SiBE12-908
Troubleshooting
Service Diagnosis
139
2.27
Thermistor or Related Abnormality (Outdoor Unit)
Remote
Controller Display
P4
,
J3
,
J6
,
J8
,
J9
,
H9
Outdoor Unit LED
Display
A
5
5
-
Method of
Malfunction
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature detected by each thermistor.
Malfunction
Decision
Conditions
When power is supplied and the thermistor input is 4.98 V or more
or when the thermistor input is 0.02 V or less for 5 sec. continuously
For
J3
,
“Discharge pipe thermistor < heat exchanger thermistor” is taken into consideration to identify
the fault.
For
J8
or
J9
, although the system of the corresponding room will be shut down, the outdoor unit
can operate.
Supposed
Causes
Improper connection of connector
Defective thermistor
Defective indoor unit PCB
For
J3
, defective heat exchanger thermistor
(Cooling: outdoor heat exchanger thermistor, heating: indoor heat exchanger thermistor)