Breadcrumb Field code
Range, step
Default value
Date
Value
User settings
└─ Preset values
└─ Room temperature
7.4.1.1
R/W
[3-07]~[3-06], step: A.3.2.4
21°C
7.4.1.2
R/W
[3-07]~[3-06], step: A.3.2.4
21°C
└─ LWT main
7.4.2.1
[8-09]
R/W
[9-01]~[9-00], step: 1°C
45°C
7.4.2.2
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
40°C
7.4.2.5
R/W
-10~10°C, step: 1°C
0°C
7.4.2.6
R/W
-10~10°C, step: 1°C
-2°C
└─ Tank temperature
7.4.3.1
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
7.4.3.2
[6-0B]
R/W
30~min(50, [6-0E]) °C, step: 1°C
50°C
7.4.3.3
[6-0C]
R/W
30~min(50, [6-0E]) °C, step: 1°C
50°C
└─ Quiet level
7.4.4
R/W
0: Level 1
1: Level 2
2: Level 3
└─ Electricity price
7.4.5.1
R/W
0,00~990/kWh
0,01/kWh
7.4.5.2
R/W
0,00~990/kWh
0,01/kWh
7.4.5.3
R/W
0,00~990/kWh
0,01/kWh
└─ Fuel price
7.4.6
R/W
0,00~990/kWh
0,00~290/MBtu
8,0/kWh
└─ Set weather dependent
└─ Main
└────────────────── Set weather-dependent heating
7.7.1.1
[1-00]
Set weather-dependent heating
Low ambient temp. for LWT main zone heating
WD curve.
R/W
-40~5°C, step: 1°C
-10°C
7.7.1.1
[1-01]
Set weather-dependent heating
High ambient temp. for LWT main zone heating
WD curve.
R/W
10~25°C, step: 1°C
15
°C
7.7.1.1
[1-02]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~[9-00]°C, step: 1°C
55°C
7.7.1.1
[1-03]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~min(45,[9-00])°C, step: 1°C
25°C
Installer settings
└─ System layout
└─ Standard
A.2.1.1
[E-00]
R/O
0~6
6: Monobloc Hybrid
A.2.1.2
[E-01]
R/O
0: 08
A.2.1.3
[E-02]
R/O
0: Type 1
1: Type2
A.2.1.7
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
A.2.1.9
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
A.2.1.A
[E-04]
R/O
1: Yes
A.2.1.B
R/W
0: At unit
1: In room
A.2.1.C
[E-0D]
Glycol setting
R/W
0: No
1: Yes
A.2.1.D
[4-04]
Water pipe freeze prevention
R/O
0: intermittent pump operation
1: Continuous pump operation
2: OFF
A.2.1.E
[C-02]
Hybrid system type
R/W
0: Boiler
1: Bivalent boiler
└─ Options
A.2.2.1
[E-05]
R/W
0: No
1: Yes
A.2.2.2
[E-06]
R/W
0: No
1: Yes
A.2.2.3
[E-07]
R/W
0~6
0: Type1(EKHWS*D* )
4: Type 5(EKHWP*)
6: Type 7(Third party)
A.2.2.4
[C-05]
R/W
1: Thermo ON/OFF
2: C/H request
A.2.2.A
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circul. Pump
4: CP & disinf. Sh
A.2.2.B
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
A.2.2.G
R/W
0: No
1: Yes
A.2.2.H
[F-04]
Electric heaters
R/W
0: No
1: BPH only
2: BPH+DTH Type1
3: BPH+DTH Type2
4: BPH+DTH Type3
└─ Space operation
└─ LWT settings
└────────────────── Main
DHW operation
DHW tank
DHW tank type
Contact type main
LAN Adapter
High
Medium
Low
Pump operation mode
Power saving possible
User interface location
Unit type
Compressor type
Unit control method
Comfort (heating)
Eco (heating)
Comfort (heating)
DHW pump
External sensor
Indoor software type
Field settings table
Installer setting at variance with
default value
Setting name
Comfort (heating)
Eco (heating)
Eco (heating)
Storage comfort
Storage eco
Reheat
4P564438-1 - 2018.12