SiBE04-302
Troubleshooting
Service Diagnosis
115
4.18
Insufficient Gas
Remote
Controller
Display
U0
Method of
Malfunction
Detection
Gas shortage detection I : A gas shortage is detected by checking the CT-detected input current
value and the compressor running frequency.
Gas shortage detection II : A gas shortage is detected by checking the difference between
indoor unit heat exchanger temperature and room temperature as well as the difference
between outdoor unit heat exchanger temperature and room temperature.
Malfunction
Decision
Conditions
Gas shortage detection I :
Input current <
(A/Hz) x Compressor running frequency × V
However, when the status of running frequency >
(Hz) is kept on for a certain time.
Note : The values are different from model to model.
Gas shortage detection II :
If a gas shortage error takes place 4 times successively, the system will be shut down. The error
counter will reset itself if this or any other error does not occur during the following 60-minute
compressor running time (total time).
Supposed
Causes
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Discharge pipe thermistor disconnected, or indoor unit or outdoor unit heat exchanger
thermistor disconnected, room or outdoor air temperature thermistor disconnected
Stop valve closed
Electronic expansion valve defective
FTK(X)S, ATK(X)S series.
1120 / 256
–80
65
Others
2760 / 256
–140
55
Содержание ARK25BVMB
Страница 10: ...SiBE04 302 List of Function 1 Part 1 List of Function 1 Functions 2 1 1 Cooling Only 2 1 2 Heat Pump 5 ...
Страница 17: ...Functions SiBE04 302 8 List of Function ...
Страница 31: ...Specifications SiBE04 302 22 Specifications ...
Страница 137: ...Check SiBE04 302 128 Service Diagnosis ...
Страница 170: ...SiBE04 302 Outdoor Unit Removal Procedure 161 2 Slide the MID upward and release Step Procedure Points ...
Страница 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Страница 177: ...Outdoor Unit SiBE04 302 168 Removal Procedure 2 Slide the reactor assembly this side and release Step Procedure Points ...
Страница 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Страница 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Страница 199: ...SiBE04 302 iv Index ...