background image

D2CND0 D2CND0 D2TND0 

D2TND0 D2TND024A4AA 

Wall-mounted condensing boiler

ESIE17-09 / 2017.11

Servicing manual

35

Explanations  of  parameters  related  with  weather  compen

-

sation are given in “Service parameters” and “User settings 

menu” sections.

7.10.6.2  Effect of Heating Slope to CH Temperature

The effect of heating slope is illustrated on the graph below; 

7.10.7  Scot Parameters (C) Safety combustion techno

-

logy system

The PCB of the appliance provides continuous control of com

-

bustion efficiency and combustion performance by means of 

SCOT system. Due to SCOT system, gas valve operation is 

independent of fan, so there is no need to gas valve adjust

-

ment for gas/air ratio optimization.

Ionization electrode senses a current from the flame which is 

on the surface of the burner, and transmits the current to the 

PCB at the  level of µA.

PCB evaluates the transmitted current as a “point” value. This 

value is defined as the “ion” in SCOT software.

By controlling ionization continuously, SCOT system ensures 

the fuel / air mixture homogenously for each gas type.

Frequently occuring combustion and ignition 

related errors can be resolved by optimizing the 

parameters. C parameters are explained in detail 

at following section.

INFORMATION

When the flue duct is not installed properly, SCOT 

system breakdown errors occur often. Make sure 

that flue duct is mounted properly on the boiler for 

smooth operation.

WARNING

7.10.7.1  Detailed Explanations of C Parameters
C00:

 This parameter is used to switch between fuel types. If 

natural gas is to be used as supply gas, parameter must be 

adjusted to “0” (zero). If LPG is to be used as supply gas, pa

-

rameter must be adjusted to “1” (one).

C01:

 If a gas valve is at the limits of production tolerances, 

starting gas/air ratio will be far from average value which may 

also  result  in  ignition  problems  (delayed  or  loud  ignition).  If 

such problems are present, C02 parameter must be optimized 

first. If C02 parameter change is not helping the ignition prob

-

lem, offset parameter can be the real reason. Increasing the 

offset value will enrich the starting gas mixture which will help 

delayed ignition problems.

7 Operation

a

b

c

d

f

g

e

+

+

+

=

a Outdoor Temperature

b ODS correction P02

c Building estimation P01

d CH water temp. calculation

e Target CH water temperature

f Heating slope U01

g Virtual room temp. setpoint

(5)

(6)

(8)

(10)

(12)

(16)

(20)

(24)

(30)

10

20

0

-10

-20

-3030

40

50

60

70

80

Resultant boiler set point (ºC)

Room set point 22 (ºC)

Outside temperature (ºC)

min. (ºC)

Array of heating slopes max.  (ºC)

Following parameters have impact to weather compensation 

calculation: 

• 

• 

Outdoor sensor correction (Parameter P02 )

• 

Building estimation (Parameter P01) 

• 

Heating slope (Parameter U01)

• 

Virtual room temperature set point 

Calculation of CH temperature set point in principal is shown 

below;

7.10.6.1  Weather compensation calculation

The  required  central  heating  temperature  is  calculated  ac

-

cording to the outside temperature and the virtual room tem

-

perature set point, which is adjusted by left dial.

Note: 

If the outside temperature falls, the central heating tem

-

perature will be increased.

SCOT PARAMETER SETTINGS

Parame-

ter No

Description 

Unit

Fac-

tory 

setting

Range

C00

Gas type

none 0

0 - 1

C01

Adjustment of gas 

start offset

%

0

-9 - 20

C02

Adjustment of startup 

capacity

%

0

-8 - 7

C03

Flue duct adjustment %

0

-5 - 10

C04

Adjustment minimum 

capacity

%

0

0 - dyn. 

max.

C05

Gas control offset

%

29.3

17 - 44

C06

Flame ionization 

signal

pts

-

0 - 100

C07

Gas valve control 

PWM

%

-

0 - 100

C08

Actual capacity value

%

-

0 - 100

C09

Ionization base value pts

-

0 - 255

C10

Minimum start ioniza

-

tion value

pts

-

0 - 255

C11

Ignition time

s

-

0 - 4.5

C12

Reducing ion base 

value

pts

-

-5 - 10

C13

Reducing ion at mini

-

mum capacity

pts

-

-5 - 10

CE

Password entry

none -

0 - 999

Содержание D2CND024A1AA

Страница 1: ...Servicing manual Wall mounted condensing boiler D2CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA English Servicing manual Wall mounted condensing boiler...

