Troubleshooting
SiBE04-302
94
Service Diagnosis
Troubleshooting
Check No.6
Refer to P.122
Note:
If the outdoor air temperature is below –10°C in the cooling mode, the system may get
interrupted with error
A5
displayed. The system will be reset itself, but this stop will be put in the
error history memory.
NO
NO
NO
Check No. 6
Indoor unit heat exchanger
thermistor check
Check the intake air filter.
Check the air passage.
YES
YES
(R1401)
Check the dust accumulation on
the indoor unit heat exchanger.
YES
YES
Is there any
short-circuit?
Is it very dirty?
Is it very dirty?
Does it conform to
the thermistor characteristic
chart?
NO
Provide sufficient air passage.
Clean the air filter.
Clean the heat exchanger.
Replace the indoor unit PCB.
Replace the thermistor
(replace the indoor unit PCB).
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание ARK25BVMB
Страница 10: ...SiBE04 302 List of Function 1 Part 1 List of Function 1 Functions 2 1 1 Cooling Only 2 1 2 Heat Pump 5 ...
Страница 17: ...Functions SiBE04 302 8 List of Function ...
Страница 31: ...Specifications SiBE04 302 22 Specifications ...
Страница 137: ...Check SiBE04 302 128 Service Diagnosis ...
Страница 170: ...SiBE04 302 Outdoor Unit Removal Procedure 161 2 Slide the MID upward and release Step Procedure Points ...
Страница 172: ...SiBE04 302 Outdoor Unit Removal Procedure 163 4 Remove the fan motor Step Procedure Points ...
Страница 177: ...Outdoor Unit SiBE04 302 168 Removal Procedure 2 Slide the reactor assembly this side and release Step Procedure Points ...
Страница 184: ...SiBE04 302 Others 175 Part 8 Others 1 Others 176 1 1 Explanation 176 1 2 Jumper Settings 177 ...
Страница 195: ...Wiring Diagrams SiBE04 302 186 Appendix ...
Страница 199: ...SiBE04 302 iv Index ...