WIRING- MAIN POWER
!
WARNING
!
When installing the ground leakage protector make sure that
it is compatible with the inverter (resistant to high frequency
electrical noise) to avoid unnecessary opening of the ground
leakage protector.
NOTE: Voltage measurements should be taken at the unit’s
field power connection point during operation under full
load (maximum amperage operating condition) to ensure
accuracy.
For low voltage wiring, it is recommended to use an 18 gauge
copper cable that is color-coded for easy identification.
NOTE: Refer to the electrical wiring diagram for fuse
information (Example: F20A600V).
This symbol is used to identify any terminal
intended to be connected to an external
conductor for protection against electric
shock in the event of a fault, or the terminal of
a protective grounding electrode.
Protective ground (GND)
Primary markings on fuse cap
Eg: T 3.15A H 250V
Refer Table 4
Ampere
rating of
3.15 Amps
Voltage raiting of
250 Volts or Less
Refer Table 5
MARK
FUSE ELEMENT VELOCITY
SS
Very fast acting (Flink Flink)
F
Fast acting (Flink)
M
Medium acting (Mitterltrage)
T
Slow acting (Trage)
TT
Very slow acting (Trage Trage)
Table 4. Fuse element velocity markings
Table 5. Fuse element velocity markings
Fuse Nomenclature
MARK
BREAKING CAPACITY
H
High breaking capacity
L
Low breaking capacity
Table 6. Maximum overcurrent protection and Minimum circuit
amperage
RT/UN
Voltage
PH
MCA
MOP
3
208-230
1
42.5
57.25
3
208-230
1
53.13
76.38
3
208-230
3
37.63
48.48
5
208-230
3
41.5
55.45
3
460
3
14
19.2
5
460
3
16.75
24.15