7 Configuration

Installation manual

23

ETV23E
Daikin Altherma 3 H HT F
4P644729-1E – 2023.10

Accessing settings – Legend for tables

You  can  access  the  installer  settings  using  two  different  methods.
However,  NOT  all  settings  are  accessible  via  both  methods.  If  so,
the  corresponding  table  columns  in  this  chapter  are  set  to  N/A  (not
applicable).

Method

Column in tables

Accessing settings via the breadcrumb in the

home menu screen

 or the 

menu structure

.

To enable breadcrumbs, press the   button
in the home screen.

#

For example: [2.9]

Accessing settings via the code in the

overview field settings

.

Code

For example: [C-07]

See also:

"To access the installer settings"

 [

4

 23]

"7.5 Menu structure: Overview installer settings"

 [

4

 31]

7.1.1

To access the most used commands

To change the user permission level

You can change the user permission level as follows:

1

Go to [B]: 

User profile

.

User profile

B

2

Enter the applicable pin code for the user permission
level.

▪ Browse  through  the  list  of  digits  and  change  the

selected digit.

▪ Move the cursor from left to right.

▪ Confirm the pin code and proceed.

Installer pin code

The 

Installer

  pin  code  is 

5678

.  Additional  menu  items  and

installer settings are now available.

5678

Installer

Advanced user pin code

The 

Advanced user

 pin code is 

1234

. Additional menu items for the

user are now visible.

1234

Advanced user

User pin code

The 

User

 pin code is 

0000

.

0000

User

To access the installer settings

1

Set the user permission level to 

Installer

.

2

Go to [9]: 

Installer settings

.

To modify an overview setting

Example: 

Modify [1‑01] from 15 to 20.

Most  settings  can  be  configured  via  the  menu  structure.  If  for  any
reason it is required to change a setting using the overview settings,
then the overview settings can be accessed as follows:

1

Set the user permission level to 

Installer

. See 

"To

change the user permission level"

 [

4

 23].

2

Go to [9.I]: 

Installer settings

 > 

Overview

field settings

.

3

Turn the left dial to select the first part of the setting
and confirm by pressing the dial.

00
01
02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

0

1

2
3

4

Turn the left dial to select the second part of the
setting

00
01

15

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

5

Turn the right dial to modify the value from 15 to 20.

00
01

20

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

6

Press the left dial to confirm the new setting.

7

Press the center button to go back to the home
screen.

INFORMATION

When  you  change  the  overview  settings  and  you  go  back
to  the  home  screen,  the  user  interface  will  show  a  popup
screen and request to restart the system.

When  confirmed,  the  system  will  restart  and  recent
changes will be applied.

7.2

Configuration wizard

After  first  power  ON  of  the  system,  the  user  interface  starts  a
configuration wizard. Use this wizard to set the most important initial
settings  for  the  unit  to  run  properly.  If  required,  you  can  afterwards
configure  more  settings.  You  can  change  all  these  settings  via  the
menu structure.

Protective functions

The unit is equipped with the following protective functions:

▪ Room antifrost [2-06]

▪ Water pipe freeze prevention [4-04]

▪ Tank disinfection [2-01]

The unit automatically runs the protective functions when necessary.
During installation or service, this behaviour is undesired. Therefore,
the  protective  functions  can  be  disabled.  For  more  information,  see
the Installer reference guide, chapter Configuration.

Содержание Altherma 3 H HT F ETVH16SU18E 6V Series

Страница 1: ...Installation manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16SU18E 6V ETVH16SU23E 6V 1 2 3 9 A B C Z 1 2 3 9 https daikintechnicaldatahub eu...

Страница 2: ...uration 22 7 1 Overview Configuration 22 7 1 1 To access the most used commands 23 7 2 Configuration wizard 23 7 2 1 Configuration wizard Language 24 7 2 2 Configuration wizard Time and date 24 7 2 3...

Страница 3: ...and By Me platform is required For more information see https professional standbyme daikin eu Daikin e Care Mobile app for installers and service technicians that allows you to register configure and...

Страница 4: ...be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Do NOT push or place redundant cable length into the unit WARNING The backup heater...

Страница 5: ...ng Regulations you must verify that the following accessories are present Delivered with indoor unit Tundish 15 mm inlet 22 mm outlet Delivered with domestic hot water tank kit Pressure reducing valve...

Страница 6: ...e top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove t...

Страница 7: ...torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoor unit 1 Lift the indoor unit from the pallet and place it on the floor Also see 3 1 2 To handle the indoor unit...

Страница 8: ...m water pressure is 3 bar 0 3 MPa Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded The minimum water pressure to operate is 1 bar 0 1 MPa Water temp...

Страница 9: ...OUT to outdoor unit screw connection 1 NOTICE It is recommended to install shut off valves to domestic cold water in and domestic hot water out connections These shut off valves are field supplied How...

Страница 10: ...e relief valve combination to the water mains inlet 7 Install the tundish part of the kit in a vertical position within a maximum of 600 mm away from the pressure reducing valve pressure relief valve...

Страница 11: ...200 thereafter Maximum permitted equivalent length of 22 mm pipework is 9 m Each bend or elbow is equivalent to 0 8 m of pipework 5 2 3 To connect the recirculation piping Prerequisite Only required i...

Страница 12: ...30 30 C 35 INFORMATION Protection against bursting the glycol will prevent the piping from bursting but NOT the liquid inside the piping from freezing Protection against freezing the glycol will preve...

Страница 13: ...7 Alarm output See 6 3 6 To connect the alarm output 418 Space cooling heating operation control See 6 3 7 To connect the space cooling heating ON OFF output 418 Changeover to external heat source con...

Страница 14: ...bizone kit 9 P Bizone kit for room thermostat wired or wireless In case of See Wireless room thermostat Installation manual of the wireless room thermostat Addendum book for optional equipment Wired r...

Страница 15: ...ower supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed ALWAYS connect the backup heater power supply and the...

Страница 16: ...OTICE Do NOT cut or remove the backup heater power supply cable 6 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zone and a combination of underfloor hea...

Страница 17: ...User interface panel 3 Upper switch box cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below A 6 5 4 3 S3S S2S B A B X5M 3 4 5 6 3 Fix the cable...

Страница 18: ...between X2M 7 9 and Q1L thermal protector backup heater Do NOT change 3 Fix the cable with cable ties to the cable tie mountings 6 3 7 To connect the space cooling heating ON OFF output Wires 2 1 0 75...

Страница 19: ...ppropriate terminals as shown in the illustration below A X1 X2 L N B A B A4P X2M X1 a X2 a Installation of EKRP1HBAA is required 3 Fix the cable with cable ties to the cable tie mountings 6 3 9 To co...

Страница 20: ...ermostat stop error 8H 03 will occur 6 3 11 To connect a Smart Grid This topic describes 2 possible ways to connect the indoor unit to a Smart Grid In case of low voltage Smart Grid contacts In case o...

Страница 21: ...K1A L N L N STEP 3 a b c d e f STEP 1 STEP 2 A1 A2 4 3 2 1 X10M K2A A1 A2 2 1 STEP 1 Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Sma...

Страница 22: ...o and know to configure the system after it is installed NOTICE This chapter explains only the basic configuration For more detailed explanation and background information see the installer reference...

Страница 23: ...ngs can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the user permi...

Страница 24: ...the user interface go to the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not Alternatively when Emergency is set to auto SH reduced DHW on spac...

Страница 25: ...n control feature to work properly When measuring the resistance value of each heater you can set the exact heater capacity and this will lead to more accurate energy data Backup heater type The backu...

Страница 26: ...hermostat Unit operation is decided by the external thermostat or equivalent e g heat pump convector Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human C...

Страница 27: ...ction function To set the heat pump ON hysteresis Code Description 5 9 6 00 Heat pump ON hysteresis 2 C 40 C Settings for Schedule only mode and Schedule reheat mode Comfort setpoint Only applicable w...

Страница 28: ...ailable for Main zone Heating Main zone Cooling Additional zone Heating Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpo...

Страница 29: ...define the setpoint mode To use the weather dependent curve you need to define the correct setpoint mode Go to setpoint mode Set the setpoint mode to Main zone Heating 2 4 Main zone Setpoint mode WD h...

Страница 30: ...menus The most important settings are presented here 7 4 1 Main zone Ext thermostat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external...

Страница 31: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Страница 32: ...nce guide The indoor unit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the...

Страница 33: ...start the measurement will be successful Before 30 min from start the measurement might be unsuccessful If the measurement is successful the logic to activate the backup heater will use a timeframe tu...

Страница 34: ...r to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system and what t...

Страница 35: ...ter coming out of the relief valve open the valve until the discharged water does NOT contain dirt anymore flush the system It is recommended to do this maintenance more frequently Pressure relief val...

Страница 36: ...Temperature and pressure relief valve Check for correct operation of the temperature and pressure relief valve Manually operate the temperature and pressure relief valve to ensure free water flow thr...

Страница 37: ...can thoroughly clean it Then you need to do as follows 10 6 1 To remove the water filter 437 10 6 2 To clean the water filter in case of trouble 438 10 6 3 To install the water filter 438 10 6 1 To r...

Страница 38: ...er housing and clean with water 4 Install the cleaned rolled up filter and strainer in the water filter housing INFORMATION Correctly install the strainer in the magnetic filter dirt separator housing...

Страница 39: ...B2L B f B f A Indoor unit B Field installed a1 Space heating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW...

Страница 40: ...eless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON OFF thermostat wired...

Страница 41: ...stic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat For safety thermostat For smartgr...

Страница 42: ...l kWh rate power supply installation Unit power supply 400 V or 230 V earth Only for normal power supply installation OUTDOOR UNIT STANDARD PART POWER SUPPLY WLAN module communication 5 core A20P J2 X...

Страница 43: ...VH16SU23EA6V 30 12 kW Primary flow rate to reach primary heating power input 15 l min Standing heat loss ETVH16SU18EA6V 1 35 kWh 24h ETVH16SU23EA6V 1 76 kWh 24h Model storage capacity mass of unit whe...

Страница 44: ...re set pressure of pressure reducing valve 3 5 bar Maximum primary working pressure heating 2 5 bar Maximum flow temperature 65 oC Expansion vessel pre charge pressure 3 5 bar Expansion valve setting...

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...4P644729 1E 2023 10 Copyright 2021 Daikin 4P644729 1 E 00000006 Verantwortung f r Energie und Umwelt...

Отзывы: