Installation Manual

ED72-975

46

BRC1E61

3P243521-1

18 

English

 

Ɣ

If operation is not available due to any malfunction, refer to following 

Failure diagnosis method

 .

After the test operation  fi

 nishes, check that 

 

Ɣ

error

 code record is not displayed in the Service 

Contact/Model Information screen of the main menu according to the following procedure.

CAUTION

7-14 

Press Menu/Enter button in the basic 

screen. Main menu screen is dis-

played.

Select 

7-15 

 Service Contact/Model Info 

 in 

the main menu, and press Menu/Enter 

button.  

Service Contact/Model Information 

7-16 

screen is displayed. Check that error 

code record is not displayed in the 

screen.  

Screen which does not display the  

error code record means normal 

status.

If the error code record is displayed, 

7-17 

conduct the failure diagnosis referring 

to <Error code list> in the installation 

manual of the indoor unit.

After the failure diagnosis fi

 nishes, 

press and hold On/Of

f button for 

4 seconds or longer in the “Service 

Contact/Model Info” screen to erase 

the error code record. 

Failure diagnosis method

When the remote controller displays  

Ɣ

any item in following table, inspect the 

details in the table. 

If a error occurs, “code” is displayed in  

Ɣ

the LCD like right fi

 gure. 

Conduct the failure analysis referring to 

“Error code list” in the installation 

manual of the indoor unit. 

And when the unit No. which detected 

the error during group control is 

confi

 rmed, refer to “ 

8. Checking 

procedure of error record

”.

<Basic screen>

14

7-

Set temperature

28

°C

Cool

Return

Setting

Press Menu/Enter button.

<Main menu screen>

15

7-

Return

Setting

MainMenu

Set temp mode changeover

Airflow Direction

Quick Cool/Heat On/Of

f

V

e

ntilation

T

imer setting

Service Contact/Model Info

1/2

Press Menu/Enter button.

16

7-

17

7-

Return

Setting

Error code:U5

Indoor unit 

–––

/000

Outdoor unit 

–––

/000

Contact address

0123

4567

8900

Press and hold On/Of

button for  

4 seconds or 

longer during backlight lit. 

Set temperature

28

°C

Cool

T

e

st Operat. CODE : U5

01_EN_3P243521-1.indd   18

2/3/2009   1:19:23 PM

English 

17

7-6 

Press On/Of

f button within about 

10 seconds. 

The test operation starts. 

Check operation condition for 

3 minutes.

Note)  

In the case of above-men-

 

tioned procedures 

7-5

 and 

7-6

 in reverse order

, test 

operation  can start as well.

Press Menu/Enter button in the basic 

7-7 

screen.  

Main menu is displayed. 

In the case of a model having airfl

 ow 

7-8 

direction setting function, select 

 Airfl

 ow 

Direction 

 in the main menu 

and check that airfl

 ow direction is 

actuated according to the setting. 

For operation of airfl

 ow direction 

setting, see the operation manual.

After the operation of airfl

 ow direction 

7-9 

is confi

 rmed, press Menu/Enter button. 

Basic screen returns.

Press and hold Cancel button for 

7-10 

4 seconds or longer in the basic 

screen. 

Field setting menu is displayed. 

Select 

7-1

 T

est operation ON/OFF 

 in the 

fi 

eld setting menu, and press Menu/

Enter button. Basic screen returns and 

normal operation is conducted.

Check the functions according to the 

7-12 

operation manual.

When the decorative panel is not 

7-13 

installed, shut of

f the power supply 

after the test operation  fi

 nishes.

If interior work is not completed after the  

Ɣ

test operation fi

 nish, explain to the 

customer that operation should not be 

performed until the interior work comple-

tion to protect the indoor unit. 

(If the operation is performed, the 

indoor unit may be contaminated with 

the materials which arise from paints or 

adhesives during the interior work, and 

water splash or water leak may occur

.)

6

7-

7

7-

Set temperature

28

°C

Cool

T

e

st Operation

Press On/Of

f button 

(within 10 seconds).

Press Menu/Enter button.

<Main menu screen>

8

7-

Return

Setting

MainMenu

Set temp mode changeover

Airflow Direction

Quick Cool/Heat On/Of

f

V

entilation

T

imer setting

Service Contact/Model Info

1/2

Press Menu/Enter button.

9

7-

Return

Setting

Airflow Direction

Swing

Change the airfl

 ow 

direction by using 

 

(Up/Down)button.

Press Menu/Enter button.

10

7-

Set temperature

28

°C

Cool

T

e

st Operation

Press and hold Cancel 

button for  

4 seconds or 

longer during backlight lit. 

11

7-

Return

Setting

Field setting

T

e

st operation ON/OFF

Register Service Contract

Field setting list

Group No. setting

Indoor unit 

Airnet No. set

Outdoor unit 

Airnet No. set

1/2

Press Menu/Enter button.

<Basic screen>

01_EN_3P243521-1.indd   17

2/3/2009   1:19:22 PM

Содержание BRC1E61

Страница 1: ...ED72 975 Navigation Remote Controller Wired Remote Controller BRC1E61...

Страница 2: ...Direct Buttons 17 6 4 Quick Reference of Main Menu Items 22 6 5 Menu Manipulation 23 6 6 Maintenance 35 6 7 Useful Information 36 7 Installation Manual 38 7 1 Safety Precautions 38 7 2 Accessories 39...

Страница 3: ...Multilingual Display Available for selection of 10 languages to display arbitrarily Other Features Wide variety of functions to meet customer needs such as schedule setting and contact address displa...

Страница 4: ...imple and Functional Design 1 3 Simple Operation Compared to the conventional structure of button allocation for each function the number of buttons has been decreased from 15 to 9 Can intuitively han...

Страница 5: ...system Available for simple operation with arrow keys and menu driven system Available for simple operation with arrow keys and menu driven system Select the item you wish to set with direction keys a...

Страница 6: ...1 5 Available for simple operation with arrow keys and menu driven system Guide on display The item you wish to set can be changed with up or down button The display gives an explanation of each setti...

Страница 7: ...r display in 10 different languages Always available for switching display by selecting from main menu 10 languages English German French Spanish Italian Portuguese Greek Dutch Russian and Turkish Ope...

Страница 8: ...ED72 975 Features BRC1E61 7 1 5 Other Functions...

Страница 9: ...ot be set with the sub remote controller Restriction of operation from the sub remote controller When the On Off button is pressed in the sub remote controller during Home Leave operation in the main...

Страница 10: ...te controller DCS303A51 Wiring adaptor for electrical appendices KRP2A5 6 3 Quick Cooling Heating restriction for SkyAir only Under the following conditions Quick Cooling Heating operation stops to re...

Страница 11: ...975 10 BRC1E61 4 Dimensions 5 Applicable Models 5 1 Applicable Models 3D064037 Applicable Indoor unit VRV All models that can be connected BRC1C62 or BRC1D61 SkyAir All models that can be connected BR...

Страница 12: ...mote controller by yourself Improper installation may result in electric shocks or re Consult your Daikin dealer Do not use ammable materials e g hairspray or insecticide near the product Do not clean...

Страница 13: ...nsult the dealer if the air conditioner submerges owing to a natural disaster such as a ood or typhoon Do not operate the air conditioner in that case or otherwise a malfunction electric shock or re m...

Страница 14: ...Safety Precautions 01_EN_3P243520 1 indd 6 2 6 2009 5 49 57 PM English 5 CAUTION After prolonged use check the unit stand and its mounts for damage If left in a damaged condition the unit may fall an...

Страница 15: ...nd side Each screen is scrolled in the left hand direction Home leave settings are enabled with this button kept pressed for at least four seconds See page 19 On Off button 8 Press this button and sys...

Страница 16: ...lay See page 23 Displayed when the key lock is set 9 display See page 34 Displayed if the schedule timer or OFF reminder timer is enabled Under Centralized control 10 Displayed if the system is under...

Страница 17: ...on and swing are set see page 28 This item is not displayed if the system is not provided with a function to set air ow directions Clock 24 hours real time clock 14 Displayed if the clock is set see p...

Страница 18: ...ayed Return Setting MainMenu Set temp mode changeover Airflow Direction Quick Cool Heat On Off Ventilation Timer setting Service Contact Model info 1 2 Return Setting Timer setting Schedule timer Off...

Страница 19: ...h 6 The Operation lamp will be turned OFF and the system will stop operating when On Off button is pressed again While the system is in heating operation the system will be in fan operation for approx...

Страница 20: ...main menu see page 28 The air ow direction of the system cannot be changed unless the system is provided with a function to allow air ow direction changes 4 The Operation lamp will be turned OFF and...

Страница 21: ...ime Selection Settings 2 Set temperature 28 C Cool Return Setting Set temperature 28 C Cool Return Setting Press Operation Mode Selector button of the remote controller for which the selection eligibi...

Страница 22: ...28 C Cool Return Setting Press the remote controller that has the cooling heating selection eligibility or the remote controller without the display Changeover under control several times until the d...

Страница 23: ...mer Off reminder timer Home leave 01_EN_3P243520 1 indd 25 2 6 2009 5 50 03 PM 24 English The main menu has the following items Setting and display items Description Reference page Set temp mode chang...

Страница 24: ...s highlighted and ready to be changed The set temperature will increase by 1 C when the button is pressed and decrease by 1 C when the button is pressed Note The difference between the maximum and min...

Страница 25: ...rn to the basic screen 01_EN_3P243520 1 indd 29 2 6 2009 5 50 04 PM 28 English Air ow Direction Setting Manipulating Air ow Direction Setting Operation Method 1 Return Setting MainMenu Set temp mode c...

Страница 26: ...n the main menu screen Press Menu Enter button to return to the basic screen Quick Cooling Heating will no longer appear on the basic screen Quick Cooling Heating is now off 01_EN_3P243520 1 indd 31 2...

