Indoor Unit
SiENBE04-512A
140
Removal Procedure
1. Indoor Unit
1.1
Removal of Air Filter
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1. External features
If ON/OFF button is kept
pushing for 5 seconds, a
forced cooling operation will
be carried out for approx. 15
minutes.
2. Removing air filters
1
Pull protrusions on left
and right sides of panel
with fingers and open
front grille all the way.
2
Lift center section of air
filter and disengage
hooks.
Remove air filter by
pulling forward.
Left and right filters are
interchangeable.
To re-install, insert air filter
along the guide.
ON/OFF
bu
tton
Receiver
Intelligent eye
(R2509)
Oper
a
tion
l
a
mp (Green)
HOME
LEAVE
l
a
mp
(Red)
Timer l
a
mp
(Yellow)
SiENBE04-512A.book Page 140 Friday, October 5, 2007 1:49 PM
Содержание ARKH20CVMB7
Страница 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series ...
Страница 17: ...List of Functions SiENBE04 512A 8 List of Functions ...
Страница 18: ...SiENBE04 512A Specifications 9 Part 2 Specifications 1 Specifications 10 1 1 Cooling Only 10 1 2 Heat Pump 16 ...
Страница 37: ...Specifications SiENBE04 512A 28 Specifications ...
Страница 73: ...Control Specification SiENBE04 512A 64 Function and Control ...
Страница 103: ...Instruction SiENBE04 512A 94 System Configuration ...
Страница 147: ...Check SiENBE04 512A 138 Service Diagnosis ...
Страница 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure ...
Страница 226: ...SiENBE04 512A Others 217 Part 8 Others 1 Others 218 1 1 Test Run from the Remote Control 218 1 2 Jumper Settings 219 ...
Страница 229: ...Others SiENBE04 512A 220 Others ...
Страница 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix ...
Страница 245: ...SiENBE04 512A iv Index wiring diagrams 229 ...