6 Electrical installation
Installation manual
13
ETV23E
Daikin Altherma 3 H HT F
4P644729-1E – 2023.10
6
Electrical installation
INFORMATION
This unit is a heating only model. Therefore, all references
to cooling in this document are NOT applicable.
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
CAUTION
Do NOT push or place redundant cable length into the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1
About electrical compliance
Only for the backup heater of the indoor unit
"6.3.2 To connect the backup heater power supply"
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Indoor unit:
Item
Tightening torque (N•m)
X1M
2.45 ±10%
X2M
0.88 ±10%
X5M
0.88 ±10%
X6M
2.45 ±10%
X10M
0.88 ±10%
M4 (earth)
1.47 ±10%
6.3
Connections to the indoor unit
Item
Description
Power supply (main)
See
"6.3.1 To connect the main power
14].
Power supply (backup
heater)
See
"6.3.2 To connect the backup heater
15].
Shut-off valve
See
"6.3.3 To connect the shut-off
16].
Electricity meters
See
"6.3.4 To connect the electricity
17].
Domestic hot water
pump
See
"6.3.5 To connect the domestic hot
17].
Alarm output
See
Space cooling/heating
operation control
See
"6.3.7 To connect the space cooling/
18].
Changeover to
external heat source
control
See
"6.3.8 To connect the changeover to
19].
Item
Description
Power consumption
digital inputs
19].
Safety thermostat
thermostat (normally closed
contact)"
Smart Grid
WLAN cartridge
cartridge (delivered as accessory)"
22].
Room thermostat
(wired or wireless)
See below table.
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Ext thermostat type
For the additional zone:
▪ [3.A]
Ext thermostat type
▪ [3.9] (read-only)
Control
Heat pump convector
There are different controllers and
setups possible for the heat pump
convectors.
Depending on the setup, you also
need to implement a relay (field
supply, see addendum book for
optional equipment).
For more information, see:
▪ Installation manual of the heat
pump convectors
▪ Installation manual of the heat
pump convector options
▪ Addendum
book
for
optional
equipment
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Ext thermostat type
For the additional zone:
▪ [3.A]
Ext thermostat type
▪ [3.9] (read-only)
Control
Remote outdoor
sensor
See:
▪ Installation manual of the remote
outdoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=1 (
External sensor
=
Outdoor
)
[9.B.2]
Ext. amb. sensor offset
[9.B.3]
Averaging time