Страница 27: ...comfortable temperature Fan speed display goes off and fan speed can no longer be switched Cannot be set when in fan and dry modes Quick Cooling Heating mode will run for a maximum of 30 minutes befo...

Страница 28: ...temperature 28 C Cool Return Setting Selecting the desired ventilation mode and pressing Menu Enter button enters the settings and takes you back to the basic screen Pressing the Cancel button takes y...

Страница 29: ...be changed Press buttons to change the set temperature The set temperature will increase by 1 C when the button is pressed and decrease by 1 C when the button is pressed Pressing Menu Enter button ent...

Страница 30: ...nter button enters the schedule timer settings and takes you back to the basic screen 01_EN_3P243520 1 indd 39 2 6 2009 5 50 08 PM 38 English 5 Return Setting Monday Schedule timer Time Operation 06 0...

Страница 31: ...09 PM 40 English Holiday setting The schedule timer will be disabled for days that have been set as holiday Operation Method 1 Return Setting Schedule timer Enable Disable setting Condition setting Ho...

Страница 32: ...ings Operation Method 1 Return Setting Schedule timer Disable Off reminder Timer Disable Timer setting Bring up the timer settings screen See page 34 Press buttons to select the Off reminder timer on...

Страница 33: ...5 2 6 2009 5 50 10 PM 44 English Service Contact Model Information Display method for service contact and model information Operation Method 1 Return Setting MainMenu Set temp mode changeover Airflow...

Страница 34: ...ed by factors such as the location of the unit if it is in direct sunlight for e g and unit operation during defrosting After setting press Menu Enter button to con rm settings and return to the basic...

Страница 35: ...December 31 2099 Note 01_EN_3P243520 1 indd 49 2 6 2009 5 50 12 PM 48 English Setting Status List Manipulating the setting status list Operation Method 1 Return Setting MainMenu Convenient functions S...

Страница 36: ...button The display shown in 1 will disappear from the basic screen when the lter sign is reset 01_EN_3P243520 1 indd 51 2 6 2009 5 50 13 PM 50 English 7 Return Setting Is it settled by setting Clock...

Страница 37: ...ify your Daikin dealer of the Error code and Model name 01_EN_3P243520 1 indd 53 2 6 2009 5 50 14 PM 52 English Caution Do not wash the remote controller Doing so may cause electric leakage and result...

Страница 38: ...ems Model name Date of installation Failure conditions As precise as possible Your address name and telephone number Relocation The relocation of the remote controller requires special technology Cons...

Страница 39: ...eakage electric shocks or re Be sure to use only the speci ed accessories and parts for installation work Failure to use the speci ed parts may result in the unit falling water leaakage electric shock...

Страница 40: ...mote controller with water as this may result in electric shocks or re Install the indoor and outdoor units power cord and connecting wires at least 1 meter away from televisions or radios to prevent...

Страница 41: ...EMC Electromagnetic Compatibility Australian regulation NOTE 01_EN_3P243521 1 indd 6 2 3 2009 1 19 17 PM English 5 Determine the direction of controller wiring outlet back 3 4 outlet left outlet upper...

Страница 42: ...y using attached small screws 2 pcs Small screws M4 16 Switch box field supply Use optional accessory KJB211A Switch box for two units with no cover 84 46 Installation pitch 01_EN_3P243521 1 indd 8 2...

Страница 43: ...t temperature The next items on the lower side will be highlighted The highlighted items will be scrolled continuously when the button is kept pressed Used to change the item selected Right button 6 U...

Страница 44: ...or longer the Operation mode selector button of sub remote controller side Connection under check Please wait for a moment Sub remote contrl Basic screen 2 5 Set temperature 28 C Fan Return Press the...

Страница 45: ...screen 6 6 7 6 Return Setting Is it settled by setting Field setting list Yes No Press Menu Enter button Setting con rmation 01_EN_3P243521 1 indd 14 2 3 2009 1 19 21 PM English 13 Field setting meth...

Страница 46: ...light lit Field setting menu screen 5 7 Return Setting Field setting Test operation ON OFF Register Service Contract Field setting list Group No setting Indoor unit Airnet No set Outdoor unit Airnet N...

Страница 47: ...hin about 10 seconds The test operation starts Check operation condition for 3 minutes Note In the case of above men tioned procedures 7 5 and 7 6 in reverse order test operation can start as well Pre...

Страница 48: ...nter button Field setting menu screen 01_EN_3P243521 1 indd 20 2 3 2009 1 19 25 PM English 19 Remote controller display Description No display Power outage power voltage error or open phase Wrong wiri...

Страница 49: ...asic screen Main menu screen 1 11 Return Setting MainMenu Convenient functions Setting status list Clock setting Language changeover 2 2 Press Menu Enter button 2 11 3 11 Return Setting Clock setting...

Страница 50: ...ED72 975 Printed in Japan 06 2009 K FS Specifications designs and other content appearing in this brochure are current as of April 2009 but subject to change without notice...

Отзывы: