This menu offers you, for example, the following options for the
basic configuration of the device:
TCP/IP configuration
(LIOB-48x/58x)
IP configuration page (IP address,
etc.).
Send identification
messages
Send a service pin message (LI-
OB-18x/48x) or an I-Am message
(LIOB-58x).
Restart system
By choosing this option, the device
performs a hard reset.
Delete DP configu-
ration
By choosing this item, the user can
clear the entire data point configura-
tion of the device.
Factory settings
By selecting this option, the user
can reset the entire device to factory
defaults.
PIN
Allows the default PIN to be changed
to any 4-digit number to protect
certain operations on the LCD user
interface. The user will be prompted to
enter the PIN in the protected areas.
Contrast
Change the display contrast.
Language
Change the LCD language. Note that
this requires a restart of the device.
Reset I/O counters
Resets all I/O counters such as pulse
count values.
To set the IP address on the LCD:
1. Navigate to the IP address on the main screen and press the
button.
2. Navigate to the required input fields, press and change the
value. Press again to set the value. Continue to the next field.
3. Finally navigate to Save and Restart and press.
4. Confirm the reboot and the device will reboot with the new IP
address.
To set the BACnet device ID through the LCD display:
1. On the main LCD screen, navigate to the Device Setup “”
option.
2. Then navigate to the BACnet menu “”.
3. In that menu, navigate to the ID entry to enter the device ID.
The field is divided into two controls, one for thousands and
one for singles, to simplify entering large numbers.
4. Once the device ID has been entered, the device name is
automatically mounted using that device ID, if no other name
has been configured in the web interface.
5. For the changes to take effect, the device must be rebooted. To
do this, you can select the menu option
Control
STATUS LED OF LIOB-58X/59X
The meaning of the LED signals for the LIOB-58x/59x models is
shown in Table .
Table 1. LIOB-58x/59x Status LED Patterns
Behavior
Description
Comment
Shutdown
No traffic
No packets are received or
transmitted.
Blinking GREEN
Traffic
L-IOB device is receiving or
transmitting packets.
ORANGE
Manual Mode
At least one I/O is in manual
mode.
RED
Error
An error has occurred (e.g. a
sensor is disconnected).
Red flashing at
0.5 Hz and "LIOB
Fallback" displayed
on LCD interface
Cancellation of
the reservation
The primary program image
is corrupted and the L-IOB
has started the backup
image. In this case, the pro-
gram must be updated again.
Содержание Clima-Flex CLIWP Series