SiENBE04-512A
Troubleshooting
Service Diagnosis
119
4.16 Thermistor or Related Abnormality (Outdoor Unit)
Remote Control
Display
P4, J3, J6, H9
Method of
Malfunction
Detection
This type of error is detected by checking the thermistor input voltage to the microcomputer.
[A thermistor error is detected by checking the temperature.]
Malfunction
Decision
Conditions
The thermistor input is above 4.96 V or below 0.04 V with the power on.
Error
J3
is judged if the discharge pipe thermistor temperature is smaller than the condenser
thermistor temperature.
Supposed
Causes
Connector in poor contact
Thermistor defective
Outdoor unit PCB defective
Indoor unit PCB defective
Condenser thermistor defective in the case of
J3
error (outdoor unit heat exchanger
thermistor in the cooling mode, or indoor unit heat exchanger thermistor in the heating
mode)
SiENBE04-512A.book Page 119 Friday, October 5, 2007 1:49 PM
Содержание ARKH20CVMB7
Страница 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series ...
Страница 17: ...List of Functions SiENBE04 512A 8 List of Functions ...
Страница 18: ...SiENBE04 512A Specifications 9 Part 2 Specifications 1 Specifications 10 1 1 Cooling Only 10 1 2 Heat Pump 16 ...
Страница 37: ...Specifications SiENBE04 512A 28 Specifications ...
Страница 73: ...Control Specification SiENBE04 512A 64 Function and Control ...
Страница 103: ...Instruction SiENBE04 512A 94 System Configuration ...
Страница 147: ...Check SiENBE04 512A 138 Service Diagnosis ...
Страница 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure ...
Страница 226: ...SiENBE04 512A Others 217 Part 8 Others 1 Others 218 1 1 Test Run from the Remote Control 218 1 2 Jumper Settings 219 ...
Страница 229: ...Others SiENBE04 512A 220 Others ...
Страница 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix ...
Страница 245: ...SiENBE04 512A iv Index wiring diagrams 229 ...