Страница 2: ...CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA Wall mounted condensing boiler ESIE17 09 2017 11 Servicing manual 2 LOG Version Code Description Date ESIE17 09 Document release 1 11 201...

Страница 3: ...s 26 7 1 2 LCD screen 26 7 1 3 Status icons 26 7 1 4 Daikin Eye 26 7 1 5 Stand by 26 7 1 6 Flame 26 7 1 7 Error 26 7 2 Operating The Appliance 27 7 2 1 Low Water Temperature Function 27 7 2 2 Electron...

Страница 4: ...s composed of an LCD screen push buttons and two dials and which is located on the front cover of the appliance The appliance is equipped with several safety systems to pro tect it against dangerous c...

Страница 5: ...w temperature sensor which is located at the outlet of the main heat exchanger This protection ac tivates the boiler pump when the water temperature drops below depends on P03 parameter value and it a...

Страница 6: ...ostat 17 Fan 18 Return temperature sensor 19 Silencer 20 Automatic air vent pump 21 Water pressure sensor 22 By pass 23 Boiler pump 24 Domestic hot water flow sensor 25 Domestic hot water flow limiter...

Страница 7: ...56 68 56 77 Combustion products temperature min max G31 C 56 60 56 68 55 76 Maximum combustion products temp at nominal heat input C 80 82 90 CO2 Emission at nominal and minimum heat input G20 9 0 0...

Страница 8: ...14_FLOW X4 15_OWC X4 16_OWC X3 1_PwmWh X3 2_PwmB1 X3 3_ReWhSw X3 4_Gnd X3 5_5v X2 8_LP1 X2 1_SOLs X2 2_SOL X2 3_RTs X2 4_RT X2 5_NPSRT X2 6_LPSRT X2 7_NP1 X5 X4 X3 X2 X1 X1 1_NP X1 2_LP X1 3_NI X1 4_...

Страница 9: ...stable spanner Number 30 32 24 26 14 18 3 3 Spare parts To ensure long lasting operation of the appliance always use original spare parts Spare parts must be ordered from spare parts catalog by specif...

Страница 10: ...Domestic Hot Water Circuit Isolate the appliance from power supply and closedown the gas valve Close all the isolating valves on the central heating circuit Open the drain valve 1 and drain the centr...

Страница 11: ...from power supply and closedown the gas valve Undo M5 screw at the figure 1 Remove the assembly clips of front cover 2 Remove the front cover by pulling up 3 Undo 2 sheet screw holding control panel 4...

Страница 12: ...connector of flow sensor 2 and pressure sensor 3 Disconnect the wire connector of 3 way valve refer to 4 6 1 Dismantle the ignition electrode and earth cable from the power supply 4 Firstly loosen th...

Страница 13: ...socket s housing and disconnect the sensor 13 Take out cable connections of fan manually 14 Re assemble in reverse order Be careful all electrical cables during the removal of cable group wire harnes...

Страница 14: ...e gas supply pipe from the gas valve and brass nipple by using wrench 1 Unscrew the 2xM5 screws that connect gas manifold and burner hood 2 Seperate the gas manifold from the burner hood clip and take...

Страница 15: ...low return and flue NTC sensors and high limit thermostat refer to Section 4 3 Take out the syphon parts refer to Section 4 8 Unscrew the screws that connect hermetic cabinet and right cover 1 Remove...

Страница 16: ...nted condensing boiler ESIE17 09 2017 11 Servicing manual 16 4 Part replacement Remove the screw holding the hermetic cabinet with main heat exchanger M5 allen 9 Detach the main heat exchanger by push...

Страница 17: ...nti nel s products which are appropriate for cleaning of heat exchanger inside Inspect the heat exchanger from the top and bottom Take any foreign object Use the cleaning tool into the heat exchanger...

Страница 18: ...2 Undo the screws that connect to hermetic cabinet to the pump 3 Undo the 2 screws that connect to hermetic cabinet to the pump 4 for T models Loosen the union joint that provides the return pipe pump...

Страница 19: ...the DHW flow CH flow installation pipes from the boiler by using wrench refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the expansion vessel refer to Section 4 10 Remove the fast...

Страница 20: ...osedown the gas valve Drain the water from the boiler refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the silencer refer to Section 4 4 Remove the syphon part from condensate sum...

