLES

7.5 Ton LC Indoor Split System

Models: DAX0904

Содержание DAX Series

Страница 1: ...suitable for Upflow and Horizontal Installations only do not use for downflow Installations ATTENTION INSTALLING PERSONNEL Prior to installation thoroughly familiarize yourself with this Installation...

Страница 2: ...and a carbon monoxide producing device is operated therein there must be adequate direct outside ven la on CARBONMONOXIDE POISONING HAZARD Special Warning for Installa on of Furnace or Air Handling Un...

Страница 3: ...ng the table Model Identification section check the equipment model number and voltage to ensure the unit is appropriately sized for the condenser unit s If an incorrect unit is supplied it must not b...

Страница 4: ...g this unit in an area that may become wet elevate the unit with a sturdy non porous material In installations that may lead to physical damage warehouse industrial sites etc it is advised to install...

Страница 5: ...00 23 31 31 30 3000 23 30 30 30 3100 21 29 29 30 3200 21 29 29 DAX0904 Temperature Rise Table F 7 5Ton DAX1204 Temperature Rise Table F KW CFM 208 240 480 15 3800 9 12 12 15 3900 9 12 12 15 4000 9 12...

Страница 6: ...ipment Use the following check list when selecting the appropriate wire size for your unit Wire size must carry the Minimum Circuit Ampacity MCA Refer to the NEC USA or CSA Canada for wire sizing The...

Страница 7: ...o a mating plug in the airhandler The high voltage connections are to be made at the air handler contactor These wires are to be routed through the pipe nipples supplied with the heater kit as shown i...

Страница 8: ...quid lines are to be manifolded when matched with a single condenser heat pump See the following sketches for additional details On a 7 ton DAX unit you can use either one 7 ton condenser or two 4 ton...

Страница 9: ...SPEED COOLING AC HP DEFAULT SPEED FOR ALL Y2 3 HIGH SPEED HEATING DEFAULT SPEED FOR HP OR AC HP WITH ELECTRIC HEAT 4 FAN ONLY 5 HIGH COOL HIGHER SPEED Prior to changing the torque settings refer to ai...

Страница 10: ...51 0 5 3407 958 0 53 0 6 3310 987 0 54 0 7 3176 1021 0 56 0 8 3050 1058 0 58 HORIZONTAL SPEED TAP ESP In H2O SCFM RPM BHP T1 0 1 2125 552 0 06 0 2 1583 553 0 06 0 3 1132 591 0 07 0 4 911 653 0 07 0 5...

Страница 11: ...02 0 89 0 6 4175 1124 0 91 0 7 4099 1148 0 93 0 8 4022 1171 0 95 HORIZONTAL SPEED TAP ESP In H2O SCFM RPM BHP T1 0 1 2576 618 0 16 0 2 2460 661 0 18 0 3 2328 702 0 19 0 4 2173 747 0 20 0 5 2016 789 0...

Страница 12: ...SEQ SEQUENCER RELAY TB TERMINAL BLOCK TR TRANSFORMER 2 S1 S2 R C G W1 W2 Y1 Y2 O TB T1 T2 T3 T4 T5 4 3 2 1 5 PLF BM1 PLF BM2 GR YL PU WH BR GR YL PU WH BR GR YL PU WH BR 4 3 2 1 5 YL BR BR YL 5 3 4 T...

Страница 13: ...NG DIAGRAM SHOWING DAX MODEL SERIES WITH FIELD CONNECTIONS THIS DIAGRAM IS TO BE INCLUDED IN INSTALLATION INSTRUCTIONS A SEPARATE WIRING DIAGRAM IS CONTAINED INSIDE THE CONTROL BOX FOR UNIT FACTORY WI...

Страница 14: ...14 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 15: ...15 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 16: ...022 2023 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikin...

Отзывы: