cm-cliwp-cf-eng
www.clima-flex.com
10
2. The I/O available on that L-IOB device are shown in the
Inputs
/
Outputs
table.
LOYTEC INPUTS AND OUTPUTS
NAME
NOMENCLATURE
SENSOR TYPE
I/O
PHYSICS
AI
DI
AO
DO
(TRIAC
)
SPD
(500 Pa)
High Pressure
AP
N.O. Switch
UI-1
1
Low Pressure
BP
N.O. Switch
UI-2
1
Outdoor Temp.
TEx
Thermistor 10KM II
UI-3
1
Return Temp.
TR
Thermistor 10KM II
UI-4
1
Injection Temp.
TI
Thermistor 10KM II
UI-5
1
Motor Saver
MS
N.O. Switch
UI-6
1
AP Vent. Condenser
Apv
Relay 24 VAC
DO-1
1
AP Evaporator
Apc
Relay 24 VAC
DO-2
1
AP Compressor
APdx
24 VAC Relay
DO-3
1
AC Free Cooling
ACf
0-10 VDC
AO-1
1
Zone Temp.
TZ
LSTAT (MODBUS RTU)
Total points per Ctrl
3
3
1
3
0
3. To adapt the I/O name, double-click on the name in the
Name
column and edit it, e.g. ‘RoomTemp’.
4. Select (or multi-select) an I/O in the list of
Inputs/Outputs
and look at the list of
Object Parameters
below. These parameters can be
used to configure the I/O.
5. In the Data points tab, the data points for the I/O have been created. These data points can be used, for example, in the IEC61131
logiCAD program. For the inputs, the data point L1_x_UIand_Input will be used to read an input value and for the outputs the data point
L1_x_DOand_Output will be used to set an output value.
Control