background image

D2CND0 D2CND0 D2TND0 

D2TND0 D2TND024A4AA 

Wall-mounted condensing boiler

ESIE17-09 / 2017.11

Servicing manual

27

7.2 

Operating The Appliance 

Switching ON

Connect the appliance to the main power supply.

Press the “Mode” button for 5 seconds to switch ON the appli

-

ance. After that, you can select an operation mode by press

-

ing the Mode button shortly.

Use  of  the  appliance  is  explained  in  following  parts  of  this 

manual.

7.2.1 

Low Water Temperature Function

Low water temperature function is a safety function that takes 

place at first central heating operation after each power supply 

interruption and at first central heating operation after each 90 

days. When this function is active, boiler operates according 

to a defined set value for around 15 minutes and the     icon 

blinks.     After this function is ended, normal operation goes 

on (for details of the function refer to page 36).

7.2.2 

Electronic Gas Adaptive System Calibration 

Electronic gas adaptive system calibrates itself in pre-deter

-

mined time intervals. First calibration takes place just after first 

burner  activation  after  each  power  ON.  Calibration  process 

duration is around 60 seconds. After calibration is ended, boil

-

er modulates to required capacity. Calibration process has no 

any effect to boiler operation.

7.3 

Basic use

7.3.1 

Home Screen

It is the screen that is displayed after activating the LCD sc

-

reen with one of the dials or buttons. You can use the home 

screen to read out settings that are meant for daily use. What 

you  can  see  on  the  home  screen  depends  on  your  system 

configuration.

The following home screens may be possible;

• 

Room temperature (Daikin room thermostat connected)

• 

Central Heating set temperature

• 

Virtual room temperature (with Outdoor Sensor)

• 

Domestic hot water set temperature

• 

System Pressure (at stand-by mode)

7.3.2 

Selecting Operation Mode

The operation mode can be changed by pushing the “Mode” 

button. 

7.4 

Description of the Operation Modes

7.4.1 

Stand-by Mode

In stand-by mode both central heating and domestic hot water 

operation modes are disabled. The protection functions such 

as frost protection are still active at standby mode. The home

-

screen shows the system pressure, as well as the       icon.

7.4.2 

Summer Mode

In Summer mode, only domestic hot water operation mode 

is enabled. Central heating operation mode is disabled. The 

boiler will only produce heat for domestic hot water.

The domestic hot water setpoint, and the      icon is shown 

on the home screen.

The      icon blinks if domestic hot water operation is active.

7.4.3 

Winter Mode

In Winter mode, domestic hot water operation mode and cen

-

tral heating operation mode are both enabled. The boiler can 

produce domestic hot water, as well as produce heat for cen

-

tral heating.

The central heating temperature setpoint,  and the     icon, 

as well as the     icon are shown on the home screen. When 

domestic  hot  water  operation  is  active,  Domestic  hot  water 

setpoint is shown on the homescreen.

The      icon blinks if domestic hot water operation is active.

The      icon blinks if central heating operation is active.

7.4.4 

Central Heating Only Mode

In this mode, only central heating operation mode is enabled. 

The central heating temperature setpoint  and the     icon is 

shown on the home screen.

The      icon blinks if central heating operation is active.

7.4.5 

Full Off Mode

In this mode both central heating and domestic hot water op

-

eration modes are disabled. In addition, LCD display will be 

darkened and will not be activated with any user interaction. 

The protection functions such as frost protection are still ac

-

tive at Full off mode. Full off mode is activated and deactivated 

if mode button is pressed for 5 seconds while boiler is in any 

mode.

7 Operation

(5 s)

(5 s)

a

c

b

d

e

a Central heating only mode

b Standby mode

c Summer mode

d Winter mode

e Full-off mode

Содержание D2CND024A1AA

Страница 1: ...Servicing manual Wall mounted condensing boiler D2CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA English Servicing manual Wall mounted condensing boiler...

Страница 2: ...CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA Wall mounted condensing boiler ESIE17 09 2017 11 Servicing manual 2 LOG Version Code Description Date ESIE17 09 Document release 1 11 201...

