background image

6

Building Electrical Service Inspection

This unit is designed for 3-phase operation. DO NOT 

OPERATE ON A SINGLE PHASE POWER SUPPLY. SEE 

THE PRECEDING WARNING. Measure the power supply 

to the unit. The supply voltage must be in agreement with 

the unit nameplate power requirements and within the 

range shown below:

Nominal

Minimum 

Supply Voltage

Maximum 

Supply Voltage

208 - 230

197

253

460

414

506

Voltage Balance: The supply voltage shall be unbalance 

(phase to phase) within 2%. To calculate the percentage of 

voltage unbalance use the following formula:

Percentage 

       

Max Voltage Deviation From Average

     

Voltage Unbalance = 100  x  

 Average Voltage 

Example: 

 

 

L1 – L2 = 220 V

   

L2 – L3 = 216 V

 

 

 

L1 – L3 = 213 V

Avg. Voltage: 

      

     = 

(220+216+213) / 3

 

 

               =   

649 / 3

 

 

        

     =    

216

Max. Deviation from Avg. = 220 – 216 = 4

% Voltage Unbalance    =   100 x (4 / 216)

 

 

        

=   400 / 216 

              

        

=   1.8%

Determine Wire Size: The selection of the appropriate 

supply wire size is important to the operation of the 

equipment. When selecting the wire size the following are 

important elements of the decision:

• 

  The wire size is adequately sized to carry the 

Minimum Circuit Ampacity (MCA). Refer to the NEC 

(USA) or CSA (Canada) for wire sizing. The unit MCA 

for the airhandler and the optional electric heat kit 

can be found on the equipment S&R plate and the 

following table.

AIRHANDLER

VOLTAGE

HEAT KIT

MCA

DAX0904 and 

DAX1204

208 - 230

None

15.5 / 15.5

AHKD15-3A

56.3 / 62.4

AHKD20-3A

69.4 / 77.4

AHKD30-3A

95.4 / 108

460

None

5.2

AHKD15-4A

28.3

AHKD20-4A

35.8

AHKD30-4A

50.9

Wire Sizing

Wire size is important to the operation of your equipment.  

Use the following check list when selecting the appropriate 

wire size for your unit.

•  

Wire size must carry the Minimum Circuit 

Ampacity (MCA).

• 

  Refer to the NEC (USA) or CSA (Canada) for wire 

sizing. The unit MCA for the air handler and the 

optional electric heat kit can be found on the unit 

Series and Rating Plate.

•  

Wire size allows for no more than a 2% voltage 

drop from the building breaker/fuse panel to the 

unit.

Refer to the latest edition of the National Electric 

Code or in Canada the Canadian Electric Code when 

determining the correct wire size. The following table 

shows the current carrying capabilities for copper 

conductors rated at 75

°

C with a 2% voltage drop.  

Use 

this table

 determine the voltage drop per foot of 

various conductors.

MAXIMUM ALLOWABLE LENGTH IN FEET TO LIMIT 

VOLTAGE DROP TO 2%

Wire Size

(AWG)

10

15

20

25

30

35

40

45

14

77

51

38

NR NR NR NR NR

12

122 81

61

49

NR NR NR NR

10

193 129 97

77

64

55

NR NR

8

307 205 154 123 103 88

77

68

6

489 326 244 195 163 140 122 109

Minimum Circuit Ampacity (MCA)

 

Maximum Overcurrent Protection (MOP)

Every installation must include an NEC (USA) or CEC 

(Canada) approved overcurrent protection device. Also, 

check with local or state codes for any special regional 

requirements.

Protection can be in the form of fusing or HACR style 

circuit breakers. The Series and Rating Plate can be used 

as a guide for selecting the MAXIMUM overcurrent device 

or reference the following table.

NOTE: Fuses or circuit breakers are to be sized 

larger than the equipment MCA but not to exceed 

the MOP.

AIRHANDLER

VOLTAGE

HEAT KIT

MOP

DAX0904 and 

DAX1204

208 - 230

None

20 / 20

AHKD15-3A

60 / 70

AHKD20-3A

70 / 80

AHKD30-3A

100 / 110

460

None

15

AHKD15-4A

30

AHKD20-4A

40

AHKD30-4A

60

Содержание DAX Series

Страница 1: ...suitable for Upflow and Horizontal Installations only do not use for downflow Installations ATTENTION INSTALLING PERSONNEL Prior to installation thoroughly familiarize yourself with this Installation...

Страница 2: ...and a carbon monoxide producing device is operated therein there must be adequate direct outside ven la on CARBONMONOXIDE POISONING HAZARD Special Warning for Installa on of Furnace or Air Handling Un...

Страница 3: ...ng the table Model Identification section check the equipment model number and voltage to ensure the unit is appropriately sized for the condenser unit s If an incorrect unit is supplied it must not b...

Страница 4: ...g this unit in an area that may become wet elevate the unit with a sturdy non porous material In installations that may lead to physical damage warehouse industrial sites etc it is advised to install...

Страница 5: ...00 23 31 31 30 3000 23 30 30 30 3100 21 29 29 30 3200 21 29 29 DAX0904 Temperature Rise Table F 7 5Ton DAX1204 Temperature Rise Table F KW CFM 208 240 480 15 3800 9 12 12 15 3900 9 12 12 15 4000 9 12...

Страница 6: ...ipment Use the following check list when selecting the appropriate wire size for your unit Wire size must carry the Minimum Circuit Ampacity MCA Refer to the NEC USA or CSA Canada for wire sizing The...

Страница 7: ...o a mating plug in the airhandler The high voltage connections are to be made at the air handler contactor These wires are to be routed through the pipe nipples supplied with the heater kit as shown i...

Страница 8: ...quid lines are to be manifolded when matched with a single condenser heat pump See the following sketches for additional details On a 7 ton DAX unit you can use either one 7 ton condenser or two 4 ton...

Страница 9: ...SPEED COOLING AC HP DEFAULT SPEED FOR ALL Y2 3 HIGH SPEED HEATING DEFAULT SPEED FOR HP OR AC HP WITH ELECTRIC HEAT 4 FAN ONLY 5 HIGH COOL HIGHER SPEED Prior to changing the torque settings refer to ai...

Страница 10: ...51 0 5 3407 958 0 53 0 6 3310 987 0 54 0 7 3176 1021 0 56 0 8 3050 1058 0 58 HORIZONTAL SPEED TAP ESP In H2O SCFM RPM BHP T1 0 1 2125 552 0 06 0 2 1583 553 0 06 0 3 1132 591 0 07 0 4 911 653 0 07 0 5...

Страница 11: ...02 0 89 0 6 4175 1124 0 91 0 7 4099 1148 0 93 0 8 4022 1171 0 95 HORIZONTAL SPEED TAP ESP In H2O SCFM RPM BHP T1 0 1 2576 618 0 16 0 2 2460 661 0 18 0 3 2328 702 0 19 0 4 2173 747 0 20 0 5 2016 789 0...

Страница 12: ...SEQ SEQUENCER RELAY TB TERMINAL BLOCK TR TRANSFORMER 2 S1 S2 R C G W1 W2 Y1 Y2 O TB T1 T2 T3 T4 T5 4 3 2 1 5 PLF BM1 PLF BM2 GR YL PU WH BR GR YL PU WH BR GR YL PU WH BR 4 3 2 1 5 YL BR BR YL 5 3 4 T...

Страница 13: ...NG DIAGRAM SHOWING DAX MODEL SERIES WITH FIELD CONNECTIONS THIS DIAGRAM IS TO BE INCLUDED IN INSTALLATION INSTRUCTIONS A SEPARATE WIRING DIAGRAM IS CONTAINED INSIDE THE CONTROL BOX FOR UNIT FACTORY WI...

Страница 14: ...14 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 15: ...15 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 16: ...022 2023 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikin...

Отзывы: