D2CND0 D2CND0 D2TND0
D2TND0 D2TND024A4AA
Wall-mounted condensing boiler
ESIE17-09 / 2017.11
Servicing manual
32
7.10.3.1 Service Parameters (P)
P06:
Maximum central heating capacity can be restricted by
this parameter. For each model, max. CH capacity in percent
-
age is different as below;
P07:
Minimum capacity of the pump during central heating
operation.
P08:
Maximum capacity of the pump during central heating
operation.
P09:
Capacity of the pump during central heating operation
burner off, pump post run or frost protection functions.
7 Operation
7.10.3 Installer Settings Menu
Only qualified persons are allowed to enter the Installer Set
-
tings menu.
b
a
Reaching user setting parameters
a) Turn right dial to se
-
lect index number.
Push when the pa
-
rameter that you want to
change appears on the
screen.
b) Change parameter value
with right dial. After changing
parameter value;
Push to apply change.
Push to cancel change.
SERVICE SETTINGS
Para-
meter
No
Description
Unit
Factory
setting
Range
P00 Reduced or switch off
mode selection
none
0
0 - 1
P01 Building estimation
none
0
0 - 1
P02 Outdoor sensor corre
-
ction
ºC
0
-4 - 4
P
03
Boiler frost protection
temperature
ºC
8
0 - 15
P04 System frost protection
temp.
ºC
4
-9 - 10
P
05
Anti-cycling time
none
2
0 - 10
P06 Maximum CH capacity
%
100
min. cap.
- 100
P07 Minimum CH pump
capacity
%
50
10 - 100
P08 Maximum CH pump
capacity
%
100
P07 -
100
P
09
Standby CH pump
capacity
%
50
16 - 100
P10 DHW solar function
delay time
s
5
0 - 255
P11 DHW solar function
activation
none
0
0 - 1
P12 Solar hysteresis on
ºC
-3
-10 - 10
P13 DHW excess cylinder
temperature
ºC
15
-30 - 30
P14 DHW pump capacity
%
100
20 - 100
P15 Max. CH flow temp.
setpoint
ºC
80
30 - 80
P16 Varican module status
none
0
0 - 1
P17
Delta-T flow and return
pump
ºC
20
5 - 30
P18 CH hysteresis tempe
-
rature
ºC
7
0 - 20
P19 Min. CH flow temp.
setpoint
ºC
30
10 - 30
P00:
In case Opentherm thermostat is switched off (no heat
demand), boiler is either switched off (=0) or operates in redu
-
ction mode (=1)
P01:
Weather compensation building condition parameter. It
is used in flow setpoint calculation when outdoor sensor is
active.
Adjust it to ‘0’ if building has many windows to the south.
Adjust it to ‘1’ if building has few windows to the south.
P02:
Correction for outdoor sensor reading.
P03:
Boiler frost protection burner activation temperature.
If flow temperature drops below this par5 K value,
pump operates. If flow temperature still drops and goes below
this parameter value, the burner operates to heat up the water
temperature in the central Heating installation up to 20°C.
P04:
System frost protection activation temperature (in case
outdoor sensor is connected). This protection is only available
if an outdoor sensor is connected to the boiler. If the outdoor
temperature falls below this parameter value, boiler pump will
switch on.
P05:
This parameter adjusts the time, which is named as anti
cycling time, between 2 successive burner operation in central
heating mode. Anti cycling time is dependant to this parameter
value and CH set value adjusted by the customer. See the
following table;
Values which below the P05 values in terms of minute
Model
Maximum CH capacity
D2CND024
91
D2TND024
100
D2TND018
75
D2TND012
52
CH Set Value /
POS Value
0 1
2
3
4
5
6
7
8
9
10
<= 20
0
2
5
5
5
5
5
5
5
5
5
25
0
2
4,7 4,7 4,7 4,7 4,7 4,7 4,7 4,7 4,7
30
0
2
4,4 4,4 4,4 4,4 4,4 4,4 4,4 4,4 4,4
35
0
2
4,1 4,1 4,1 4,1 4,1 4,1 4,1 4,1 4,1
40
0
2
3,9 3,9 3,9 3,9 3,9 3,9 3,9 3,9 3,9
45
0
2
3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6
50
0
2
3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3
55
0
2
3,1 3,1 3,1 3,1 3,1 3,1 3,1 3,1 3,1
60
0
2
2,8 2,8 2,8 2,8 2,8 2,8 2,8 2,8 2,8
65
0
2
2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5
70
0
2
2,2 2,2 2,2 2,2 2,2 2,2 2,2 2,2 2,2
>= 75
0
2
2
2
2
2
2
2
2
2
2
7.10.3.2 Detailed Explanations of Service Parameters