Страница 3: ...s 26 7 1 2 LCD screen 26 7 1 3 Status icons 26 7 1 4 Daikin Eye 26 7 1 5 Stand by 26 7 1 6 Flame 26 7 1 7 Error 26 7 2 Operating The Appliance 27 7 2 1 Low Water Temperature Function 27 7 2 2 Electron...

Страница 4: ...s composed of an LCD screen push buttons and two dials and which is located on the front cover of the appliance The appliance is equipped with several safety systems to pro tect it against dangerous c...

Страница 5: ...w temperature sensor which is located at the outlet of the main heat exchanger This protection ac tivates the boiler pump when the water temperature drops below depends on P03 parameter value and it a...

Страница 6: ...ostat 17 Fan 18 Return temperature sensor 19 Silencer 20 Automatic air vent pump 21 Water pressure sensor 22 By pass 23 Boiler pump 24 Domestic hot water flow sensor 25 Domestic hot water flow limiter...

Страница 7: ...56 68 56 77 Combustion products temperature min max G31 C 56 60 56 68 55 76 Maximum combustion products temp at nominal heat input C 80 82 90 CO2 Emission at nominal and minimum heat input G20 9 0 0...

Страница 8: ...14_FLOW X4 15_OWC X4 16_OWC X3 1_PwmWh X3 2_PwmB1 X3 3_ReWhSw X3 4_Gnd X3 5_5v X2 8_LP1 X2 1_SOLs X2 2_SOL X2 3_RTs X2 4_RT X2 5_NPSRT X2 6_LPSRT X2 7_NP1 X5 X4 X3 X2 X1 X1 1_NP X1 2_LP X1 3_NI X1 4_...

Страница 9: ...stable spanner Number 30 32 24 26 14 18 3 3 Spare parts To ensure long lasting operation of the appliance always use original spare parts Spare parts must be ordered from spare parts catalog by specif...

Страница 10: ...Domestic Hot Water Circuit Isolate the appliance from power supply and closedown the gas valve Close all the isolating valves on the central heating circuit Open the drain valve 1 and drain the centr...

Страница 11: ...from power supply and closedown the gas valve Undo M5 screw at the figure 1 Remove the assembly clips of front cover 2 Remove the front cover by pulling up 3 Undo 2 sheet screw holding control panel 4...

Страница 12: ...connector of flow sensor 2 and pressure sensor 3 Disconnect the wire connector of 3 way valve refer to 4 6 1 Dismantle the ignition electrode and earth cable from the power supply 4 Firstly loosen th...

Страница 13: ...socket s housing and disconnect the sensor 13 Take out cable connections of fan manually 14 Re assemble in reverse order Be careful all electrical cables during the removal of cable group wire harnes...

Страница 14: ...e gas supply pipe from the gas valve and brass nipple by using wrench 1 Unscrew the 2xM5 screws that connect gas manifold and burner hood 2 Seperate the gas manifold from the burner hood clip and take...

Страница 15: ...low return and flue NTC sensors and high limit thermostat refer to Section 4 3 Take out the syphon parts refer to Section 4 8 Unscrew the screws that connect hermetic cabinet and right cover 1 Remove...

Страница 16: ...nted condensing boiler ESIE17 09 2017 11 Servicing manual 16 4 Part replacement Remove the screw holding the hermetic cabinet with main heat exchanger M5 allen 9 Detach the main heat exchanger by push...

Страница 17: ...nti nel s products which are appropriate for cleaning of heat exchanger inside Inspect the heat exchanger from the top and bottom Take any foreign object Use the cleaning tool into the heat exchanger...

Страница 18: ...2 Undo the screws that connect to hermetic cabinet to the pump 3 Undo the 2 screws that connect to hermetic cabinet to the pump 4 for T models Loosen the union joint that provides the return pipe pump...

Страница 19: ...the DHW flow CH flow installation pipes from the boiler by using wrench refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the expansion vessel refer to Section 4 10 Remove the fast...

Страница 20: ...osedown the gas valve Drain the water from the boiler refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the silencer refer to Section 4 4 Remove the syphon part from condensate sum...

Страница 21: ...efer to Section 4 2 Remove the left cover of the boiler unscrew the screws that connects hermetic cabin and left cover 1 Undo the screws which connect expansion vessel and flow hydroblock 2 Disconnect...

