4.13 High Pressure Control in Cooling
Remote Control
Display
F6
Method of
Malfunction
Detection
High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the
temperature being sensed by the heat exchanger thermistor exceeds the limit.
Malfunction
Decision
Conditions
Activated when the temperature being sensed by the heat exchanger thermistor rises above
65°C. (The error is cleared when the temperature drops below 54°C.)
Supposed
Causes
The installation space is not large enough.
Faulty outdoor unit fan
Faulty electronic expansion valve
Faulty defrost thermistor
Faulty outdoor unit PCB
Faulty stop valve
Dirty heat exchanger
SiENBE04-512A.book Page 115 Friday, October 5, 2007 1:49 PM
Содержание ARKH20CVMB7
Страница 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series ...
Страница 17: ...List of Functions SiENBE04 512A 8 List of Functions ...
Страница 18: ...SiENBE04 512A Specifications 9 Part 2 Specifications 1 Specifications 10 1 1 Cooling Only 10 1 2 Heat Pump 16 ...
Страница 37: ...Specifications SiENBE04 512A 28 Specifications ...
Страница 73: ...Control Specification SiENBE04 512A 64 Function and Control ...
Страница 103: ...Instruction SiENBE04 512A 94 System Configuration ...
Страница 147: ...Check SiENBE04 512A 138 Service Diagnosis ...
Страница 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure ...
Страница 226: ...SiENBE04 512A Others 217 Part 8 Others 1 Others 218 1 1 Test Run from the Remote Control 218 1 2 Jumper Settings 219 ...
Страница 229: ...Others SiENBE04 512A 220 Others ...
Страница 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix ...
Страница 245: ...SiENBE04 512A iv Index wiring diagrams 229 ...