For the main zone:
-
The mixing valve station (including pump + mixing valve) is installed before the
underfloor heating.
-
The mixing valve station is controlled by the bizone kit controller (EKMIKPOA)
based on the heating request of the room.
-
The room temperature is controlled by the dedicated Human Comfort
Interface (BRC1HHDA used as room thermostat).
-
Ensure water circulation is possible in main zone when shut-off valves are
closed
-
In cooling mode, you can allow the underfloor heating (main zone) to provide
refreshment (no real cooling), or NOT allow it.
If allowed:
Do NOT install a shut-off valve.
Set [F-0C]=0 to activate the setpoint screen of [2]
Main zone
and [1]
Room
.
Set the leaving water temperature of the main zone NOT too low (typically:
20°C)
If NOT allowed
, install a shut-off valve (field supply) and connect it to X2M/21
and X2M/28 for a normally open valve or X2M/21 and X2M/29 for a normally
closed valve.
▪
For the additional zone:
-
The heat pump convectors are directly connected to the indoor unit.
-
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat
pump convectors. For more information, see:
The installation manual of the heat pump convectors
The installation manual of the heat pump convector options
The addendum book for optional equipment
-
The heating or cooling demand signals of each heat pump convector are
connected in parallel to the digital input on the indoor unit (X2M/35a and
X2M/30). The indoor unit will only supply the desired additional leaving water
temperature when there is an actual demand.
▪
The user interface integrated in the indoor unit decides the space operation
mode. Mind that the operation mode on each remote controller of the
heat pump convectors must be set to match the indoor unit.
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C‑07]
2 (
Room thermostat
): Unit operation
is decided based on the ambient
temperature of the dedicated Human
Comfort Interface.
Note:
▪
Main room = dedicated Human
Comfort Interface used as room
thermostat functionality
▪
Other rooms = external room
thermostat functionality