9 Hand-over to the user

Installation manual

34

ETV23E

Daikin Altherma 3 H HT F

4P644729-1E – 2023.10

8.2.5

To perform an underfloor heating screed
dryout

Conditions: 

Make  sure  all  operation  is  disabled.  Go  to  [C]:

Operation

  and  turn  off 

Space  heating/cooling

  and 

Tank

operation.

1

Set the user permission level to Installer. See 

"To

change the user permission level"

 [

4

 23].

2

Go to [A.4]: 

Commissioning

 > 

UFH screed dryout

.

3

Set a dryout program: go to 

Program

 and use the

UFH screed dryout programming screen.

4 Select 

OK

 to confirm.

Result: 

The underfloor heating screed dryout starts.

It stops automatically when done.

To stop the test run manually:

1

Go to 

Stop UFH screed dryout

.

2

Select 

OK

 to confirm.

NOTICE

To perform an underfloor heating screed dryout, room frost
protection needs to be disabled ([2‑06]=0). By default, it is
enabled  ([2‑06]=1).  However,  due  to  the  "installer-on-site"
mode (see "Commissioning"), room frost protection will be
automatically disabled for 12 hours after the first power-on.

If  the  screed  dryout  still  needs  to  be  performed  after  the
first  12  hours  of  power-on,  manually  disable  room  frost
protection  by  setting  [2‑06]  to  "0",  and  KEEP  it  disabled
until the screed dryout has finished. Ignoring this notice will
result in cracking of the screed.

NOTICE

For the underfloor heating screed dryout to be able to start,
make sure the following settings are met:

▪ [4‑00]=1

▪ [C‑02]=0

▪ [D‑01]=0

▪ [4‑08]=0

▪ [4‑01]≠1

9

Hand-over to the user

Once  the  test  run  is  finished  and  the  unit  operates  properly,  make
sure the following is clear for the user:

▪ Fill in the installer setting table (in the operation manual) with the

actual settings.

▪ Make  sure  that  the  user  has  the  printed  documentation  and  ask

him/her to keep it for future reference. Inform the user that he can
find the complete documentation at the URL mentioned earlier in
this manual.

▪ Explain the user how to properly operate the system and what to

do in case of problems.

▪ Show the user what to do for the maintenance of the unit.

▪ Explain  the  user  about  energy  saving  tips  as  described  in  the

operation manual.

10

Maintenance and service

NOTICE

General  maintenance/inspection  checklist.

  Next  to  the

maintenance  instructions  in  this  chapter,  a  general
maintenance/inspection  checklist  is  also  available  on  the
Daikin Business Portal (authentication required).

The 

general 

maintenance/inspection 

checklist 

is

complementary  to  the  instructions  in  this  chapter  and  can
be  used  as  a  guideline  and  reporting  template  during
maintenance.

NOTICE

Maintenance  MUST  be  done  by  an  authorised  installer  or
service agent.

We  recommend  performing  maintenance  at  least  once  a
year. However, applicable legislation might require shorter
maintenance intervals.

10.1

Overview: Maintenance and
service

This chapter contains information about:

▪ The yearly maintenance of the indoor unit

▪ Draining the domestic hot water tank

▪ Inspecting the inside of the domestic hot water tank

▪ Cleaning the water filter in case of trouble

10.2

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

NOTICE: Risk of electrostatic discharge

Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.

10.3

Checklist for yearly maintenance of
the indoor unit

Check the following at least once a year:

▪ Water pressure

▪ Magnetic filter/dirt separator

▪ Water pressure relief valve

▪ Relief valve hose

▪ Pressure relief valve of the domestic hot water tank

▪ Switch box

▪ Descaling

▪ Chemical disinfection

▪ Pressure reducing valve

▪ Temperature and pressure relief valve

Содержание Altherma 3 H HT F ETVH16SU18E 6V Series

Страница 1: ...Installation manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16SU18E 6V ETVH16SU23E 6V 1 2 3 9 A B C Z 1 2 3 9 https daikintechnicaldatahub eu...

Страница 2: ...uration 22 7 1 Overview Configuration 22 7 1 1 To access the most used commands 23 7 2 Configuration wizard 23 7 2 1 Configuration wizard Language 24 7 2 2 Configuration wizard Time and date 24 7 2 3...

Страница 3: ...and By Me platform is required For more information see https professional standbyme daikin eu Daikin e Care Mobile app for installers and service technicians that allows you to register configure and...

Страница 4: ...be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Do NOT push or place redundant cable length into the unit WARNING The backup heater...

Страница 5: ...ng Regulations you must verify that the following accessories are present Delivered with indoor unit Tundish 15 mm inlet 22 mm outlet Delivered with domestic hot water tank kit Pressure reducing valve...

Страница 6: ...e top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove t...

Страница 7: ...torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoor unit 1 Lift the indoor unit from the pallet and place it on the floor Also see 3 1 2 To handle the indoor unit...

Страница 8: ...m water pressure is 3 bar 0 3 MPa Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded The minimum water pressure to operate is 1 bar 0 1 MPa Water temp...

Страница 9: ...OUT to outdoor unit screw connection 1 NOTICE It is recommended to install shut off valves to domestic cold water in and domestic hot water out connections These shut off valves are field supplied How...

Страница 10: ...e relief valve combination to the water mains inlet 7 Install the tundish part of the kit in a vertical position within a maximum of 600 mm away from the pressure reducing valve pressure relief valve...

Страница 11: ...200 thereafter Maximum permitted equivalent length of 22 mm pipework is 9 m Each bend or elbow is equivalent to 0 8 m of pipework 5 2 3 To connect the recirculation piping Prerequisite Only required i...

Страница 12: ...30 30 C 35 INFORMATION Protection against bursting the glycol will prevent the piping from bursting but NOT the liquid inside the piping from freezing Protection against freezing the glycol will preve...

Страница 13: ...7 Alarm output See 6 3 6 To connect the alarm output 418 Space cooling heating operation control See 6 3 7 To connect the space cooling heating ON OFF output 418 Changeover to external heat source con...

Страница 14: ...bizone kit 9 P Bizone kit for room thermostat wired or wireless In case of See Wireless room thermostat Installation manual of the wireless room thermostat Addendum book for optional equipment Wired r...

Страница 15: ...ower supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed ALWAYS connect the backup heater power supply and the...

Страница 16: ...OTICE Do NOT cut or remove the backup heater power supply cable 6 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zone and a combination of underfloor hea...

Страница 17: ...User interface panel 3 Upper switch box cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below A 6 5 4 3 S3S S2S B A B X5M 3 4 5 6 3 Fix the cable...

Страница 18: ...between X2M 7 9 and Q1L thermal protector backup heater Do NOT change 3 Fix the cable with cable ties to the cable tie mountings 6 3 7 To connect the space cooling heating ON OFF output Wires 2 1 0 75...

Страница 19: ...ppropriate terminals as shown in the illustration below A X1 X2 L N B A B A4P X2M X1 a X2 a Installation of EKRP1HBAA is required 3 Fix the cable with cable ties to the cable tie mountings 6 3 9 To co...

Страница 20: ...ermostat stop error 8H 03 will occur 6 3 11 To connect a Smart Grid This topic describes 2 possible ways to connect the indoor unit to a Smart Grid In case of low voltage Smart Grid contacts In case o...

Страница 21: ...K1A L N L N STEP 3 a b c d e f STEP 1 STEP 2 A1 A2 4 3 2 1 X10M K2A A1 A2 2 1 STEP 1 Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Sma...

Страница 22: ...o and know to configure the system after it is installed NOTICE This chapter explains only the basic configuration For more detailed explanation and background information see the installer reference...

Страница 23: ...ngs can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the user permi...

Страница 24: ...the user interface go to the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not Alternatively when Emergency is set to auto SH reduced DHW on spac...

Страница 25: ...n control feature to work properly When measuring the resistance value of each heater you can set the exact heater capacity and this will lead to more accurate energy data Backup heater type The backu...

Страница 26: ...hermostat Unit operation is decided by the external thermostat or equivalent e g heat pump convector Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human C...

Страница 27: ...ction function To set the heat pump ON hysteresis Code Description 5 9 6 00 Heat pump ON hysteresis 2 C 40 C Settings for Schedule only mode and Schedule reheat mode Comfort setpoint Only applicable w...

Страница 28: ...ailable for Main zone Heating Main zone Cooling Additional zone Heating Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpo...

Страница 29: ...define the setpoint mode To use the weather dependent curve you need to define the correct setpoint mode Go to setpoint mode Set the setpoint mode to Main zone Heating 2 4 Main zone Setpoint mode WD h...

Страница 30: ...menus The most important settings are presented here 7 4 1 Main zone Ext thermostat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external...

Страница 31: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Страница 32: ...nce guide The indoor unit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the...

Страница 33: ...start the measurement will be successful Before 30 min from start the measurement might be unsuccessful If the measurement is successful the logic to activate the backup heater will use a timeframe tu...

Страница 34: ...r to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system and what t...

Страница 35: ...ter coming out of the relief valve open the valve until the discharged water does NOT contain dirt anymore flush the system It is recommended to do this maintenance more frequently Pressure relief val...

Страница 36: ...Temperature and pressure relief valve Check for correct operation of the temperature and pressure relief valve Manually operate the temperature and pressure relief valve to ensure free water flow thr...

Страница 37: ...can thoroughly clean it Then you need to do as follows 10 6 1 To remove the water filter 437 10 6 2 To clean the water filter in case of trouble 438 10 6 3 To install the water filter 438 10 6 1 To r...

Страница 38: ...er housing and clean with water 4 Install the cleaned rolled up filter and strainer in the water filter housing INFORMATION Correctly install the strainer in the magnetic filter dirt separator housing...

Страница 39: ...B2L B f B f A Indoor unit B Field installed a1 Space heating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW...

Страница 40: ...eless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON OFF thermostat wired...

Страница 41: ...stic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat For safety thermostat For smartgr...

Страница 42: ...l kWh rate power supply installation Unit power supply 400 V or 230 V earth Only for normal power supply installation OUTDOOR UNIT STANDARD PART POWER SUPPLY WLAN module communication 5 core A20P J2 X...

Страница 43: ...VH16SU23EA6V 30 12 kW Primary flow rate to reach primary heating power input 15 l min Standing heat loss ETVH16SU18EA6V 1 35 kWh 24h ETVH16SU23EA6V 1 76 kWh 24h Model storage capacity mass of unit whe...