START UP
!
WARNING
!
The installer is responsible for ensuring that all procedures are carefully followed; it is imperative that the personnel conducting the
installation are both qualified and certified.
This adherence to qualifications and certifications is crucial for compliance with all specifications and best practices, guaranteeing
the unit’s proper operation
!
WARNING
!
This appliance is designed for use only by individuals who do not have reduced physical, sensory, or mental capabilities and possess
the necessary experience and knowledge (including children). If this is not the case, the appliance should be operated under the
supervision or guidance of someone responsible for ensuring the user’s safety.
!
WARNING
!
Children should be supervised to ensure that they do not play with the appliance.
!
WARNING
!
For appliances intended for use at altitudes exceeding 2 000 m, the maximum altitude of use shall be stated by AHRI 390.
25
25
10
10
-
-
BV
BVT
T
0,5
0 15%
0 20s
20s
%Vn
%Vn
t.
t.
retardo
retardo
t. inibição
t. inibição
assimetria
assimetria
Geral
Geral
Relé
Relé
Falha
Falha
12
12
11
10
)
6
( )
6
(
)
4
( )
4
(
)
2
( )
2
(
SS
RR
T T
-
-
5
5
- 15
-15
-20
-20
-
-
25
25
20
10
5
15
1. General LED on: indicates instrument energized.
2. Relay LED on: indicates relay energized, i.e. the input voltage is within
the set parameters.
3.
Fault LED (BVT ): flashing once per second: indicates lack of phase R
Flashing 2 times per second: indicates lack of phase S
Flashing 3 times per second: indicates lack of phase T
Flashing 4 times per second: indicates under voltage fault
Flashing 5 times per second: indicates overvoltage fault
Flashing constantly: indicates reversed phase sequence
LED Falha (BVD ): flashing once per second: indicates under voltage
fault
flashing twice per second: indicates overvoltage fault
Phase Protector (Motorsaver)
4. Under voltage setting
5. Hysteresis setting (only BVD )
6. Inhibit time setting
7. Delay time setting
8.
Maximum voltage setting
9. Asymmetry setting (BVT only ) Under voltage set
NOTE: While the units are preset at the factory, the power supply can differ at each installation site. Due to potential imbalances,
adjustments must be made before start-up. This is essential to safeguard the motors and electrical components of all units.