Страница 21: ...efer to Section 4 2 Remove the left cover of the boiler unscrew the screws that connects hermetic cabin and left cover 1 Undo the screws which connect expansion vessel and flow hydroblock 2 Disconnect...

Страница 22: ...support s 3 screws holding the main pcb and remove the cable support 4 Unscrew the 3 screws that connect PCB and control panel 5 Isolate the appliance from power supply and closedown the gas valve Ope...

Страница 23: ...pump and heat exchanger are opened Vent the air from the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting If after the purge the pressure dec...

Страница 24: ...w you can see the Cable glands placement Holes on the bottom sheet that are reserved for cable glands are covered with insulation material The insulation material must be bored if glands are to be use...

Страница 25: ...fter first power ON the boiler does not increase its capacity above a preset value for about 12 minutes even if there is demand First 0 2 minutes The electronic gas adapti ve system calibrates itself...

Страница 26: ...ashes to its maximum then constantly keeps glowing during burner operation with blue LED 7 1 7 Error The Daikin eye will go into error mode when a warning lockout or blocking error occurs During the e...

Страница 27: ...re at stand by mode 7 3 2 Selecting Operation Mode The operation mode can be changed by pushing the Mode button 7 4 Description of the Operation Modes 7 4 1 Stand by Mode In stand by mode both central...

Страница 28: ...o room ther mostat or outdoor sensor are connected The central heating water temperature setpoint is displayed The setpoint can be adjusted with the left dial The icon is shown on the screen when cent...

Страница 29: ...Note Independent of personal use pattern Comfort mode preheating function could be adjusted to operate continuously from the user settings For example When the domestic hot water DHW mode is activate...

Страница 30: ...ximum value during domestic hot water operation 100 c A10 0 Standby mode burner is not active A10 1 Start up preparation to ignition A10 2 Ignition and flame stabilisition phase A10 3 Release control...

Страница 31: ...onnected this parameter value is the central heating water tempearture setpoint when there is no a heat demand Note For this parameter value to be active Reducing mode have to be enabled by your servi...

Страница 32: ...0 20 P19 Min CH flow temp setpoint C 30 10 30 P00 In case Opentherm thermostat is switched off no heat demand boiler is either switched off 0 or operates in redu ction mode 1 P01 Weather compensation...

Страница 33: ...ble only for storage tank type models P15 Max temperature that can be adjusted by left dial when setting central heating flow temperature P16 This parameter is a read only parameter which shows the co...

Страница 34: ...0 C 10 circuits and lenght of the each circuit is 80 metres without an additional pump When the boiler is connected to an UFH system the following parameter changes must certainly be done Parameter Ma...

Страница 35: ...ir ratio will be far from average value which may also result in ignition problems delayed or loud ignition If such problems are present C02 parameter must be optimized first If C02 parameter change i...

Страница 36: ...may cause loud ignition C03 This parameter is used to increase maximum allowable flue duct length by increasing fan speed Adjust this parameter to 3 to use longer flue ducts for C13x and C33x types of...

Страница 37: ...e pass word as 043 c For 100 calibration and C12 C13 adjustment set the password as 046 Press Enter button The boiler will start calibration ac cording to above mentioned input values LED s on the scr...

Страница 38: ...set to 45 C 2 Pump runs at 100 capacity Function is active for 10 minutes of burner operation After function is ended boiler operates according to central heating setpoint adjusted by the customer an...

Страница 39: ...mall plug which contains a programmed memory With BCC set of parameters inside the PCB can be changed at field without need to change the PCB itself The BCC con tains all control parameters and safety...

Страница 40: ...or code will still be shown on display Resetting the boiler will remove the error 9 1 4 Error during Parameter transfer If an error occurs during the Parameter transfer or if parameter update is not i...

Страница 41: ...12 66 Ion base val ue exceeds lower factory limit Reset the boiler Make a manuel calibration Check the ionization elecktrode it s cable connection and it s earth cable Replace if defective ER ROR CODE...

Страница 42: ...leshooting ERROR CODE REASON ELIMINATION 81 01 Flow tem perature sensor fault Check continuity between the sen sor and PCB replace wire harness if necessary Check flue tempera ture sensor resistance u...

Страница 43: ...the building should be checked and voltage stabiliser should be used for smooth operation U4 65 Opentherm RT connection is defective Boiler operates as if Opentherm room thermostat not connected Check...

Страница 44: ...TMA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr ESIE17 09 2017 11 C...

Отзывы: