7
|
Unit installation
Installer reference guide
71
ERGA04~08EA + EHBH/X04+08EF
Daikin Altherma 3 R W
4P629085-1B – 2021.11
If…
Then…
Total refrigerant charge in the
system
Room type
Allowed patterns
<1.84 kg (i.e. if the piping length is
<27 m)
All
1
(2, 3 and 4 are superfluous. There is
no need to check the minimum floor
area or to provide ventilation
openings.)
≥1.84 kg (i.e. if the piping length is
≥27 m)
Living room, kitchen, garage, attic,
basement, storage room
2, 3
Technical room (i.e. room that is
NEVER occupied by persons)
2, 3, 4
PATTERN 1
PATTERN 2
PATTERN 3
PATTERN 4
A
A
a2
a1
A
B
a2
a1
A
Ventilation openings
N/A
N/A
Between room A
and B
Between room A
and outside
Minimum floor area
N/A
Room A
Room A + Room B
N/A
Restrictions
See
See
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
a1
Bottom opening for natural ventilation
a2
Top opening for natural ventilation
PATTERN 1
For PATTERN 1 you only need to comply with the spacing guidelines described in
requirements of the indoor unit"
69].
PATTERN 2 and 3
For PATTERN 2 and 3, additionally to the spacing guidelines described in
"7.1.3 Installation site requirements of
69], you also need to comply with the minimum floor area requirements as described in the
following flow chart. The flow chart uses the following tables:
"16.5 Table 1 – Maximum refrigerant charge allowed
"16.6 Table 2 – Minimum floor area: indoor unit"
278] and
Minimum bottom opening area for natural ventilation: indoor unit"
279].