6
|
Application guidelines
Installer reference guide
36
EPRA08~W1 + ETBH/9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
▪
Efficiency.
Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heat pump system.
▪
Comfort.
In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.
Heat pump convectors
Setup
A
B
a
A
Main leaving water temperature zone
B
One single room
a
Heat pump convectors (+ controllers)
▪
For more information about connecting the electrical wiring to the unit, see:
-
"9.2 Connections to the outdoor unit"
-
"9.3 Connections to the indoor unit"
▪
The heat pump convectors are connected as follows:
-
Warm water → Indoor unit
-
Cold water → Outdoor unit
▪
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump
convectors. For more information, see:
-
The installation manual of the heat pump convectors
-
The installation manual of the heat pump convector options
-
The addendum book for optional equipment
▪
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
▪
The space operation mode is sent to the heat pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
1 (
External room thermostat
):
Unit operation is decided by the
external thermostat.