Страница 22: ...support s 3 screws holding the main pcb and remove the cable support 4 Unscrew the 3 screws that connect PCB and control panel 5 Isolate the appliance from power supply and closedown the gas valve Ope...

Страница 23: ...pump and heat exchanger are opened Vent the air from the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting If after the purge the pressure dec...

Страница 24: ...w you can see the Cable glands placement Holes on the bottom sheet that are reserved for cable glands are covered with insulation material The insulation material must be bored if glands are to be use...

Страница 25: ...fter first power ON the boiler does not increase its capacity above a preset value for about 12 minutes even if there is demand First 0 2 minutes The electronic gas adapti ve system calibrates itself...

Страница 26: ...ashes to its maximum then constantly keeps glowing during burner operation with blue LED 7 1 7 Error The Daikin eye will go into error mode when a warning lockout or blocking error occurs During the e...

Страница 27: ...re at stand by mode 7 3 2 Selecting Operation Mode The operation mode can be changed by pushing the Mode button 7 4 Description of the Operation Modes 7 4 1 Stand by Mode In stand by mode both central...

Страница 28: ...o room ther mostat or outdoor sensor are connected The central heating water temperature setpoint is displayed The setpoint can be adjusted with the left dial The icon is shown on the screen when cent...

Страница 29: ...Note Independent of personal use pattern Comfort mode preheating function could be adjusted to operate continuously from the user settings For example When the domestic hot water DHW mode is activate...

Страница 30: ...ximum value during domestic hot water operation 100 c A10 0 Standby mode burner is not active A10 1 Start up preparation to ignition A10 2 Ignition and flame stabilisition phase A10 3 Release control...

Страница 31: ...onnected this parameter value is the central heating water tempearture setpoint when there is no a heat demand Note For this parameter value to be active Reducing mode have to be enabled by your servi...

Страница 32: ...0 20 P19 Min CH flow temp setpoint C 30 10 30 P00 In case Opentherm thermostat is switched off no heat demand boiler is either switched off 0 or operates in redu ction mode 1 P01 Weather compensation...

Страница 33: ...ble only for storage tank type models P15 Max temperature that can be adjusted by left dial when setting central heating flow temperature P16 This parameter is a read only parameter which shows the co...

Страница 34: ...0 C 10 circuits and lenght of the each circuit is 80 metres without an additional pump When the boiler is connected to an UFH system the following parameter changes must certainly be done Parameter Ma...

Страница 35: ...ir ratio will be far from average value which may also result in ignition problems delayed or loud ignition If such problems are present C02 parameter must be optimized first If C02 parameter change i...

Страница 36: ...may cause loud ignition C03 This parameter is used to increase maximum allowable flue duct length by increasing fan speed Adjust this parameter to 3 to use longer flue ducts for C13x and C33x types of...

Страница 37: ...e pass word as 043 c For 100 calibration and C12 C13 adjustment set the password as 046 Press Enter button The boiler will start calibration ac cording to above mentioned input values LED s on the scr...

Страница 38: ...set to 45 C 2 Pump runs at 100 capacity Function is active for 10 minutes of burner operation After function is ended boiler operates according to central heating setpoint adjusted by the customer an...

Страница 39: ...mall plug which contains a programmed memory With BCC set of parameters inside the PCB can be changed at field without need to change the PCB itself The BCC con tains all control parameters and safety...

Страница 40: ...or code will still be shown on display Resetting the boiler will remove the error 9 1 4 Error during Parameter transfer If an error occurs during the Parameter transfer or if parameter update is not i...

Страница 41: ...12 66 Ion base val ue exceeds lower factory limit Reset the boiler Make a manuel calibration Check the ionization elecktrode it s cable connection and it s earth cable Replace if defective ER ROR CODE...

Страница 42: ...leshooting ERROR CODE REASON ELIMINATION 81 01 Flow tem perature sensor fault Check continuity between the sen sor and PCB replace wire harness if necessary Check flue tempera ture sensor resistance u...

Страница 43: ...the building should be checked and voltage stabiliser should be used for smooth operation U4 65 Opentherm RT connection is defective Boiler operates as if Opentherm room thermostat not connected Check...

Страница 44: ...TMA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr ESIE17 09 2017 11 C...

Отзывы: